• 제목/요약/키워드: UHF method

검색결과 176건 처리시간 0.026초

가스절연개폐장치용 UHF 부분방전검출장치의 새로운 감도 측정방법 (A Novel Sensitivity Verification Method for the UHF Partial Discharge Detection System in Gas Insulated Switchgear (GIS))

  • 구선근;박기준;윤진열
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권9호
    • /
    • pp.450-455
    • /
    • 2001
  • We proposed a new sensitivity verification method for the UHF partial discharge(PD) detection system. Initially, we measure the UHF power induced by 5 pC PD which takes place near UHF sensor. Subsequently, we inject the swept UHF signal from a network analyzer into the GIS and measure the attenuation of the signal along the 71S Both the UHF power by 5 pC PD and the attenuation make it possible to verify the sensitivity and spatial coverage of the PD detection system. This method doesn\`t require the calibration of injected pulse type UHF signal into the GIS and makes us precisely measure the attenuation in frequency domain.

  • PDF

UHF법 부분방전 진단기법에 의한 가스절연 개폐장치의 성능검증 (Performance Verification of Gas Insulated Switchgear using UHF Partial Discharge Diagnosis Method)

  • 김정배;박경수;송원표;김덕수;김종화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.37-39
    • /
    • 2002
  • UHF method is very effective to diagnosis for partial discharge of GIS. In generally, inner UHF sensor can be attached on sheath cover of GIS under construction for periodic inspection. However, there is no inner UHF sensor for GIS of the domestic substation. We used the outer UHF sensor attached on spacer for GIS of existing substation. In this paper, we report the diagnosis result of partial discharge on 800kV GIS in domestic substation. From these results, we can find the quantity, reason and location of PD and certificate the performance of UHF method for partial discharge diagnosis of GIS.

  • PDF

실버잉크와 점퍼구조를 사용한 신용카드 크기의 UHF & HF RFID 태그 안테나 (UHF & HF RFID Credit Card Size Tag Antenna Designs Using Silver-Ink and Jumper Structure)

  • 남세현;정유정
    • 한국전자파학회논문지
    • /
    • 제27권11호
    • /
    • pp.972-977
    • /
    • 2016
  • 본 논문에서는 920 MHz UHF(Ultra High Frequency) 대역과 13.56 MHz HF(High Frequency) 대역의 RFID 태그 안테나가 PE film에 단면에 프린트된 이중대역 태그를 설계하는 과정과 그 결과를 보여준다. 태그의 전체 크기는 일반 신용카드의 크기인 $80mm{\times}50mm$이고, 가장자리에 UHF 태그 안테나가 $76mm{\times}44mm$로 카드 크기보다 조금 작게 설계되었다. HF 대역 태그는 UHF 태그의 중앙에 $40 mm{\times}42 mm$ 크기로 상호작용을 감안하여 설계되었다. 단면에 실버잉크 Printing 기법으로 일반적인 HF용 태그와 다르게 Via를 사용하지 않고, 단면에 PE Film 위에 프린트를 한 후에 Jumper를 추가함으로써 HF 대역용 Loop 안테나와 UHF 태그와 같은 면에 설계하였다. 인식거리는 UHF 대역에서 약 6 m로 장거리에서 인식이 가능하고, HF 대역에서는 5 cm 이상으로써 두 개의 대역에서 사용이 가능한 태그로서 물류와 검증용으로 사용이 가능하다.

공기중 부분방전에 대한 PRPD측정법과 UHF센서측정법의 비교분석 (Comparative analysis of PRPD method and UHF sensor method for Partial Discharge in air)

  • 이강원;이용희;박성희;장동욱;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집 Vol.3 No.2
    • /
    • pp.882-885
    • /
    • 2002
  • Assessing the condition of air insulation by measuring electromagnetic wave generated in it by partial discharges gives warning of developing faults and breakdown which may give some bad effects to other thing concerned with it. Electromagnetic wave are taken from UHF antenna with 20k ~ 2GHz frequency range. The signal waveform and FFT(Fast Fourier Transform) results from UHF antenna for PD(partial discharge) generated from two different electrode(needle-plane, needle-needle) configurations are shown and it is processed by using PRPD($\Phi-q-n$ distribution) method. Cumulative pulse sequence during 100 period is compared with PRPD method. This also will show the possibility of making apparent distinction between two PD sources.

  • PDF

UHF 기술을 응용한 전력용 변압기의 PD 모니터링 (PD Monitoring of Transformer Using UHF Technique)

  • 최용성;황종선;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2116-2117
    • /
    • 2008
  • This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

  • PDF

가스절연 개폐장치의 내부절연 성능검증을 위한 UHF 협대역 부분방전 진단법 (UHF Narrow Band Type Partial Discharge Diagnosis Method for the Internal Insulation Performance Verification of the Gas Insulated Switchgear)

  • 송원표;김정배;김민수;정재룡;박승재;고희석
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권9호
    • /
    • pp.414-420
    • /
    • 2005
  • A method for partial discharge diagnosis based on UHF narrow band type for GIS has been developed and calibrated. In generally, PD cannot be directly measured under on-line condition, but we can indirectly measure the electromagnetic wave made by PD using the high-frequency antenna. Compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise in high-voltage substation. Therefore, we can detect the real abnormality with several pC in GIS using UHF narrow-band type method. For the case of no internal VHF sensor for GIS of the domestic substation, it has applied to use the external UHF sensor attached in spacer in GIS of existing substation. In this paper, we firstly described the technique of partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity test, the relationship of dBm-pC and diagnosis result of the cause of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on the real GIS in domestic substation. These results make above method applicable for measurement of quantity and cause of PD for real operation GIS in high-voltage substation.

UHF 가술을 이용한 온라인 PD 모니터링 (On-line PD Monitoring Using UHF Technique)

  • 최용성;이경섭
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 춘계학술대회 논문집 센서 박막재료연구회 및 광주 전남지부
    • /
    • pp.115-118
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers. is designed, which has been installed inside the oil tank of a transformer by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

  • PDF

UHF 기술을 이용한 온라인 부분방전 모니터링 (On-line Insulation Diagnostic by PD Monitoring Field Practical of UHF Technique for On-line PD Monitoring)

  • 오용;최용성;황종선;이경섭
    • 전기학회논문지P
    • /
    • 제57권2호
    • /
    • pp.176-180
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers is designed, which has been installed inside the oil tank of transformer in a substation by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

UHF센서를 이용한 가스절연송전선로 절연파괴 위치 추정에 관한 연구 (A Study on Estimation of Breakdown Location using UHF Sensors for Gas Insulated Transmission Lines)

  • 박흥석;한상옥
    • 전기학회논문지
    • /
    • 제60권4호
    • /
    • pp.805-810
    • /
    • 2011
  • This paper deals with the method and algorithm used to find fault locations in gas insulated transmission line. The method uses UHF sensors and digital oscilloscope to detect discharge signals emitted to the outside through insulating spacer in the event of breakdown inside GIL. UHF sensors are the external type and installed at outside of insulating spacers of GIL. And we used wavelet signal processing to analyze the discharge signals and confirm the exact fault location findings in the GIL test line. This method can overcome demerit of TDR(Time Domain Reflectometer) method having been applied to detect fault location for conventional underground transmission lines, and Ground Fault Sensors used in conventional GIS systems. TDR method requires high level of specialty and experience in analyzing the measured signals. Ground fault sensors are installed inside GIL and can be destroyed by high transient voltage. This paper's method can simplify the fault location process and minimize the damage of sensors. In addition, this method can estimate the fault location only by the time difference when discharge signals are arrived to detecting sensors at the ends of GIL sections without reasons of breakdown. To test the performance of our method, we installed sensors at the ends of test line of GIL(84m) and sensed discharge signals occurred in GIL, energized with AC voltage generator up to 700kV.

UHF RFID 태그 칩의 임피던스 산출 불확실성 제거를 위한 모델링 방법 (Modelling Method for Removing Measurement Uncertainty in Chip Impedance Characterization of UHF RFID Tag IC)

  • 양진모
    • 한국전자파학회논문지
    • /
    • 제25권12호
    • /
    • pp.1228-1235
    • /
    • 2014
  • UHF RFID 태그를 설계하기 위해서는 태그 칩의 입력 임피던스 값이 필요하다. 입력 임피던스 산출에는 직접측정 방법이 보편적으로 사용되고 있다. 본 연구에서는 이 방법을 사용할 경우, 칩을 측정장치에 연결하기 위해 도입되는 픽스쳐에서 발생되는 문제점을 분석하고, 그 결과를 확인하였다. 이 문제를 근본적으로 피해갈 수 있는 대안으로 모델링 방법을 제안하고, 실험을 통해 타당성과 정확도를 확인하였다.