• Title/Summary/Keyword: Transmission Line Method

Search Result 1,065, Processing Time 0.027 seconds

A Study on Estimation of Breakdown Location using UHF Sensors for Gas Insulated Transmission Lines (UHF센서를 이용한 가스절연송전선로 절연파괴 위치 추정에 관한 연구)

  • Park, Hung-Sok;Han, Sang-Ok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.4
    • /
    • pp.805-810
    • /
    • 2011
  • This paper deals with the method and algorithm used to find fault locations in gas insulated transmission line. The method uses UHF sensors and digital oscilloscope to detect discharge signals emitted to the outside through insulating spacer in the event of breakdown inside GIL. UHF sensors are the external type and installed at outside of insulating spacers of GIL. And we used wavelet signal processing to analyze the discharge signals and confirm the exact fault location findings in the GIL test line. This method can overcome demerit of TDR(Time Domain Reflectometer) method having been applied to detect fault location for conventional underground transmission lines, and Ground Fault Sensors used in conventional GIS systems. TDR method requires high level of specialty and experience in analyzing the measured signals. Ground fault sensors are installed inside GIL and can be destroyed by high transient voltage. This paper's method can simplify the fault location process and minimize the damage of sensors. In addition, this method can estimate the fault location only by the time difference when discharge signals are arrived to detecting sensors at the ends of GIL sections without reasons of breakdown. To test the performance of our method, we installed sensors at the ends of test line of GIL(84m) and sensed discharge signals occurred in GIL, energized with AC voltage generator up to 700kV.

A Study on the Improvement of Data Transmission Method of PORT-MIS (항만운영정보시스템의 데이터전송방식 개선에 관한 연구)

  • 김칠호;박남규;최형림
    • Journal of Korean Port Research
    • /
    • v.14 no.2
    • /
    • pp.133-142
    • /
    • 2000
  • In order to streamline the procedure of data transmission in port and logistics industries, MOMAF introduced EDI systems as the method of data transmission of 19 documents 5 years ago. While operating EDI system, MOMAF has found the inconvenience and the inefficiency of using EDI systems in the field of requesting fast response. This thesis focuses on finding the possible fields of on-line processing system. The result of the paper presents that if data transmission area such as 'application for pilot'is changed to on-line processing method, the processing cost and time will be reduced compared with EDI processing method.

  • PDF

A study on effective sending of moving picture from train accident site (철도 사고현장의 효율적인 동영상 전송 방안에 관한 연구)

  • Cho, B.K.;Chang, S.G.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10b
    • /
    • pp.289-291
    • /
    • 2003
  • Railway takes an important role of transporting massive passenger and freight. Accidents which occur related to trains have a risk of serious loss of lives, so those accidents need to be controlled urgently Therefore moving picture transmission system is required which transmits exact information of moving picture of accident status to CTC and also communication line is also required with it. By using WTB line as a wayside transmission line, railway telephones, fax and train service information are provided to local offices. As transmission line improving project, optical cabling work is being processed by phases. Therefore optical fiber line is more effective way for a communicating way between stations than coaxial transmission line. This Paper considers connecting method when optical fibers is used for moving picture data transmission of train accidents and its problems.

  • PDF

A Design for Dynamic Line Rating System to increase Overhead Transmission Line Capacities (가공송전선의 송전용량을 증가시키기 위한 동적송전용량 시스템의 설계)

  • Kim, Sung-Duck
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.7
    • /
    • pp.72-77
    • /
    • 2011
  • Dynamic Line Rating (DLR) techniques have been greatly worthy of notice for efficiently increasing transmission capacity as well as controlling load-flow in overhead transmission lines, in comparison with the existing power system operating with Static Line Rating (SLR). This paper describes an utilization method to implement DLR control system for old transmission lines built in the first stage using the ground clearance design standard with lower dips. The suggested DLR system is focused on designing as temperature control system rather than current/load control system. Based on several performance for conductor temperatures, it is shown that DLR system with efficiency can be implemented.

An Analysis of Transmission Line Structure by Combining Image Mode and Galerkin Methods (영상-모드 및 Galerkin법을 이용한 전송선 문제 해석)

  • 신규현;정현교;한송엽
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.40 no.12
    • /
    • pp.1296-1301
    • /
    • 1991
  • This paper presents a hybrid image mode Galerkin method for the analysis of the transmission line structures suspended between infinite parallel ground planes. A Green's function that consists of numerically accelerated image mode terms is developed, which is used in boundary integral equation. Transmission lines of arbitrary cross section are analyzed using Galerkin's method. Two kinds of configurations of transmission lines are studied in sample problems.

  • PDF

A LOSSY LINE DISTRIBUTED PARAMETERS CALCULATION USING DATA OF OPEN-SHORT IMPEDANCE MEASURING METHOD (Open-Short 방식의 임피던스 측정에 의한 분포정수의 보정)

  • ANANIEV, Igor P.;Joe, Ki-Yeon;Byun, Young-Bok;Seo, Jeong-Il;Kim, Eun-Soo;Kim, Tae-Jin
    • Proceedings of the KIEE Conference
    • /
    • 1999.07f
    • /
    • pp.2553-2555
    • /
    • 1999
  • The paper contains design formulas and an execution algorithm for calculation of distributed parameters as well as wave and impedance parameters of a uniform transmission line using data of the line input impedance measurements by the OPEN-SHORT method. In difference from published before works on the OPEN-SHORT method application for line parameters determination, in which the lines with small losses are considered /1-3/, the obtained formulas allow to calculate parameters of transmission lines with arbitrary losses. It opens new possibilities of the OPEN-SHORT method utilization for development and application of the probe - type lossy dielectric media parameters meters based on transmission lines, including probe-type moisture material meters.

  • PDF

An Extended TRL Calibration Method (확장된 TRL 오차 수정 방법)

  • Kim Yusin;Lee Chang-Seok
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.16 no.11 s.102
    • /
    • pp.1099-1105
    • /
    • 2005
  • TRL error correction method is widely used for measuring high frequency device mounted on PCB. In order to correct error more precisely, the characteristic impedance of standard transmission line should be known mounted for error correction. The capacitance per the unit length of transmission line is calculated by using standard transmission line which terminate resistor additionally at previous method and the characteristic impedance of standard transmission line is calculated with fitting method according to frequency, but the characteristic impedance extracted by a manufacturing inaccuracy is influenced. In this study, a novel method can reduce the manufacturing inaccuracy using measured s-parameters and can extract more accurate characteristic impedance than the previous method.

Analysis of Electromagnetic Pulse Coupling to Twisted Cable Using Chain Matrix (Chain Matrix를 이용한 Twisted Cable의 EMP(Electromagnetic Pulse) 결합 해석)

  • Cho, Jea-Hoon;Lee, Jin-Ho;Kim, Hyeong-Dong
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.21 no.7
    • /
    • pp.734-743
    • /
    • 2010
  • In this paper, we analyzed the EMP coupling for the nonuniform transmission lines, such as twisted cables, using the chain matrix algorithm and the multi-conductor analysis. The BLT method is widely used for the EMP coupling analysis of the transmission line, however, it is difficult to apply to the nonuniform transmission lines. In order to analyze the EMP coupling of nonuniform transmission lines, the whole nonuniform transmission line is divided into incremental uniform line sections of the finite numbers, and the coupling in each small sections is now summed up to get the EMP coupling effect of the entire nonuniform transmission line. To verify the proposed EMP coupling analysis method, the result of the EMP coupling simulation is compared with the solution of BLT equations for a uniform transmission line case. The proposed method is applied to the twisted cable over ground in case of being illuminated by the HEMP in order to analyze the EMP coupling.

A Study on Overvoltage Reduction Method of Single Point Bonded Section on Combined Transmission Lines (혼합송전선로 편단접지 구간 과전압 저감 방안에 관한 연구)

  • Jung, Chae-Kyun;Kang, Ji-Won;Park, Hung-Sok;Kim, Jin
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.1881-1887
    • /
    • 2009
  • This paper discusses the effects of ECC (Earth Continuity Conductor) for reducing the level of induced sheath overvoltages at the single point bonded section of combined transmission lines which are mixed underground power cable with overhead line in one T/L. In previous papers, the characteristics of ECC on only underground power cable systems were sufficiently analyzed. However, the result of only underground power cable systems are totally different from that of combined transmission lines because ECC is commonly grounded with overhead grounding wire at mesh of cable head. Therefore, in this paper, the installation effects of ECC have been variously analyzed considering the three kinds of fault positions, cable formation of duct and trefoil, spacing between phase conductor and ECC, and the change of overhead transmission line section length on 154kV combined transmission line. Finally, simulation results show that ECC can effectively reduce the induced sheath voltage.

Analysis of Electrical Safety Level Test for Barehand Work at 765kV Vertical Double Circuit Six Bundle Conductors on the Suspension String Tower Type (765kV 수직2회선 6도체 현수형 철탑에서 직접활선작업의 안전성 평가분석)

  • Kim, Dae-Sik;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.3
    • /
    • pp.275-278
    • /
    • 2008
  • It has been issued that the necessity of Live line work for 765kV vertical double circuit six bundle conductors transmission line when the characteristics of transmission line, the composition of T/L and near the T/L circumstances etc. Others are considered. The Barehand method of UHV T/L is extremely dangerous work and especially it is directly related with lineman life so it is very dangerous. It should be performed several technology developments for live-line work on the UHV T/L, that should be considered such as the electrical influence on workers near the T/L, development of live-line facilities, guarantee of safety, the technical rules of live-line work, the safe method of live-line work and etc. In order to maintain the 765kV transmission lines safely by barehand work, first of all, we should know the analysis of electrical safety level test in live-line work at 765kV vertical double circuit six bundle conductors on the suspension string tower type.