• Title/Summary/Keyword: Transformer Protection

Search Result 206, Processing Time 0.028 seconds

전압 불안정시 PSS/E 사용자 정의모델로 구현된 거리계전기 응동 특성 (Operating Characteristic of a User Defined Distance Relay Model in PSS/E during Voltage Instability)

  • 이동규;강상희;양정재;오화진;장병태
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.82-84
    • /
    • 2003
  • This paper presented a method to develop a relay model by the user-written model function of PSS/E. As for the voltage instability, although generator current limiters, transformer's tap-changers and dynamic loads have been considered as the dominant components, the protection system is also very important because it may influence the system's dynamic behaviour. Hence a distance relay model implemented with the suggested method was added, and then the operating characteristics of the distance relay under the voltage instability condition were investigated.

  • PDF

풀브리지 DC-DC 컨버터의 도전손실과 스위칭 스트레스를 저감한 전원장치 개발 (Development of the Power Supply with Reduced Conduction Loss and Switching Stress on the Full-Bridge DC-DC Converter)

  • 라병훈;송대현;김광태;이현우
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2001년도 전력전자학술대회 논문집
    • /
    • pp.608-611
    • /
    • 2001
  • This paper is indicating the problems, which are the conduction loss on the high frequency transformer, the protection of rectification diode as the snubber loss and the stress of switching main devices, as be made high current and high speed in the phase-shift switching full-bridge DC-DC converter is used the power supply's main circuit of high capacity. In this paper, to improve those problems, it is proposed that is the resonant circuit auxiliary can be reduced conduction losses and stabilized output control. And, it is constructed prototype of the power supply as the result of computer simulations.

  • PDF

배전용 변압기 고압측으로의 뇌서지 전파 (Propagation of Lightning Surges toward primary Side of Distribution Transformer)

  • 이복희;이수봉;김병근;이승칠;이동문;정동철
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2003년도 학술대회논문집
    • /
    • pp.269-272
    • /
    • 2003
  • The importance of the improving quality of electric power is being strongly raised, owing to an increasing use of sensitive and small-sized electronic devices and system. The transient overvoltage on low-voltage AC power distribution system are induced by direct or indirect lightning return strokes, and those can cause damage and/or malfunction of the utility system for borne automation, office automation and factory automation as well as medical equipments. The behavior of lightning surge transferred to the primary side from the primary side in distribution transformers were experimentally investigated the protection effect of low voltage SPD installed at the secondary side of distribution transformers was analyzed.

  • PDF

반도체 스위치기반 펄스전원 기술 개발 및 응용 (Solid State Pulsed Power Modulator and Its Application)

  • 류홍제;장성록
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2015년도 전력전자학술대회 논문집
    • /
    • pp.193-194
    • /
    • 2015
  • In this paper, the solid state pulsed power modulator developed in KERI, which is based on IGBT technologies are overviewed. During last ten years, several kinds of solid state modulators were developed in KERI such as IGBT stacks with step up transformer, full IGBT stack based marx generator, modified IGBT marx generator and high repetitive solid state modulator. Basic principle of the design is described and each pros and cons are compared. KERI's solid state pulsed power modulators has lot of advantages for industrial pulsed power application focused on everlasting life cycle and high repetitive, and shows superior arching protection ability.

  • PDF

반도체 소자기반 펄스 전원용 게이트 구동 및 시험회로 설계 (Design of gate driver and test circuits for solid-state pulsed power modulator)

  • 공지웅;옥승복;안석호;장성록;류홍제
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2012년도 전력전자학술대회 논문집
    • /
    • pp.230-231
    • /
    • 2012
  • This paper describes a gate driver that operates numerous semiconductor switch in the solide-state pulsed power modulator. the proposed gate driver is designed to receive both the isolated drive-power and the on/off pulse signals through the transformer. Moreover, the IGBT-switch can be quickly turned off by adding protection circuit. Therefore it protects the IGBT-switch from the arc condition that frequently occurs in high-voltage pulse application. To comprehend operating characteristic of each IGBT-switch in pulse output condition, the device consisting of a high efficiency soft-switching capacitor charger and two series stacking IGBT-switch is developed. Finally, the relability of the proposed gate driver and the device for its test are proved through PSpice simulation and experiments.

  • PDF

전력용변압기보호를 위한 개선된 수치계전기법 (Advanced Numerical Relaying for Power Transformer Protection)

  • 박철원;신명철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.217-219
    • /
    • 2004
  • The second harmonic component could be decreased by magnetizing inrush when there have been changes to the material of the iron core or its design methodology. The higher the capacitance of the high voltage status and underground distribution, the more the differential current includes the second harmonic during the occurrence of an internal fault. Therefore, the conventional second harmonic-restrained RDR needs modification. This paper describes an advanced numerical algorithm that utilizes terminal voltage, differential current harmonics, harmonic ratio, and flux-differential current slope. Based on the results of testing with WatATP99 simulation data, the proposed algorithm was proven to be faster and more reliable.

  • PDF

특고압 가스 절연 부하 개폐기의 통합형 대전력 시험 방법 및 회로 구성에 관한 연구 (A Study on the Construction of Test circuit and Unification of Experiment Method for High Voltage Gas-insulated Load Switch using High Power Testing System)

  • 정흥수;김민영;김준석
    • 조명전기설비학회논문지
    • /
    • 제22권12호
    • /
    • pp.36-46
    • /
    • 2008
  • 본 논문은 대전력시험설비를 이용한 특고압 가스 절연 부하 개폐기의 대전력 시험회로의 구성과 통합형 시험 방법에 관하여 연구하였다. 대전력시험설비는 전기기기의 전기적 및 기계적인 성능을 검증하는 설비로서 단락발전기, 보호차단기, 투입스위치, 임피던스, 고압변압기, 저압변압기, 측정 및 보호시스템 등으로 구성되며, 이 시스템을 이용하여 단시간전류시험, 전류개폐용량시험, 단락투입 및 차단시험 등을 실시한다. 특고압 가스 절연 부하 개폐기의 규격으로는 국내 배전계통에 적용되는 ES(한국전력공사 표준규격) 5925-0002가 있으며, 국제 규격으로는 IEC 60265-1, 62271-1 및 IEEE C 37.74 등이 있다. 본 논문에서는 여러 규격에 각각 규정되어 있는 시험 절차, 시험회로 구성 및 시험 방법 등을 통합하여 600[MVA]급 대전력 시험설비에 적용하였다.

Structural health monitoring data anomaly detection by transformer enhanced densely connected neural networks

  • Jun, Li;Wupeng, Chen;Gao, Fan
    • Smart Structures and Systems
    • /
    • 제30권6호
    • /
    • pp.613-626
    • /
    • 2022
  • Guaranteeing the quality and integrity of structural health monitoring (SHM) data is very important for an effective assessment of structural condition. However, sensory system may malfunction due to sensor fault or harsh operational environment, resulting in multiple types of data anomaly existing in the measured data. Efficiently and automatically identifying anomalies from the vast amounts of measured data is significant for assessing the structural conditions and early warning for structural failure in SHM. The major challenges of current automated data anomaly detection methods are the imbalance of dataset categories. In terms of the feature of actual anomalous data, this paper proposes a data anomaly detection method based on data-level and deep learning technique for SHM of civil engineering structures. The proposed method consists of a data balancing phase to prepare a comprehensive training dataset based on data-level technique, and an anomaly detection phase based on a sophisticatedly designed network. The advanced densely connected convolutional network (DenseNet) and Transformer encoder are embedded in the specific network to facilitate extraction of both detail and global features of response data, and to establish the mapping between the highest level of abstractive features and data anomaly class. Numerical studies on a steel frame model are conducted to evaluate the performance and noise immunity of using the proposed network for data anomaly detection. The applicability of the proposed method for data anomaly classification is validated with the measured data of a practical supertall structure. The proposed method presents a remarkable performance on data anomaly detection, which reaches a 95.7% overall accuracy with practical engineering structural monitoring data, which demonstrates the effectiveness of data balancing and the robust classification capability of the proposed network.

가전기기용 직류전원 모듈 설계 및 신뢰성 특성 해석 (Design and Reliability Evaluation of 5-V output AC-DC Power Supply Module for Electronic Home Appliances)

  • 모영세;송한정
    • 한국산학기술학회논문지
    • /
    • 제18권4호
    • /
    • pp.504-510
    • /
    • 2017
  • 본 논문은 소형 가전기기를 위한 AC DC 파워모듈 설계를 제시하고 효율과 신뢰성 및 안정성 특성을 나타낸다. 제안하는 파워모듈은 PCB 테스트보드에서 PWM 제어 IC 칩, 파워모스 소자, 트랜스포머, 각종 수동소자 (저항, 커패시터, 인덕터)를 사용하여 제작하였다. 본 논문에서 제시한 AC DC 파워모듈 회로 시뮬레이션 결과를 토대로 측정한 실험에서 입력전압은 상용전원 전압 220 V (RMS), 주파수 60 HZ의 교류전압(VAC : Voltage alternating current)을 사용 하였으며, 출력전압, OCP (over current protection), EMI(electromagnetic interference), PWM 신호 펄스, 효율 측정, 패키징 여부에 따른 발열측정 등을 실시하였다. 또한 파워모듈의 온도에 따른 특성변화와 트랜스포머 기준으로 1차측의 회로와 2차측 회로의 절연상태 확인을 하기 위한 내전압 테스트 등의 신뢰성테스트를 실시하였다. 효율 및 신뢰성 측정결과, AC DC 파워 모듈이 5 V의 출력전압, 200 mV의 리플, 약 73 %의 효율, 온도 약 $80^{\circ}C$ 까지 안정적으로 동작함을 확인하였으며, 4.2 kV의 크기로 60초 동안 견디는 내압 성능을 보였다.

태양광전원이 연계된 고압배전선로의 보호협조 평가 방안에 관한 연구 (Evaluation Method for Protection Coordination of PV Systems Interconnected with Primary Feeders)

  • 김병기;김소희;유경상;노대석
    • 한국융합학회논문지
    • /
    • 제2권4호
    • /
    • pp.29-37
    • /
    • 2011
  • 종래의 배전계통에 있어서의 전력조류는 변전소에서 선로말단을 향한 단 방향이었지만, 신에너지전원(분산전원)이 연계된 배전계통의 경우에는 그 출력용량의 여부에 따라 양방향의 전력조류가 발생할 가능성이 있어, 계통운용상 여러 가지의 문제점이 야기될 수 있다. 분산전원은 대규모전원의 보완적 역할과 배전선로 상의 국부적 부하 감당 역할을 부과하여 그의 적극적 활용을 꾀하기 위해서는, 분산전원으로부터 배전계통에 전력을 공급하는 역 조류의 기능을 허용할 수 있는 양방향 보호협조방식의 체제를 확립할 필요가 있다. 따라서 본 연구에서는 분산전원 연계에 따른 보호협조 기본 방안과 부하절체 운전에 따른 보호협조 방안, 변압기결선에 따른 보호협조 방안 등에 대한 알고리즘을 제시하였다. 또한, 이론적인 계산법(대칭좌표법)과 MATLAB/SIMULINK에 의하여 실 계통에서의 양방향 보호협조에 관련된 문제점을 분석하고, 해결방안을 제시하였다.