• Title/Summary/Keyword: UPS inverter

Search Result 146, Processing Time 0.025 seconds

Development of the 300kVA Large Capacity IGBT UPS (IGBT를 적용한 300kVA급 대용량 무정전전원장치 개발)

  • Byun, Y.B.;Kim, T.J.;Joe, K.Y.;Park, S.J.;Kim, C.U.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07f
    • /
    • pp.2057-2059
    • /
    • 1998
  • In order to maintain a high quality output voltage, conventional UPS systems use complex filters with large passive components. To overcome this drawback, real time feedback control schemes have been invested. However, these techniques require a high inverter switching frequency to dynamically adapt to changing load conditions reduce harmonics of the output voltage, thereby rendering the system inadequate for high power applications. This paper presents real time digital signal processor(DSP) control of a large capacity UPS system feeding nonlinear loads to provide a sinusoidal inverter output voltage, unity input power factor, low bus voltage ripple, and excellent transient response.

  • PDF

Robust control of End order deadbeat current controller considering calculation time delay for UPS inverter (연산시간지연을 고려한 UPS 인버터용 2차 데드비트 전류 제어기의 강인 제어)

  • Kim, Byoung-Jin;Choi, Jae-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2000.07b
    • /
    • pp.1056-1058
    • /
    • 2000
  • Deadbeat technique has been proposed as a digital controller for an UPS inverter to achieve the fast response to a load variation and to conserve a very low THD under a nonlinear load condition. This scheme contains a fatal drawback, sensitivity against parameter variation and calculation time delay. This paper proposes a second order deadbeat current controller, which fundamentally solves the calculation time delay problem and certainly guarantees the robustness of the parameter's variation. This is shown theoretically and practically through simulation and experiment.

  • PDF

Control Method of the Three-phase VSI for 200KVA UPS (200KVA급 UPS용 3상 전압형 인버터의 제어기법)

  • Yu, B.W.;Lee, S.H.;Choi, J.H.;Choi, C.H.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07f
    • /
    • pp.2259-2261
    • /
    • 1997
  • In this paper, control scheme of the three phase VSI(Voltage Source Inverter) for 200KVA UPS is described. The proposed controller is designed to robust against parameter variations, disturbances and load change using PI controller. The switching pattern is determined to Ramp Comparison Method. The inverter provides pure sinusoidal output voltage with very low THD (Total Harmonic Distortion). Finally, the performance of the proposed inverter is shown by experimental result.

  • PDF

Real Time Digital Control of PWM Inverter for Uninterruptible Power Supply(UPS) application (무정전 전원공급장치 적용을 위한 PWM 인버터의 Digital 실시간 제어)

  • Min, Wan-Ki;Lee, Sang-Hun;Choi, Jae-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1999.11a
    • /
    • pp.56-60
    • /
    • 1999
  • This paper presents the high performance real time control system of PWM inverter for uninterruptible power supply(UPS). This system is based on a digital control scheme which calculates the pulse widths of the inverter switches for the next sampling time in digital signal processor(DSP). A PI compensator is used to eliminate the voltage error caused by the difference between the actual values of LC filter and those designed. Double regulation loops which are the inner current loop and the outer voltage loop are used to make the transient response time reduce in load disturbance and nonlinear load. This method makes it possible to obtain better response in comparison to conventional digital control system. The proposed scheme provides good performance such as stable operation, low THD of the output voltage, and good dynamic response for load variations and nonlinear load.

  • PDF

Inverter Control algorithm for UPS using Dead-Beat controller with disturbance Observer (외란 관측기와 Dead-Beat 제어기를 이용한 UPS 인버터 제어 알고리즘)

  • Jang, J.Y.;Song, J.H.;Choy, I.;Choi, J.Y.;Yoo, J.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07b
    • /
    • pp.1196-1198
    • /
    • 2000
  • In this paper, a new approach for digital feedback control of PWM inverter is proposed, in which an output DB(Dead-Beat) control is achieved combined with a simple disturbance observer. The deadbeat controller, which is constructed multiple loop control scheme for PWM inverter, is used for fast transient response. The disturbance observer can make the disturbances be cancelled by adding feedforward compensating loop in controller. The simulation result show the proposed control scheme can achieved good voltage regulation against large load variations.

  • PDF

Control Strategy of Resonant DC Link Inverter for UPS (UPS용 병렬공진형 직류링크인버터를 위한 제어방식에 관한 연구)

  • Beak, J.W.;Yoo, D.W.;Min, B.G.;Ryu, S.P.
    • Proceedings of the KIEE Conference
    • /
    • 1994.11a
    • /
    • pp.159-161
    • /
    • 1994
  • A new control technique which generates high-quality sinusoidal output voltage from a single-phase resonant do link inverter suitable for the UPS systems is presented. The inverter output voltage control system has the PID controller with a minor loop of the filter inductor current and tile feedforward controller. The proposed control scheme also solves resonant voltage overshoot without any additional switch or passive component, resulting in pulses with uniform amplitude and high efficiency. Experimental results in the case of linear and nonlinear loads are presented to confirm the usefulness of the Proposed control algorithms.

  • PDF

Robust Voltage Controller of Single-Phase Inverter for UPS (무정전전원장치용 단상인버터의 강인한 전압제어기)

  • Ku, Dae-Kwan;Ji, Jun-Keun;Cha, Gueesoo;Moon, Jun-Hee
    • Proceedings of the KIPE Conference
    • /
    • 2010.11a
    • /
    • pp.298-299
    • /
    • 2010
  • In this paper a robust voltage controller of single-phase inverter for UPS is presented. The voltage controller is designed using ${\mu}-based$ robust control scheme to simultaneously guarantee robust stability and robust tracking performance in presence of filter and load parameter variations. Firstly the robust performance of the resulting controller is theoretically confirmed via ${\mu}-analysis$. Then simulation results for single-phase inverter system with linear and nonlinear loads demonstrate feasibility of the proposed control method providing improved performance - good regulation and fast dynamic response.

  • PDF

Bilateral Series Resonant Inverter for High Frequency Link UPS (고주파 링크 무정전 교류 전원장치를 위한 직렬 공진형 인버어터)

  • 신봉수;정용호;조규형
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.38 no.7
    • /
    • pp.524-538
    • /
    • 1989
  • A new bilateral series resonant inverter and its control method are proposed. The proposed inverter consists of zero current switched cycloconverter. Output voltage is regulated by modulating the average magnitude of resonant current sinusoidally. Cycloconverter synthesizes low frequency output voltage from high frequency resonant current pulses. In the proposed inverter, bidirectional power flow in possible and isolation transformer is miniaturized. The proposed control method is verified through simulation and experiment. The proposed inverter will satisfy the small size and low cost requirements of small Uninterruptible Power Supply (UPS) of less than 1 KVA suitable for micro-computers and electronic equipments used in office and home automation.

A Study on the Particular Harmonics Elimination in VSI-FED Induction Motor (전압형 인버터로 구동되는 유도전동기의 특정고조파제거에 관한 연구)

  • 전희종;김국진
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.2 no.2
    • /
    • pp.64-70
    • /
    • 1988
  • In many applications of inverter system, it is desirable to obtain an AC output voltage with variable frequency and amplitude. For the variable-speed AC motor drive, the system is one major area of application for the variable-frequency inverter. V ariable~voltage variable-frequency sinusoidal output in three-phase inverter is possible by employing the techniques developed. In this paper, the technique of particular harmonics elimination(PHE) in three-phase PWM inverter-output waveforms is introduced. The required switching patterns are determind on personal computer. Results are stored in look-up table in EPROM and used to control the switching of the inverter devices. The experimental results indicate that the loss in an induction motor is minimized to a degree by using this algorithm. The proposed PWM pattern is effective not only to the induction motor but also to the other electromagnetic machine such as Voltage Regulator, UPS.

  • PDF

Characteristic analysis of input and output filter for UPS system (무정전전원장치용 입출력 필터 특성 분석)

  • Lee Dong Ju;Jung Seok Un;Lee Kyung Seok
    • Proceedings of the KIPE Conference
    • /
    • 2004.07b
    • /
    • pp.803-806
    • /
    • 2004
  • In this paper, configuration of prototype 300kVA UPS system with unity input power factor is briefly described and a various types of rectifier for UPS application are discussed. Input LCL filter for PWM rectifier and output LC filter for PWM inverter are designed as a prototype and their principal characteristics are discussed.

  • PDF