• Title/Summary/Keyword: Transformer Oil-paper

Search Result 235, Processing Time 0.024 seconds

A Fault Diagnosis Method of Oil-Filled Power Transformers Using IEC Code based Neuro-Fuzzy Model (IEC 코드 기반의 뉴로-퍼지모델을 이용한 유입변압기 고장진단 기법)

  • Seo, Myeong-Seok;Ji, Pyeong-Shik
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.65 no.1
    • /
    • pp.41-46
    • /
    • 2016
  • It has been proven that the dissolved gas analysis (DGA) is the most effective and convenient method to diagnose the transformers. The DGA is a simple, inexpensive, and non intrusive technique. Among the various diagnosis methods, IEC 60599 has been widely used in transformer in service. But this method cannot offer accurate diagnosis for all the faults. This paper proposes a fault diagnosis method of oil-filled power transformers using IEC code based neuro-fuzzy model. The proposed method proceeds two steps. First, IEC 60599 method is applied to diagnosis. If IEC code can't determine the fault type, neuro-fuzzy model is applied to effectively classify the fault type. To demonstrate the validity of the proposed method, experiment is performed and its results are illustrated.

Ultrasonic-detection characteristics of optical-fiber sensor for insulation diagnosis (절연진단용 광섬유 센서의 초음파 검출특성)

  • Lee, S.H.;Sim, S.H.;Lee, K.S.;Kim, D.W.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11a
    • /
    • pp.183-186
    • /
    • 2002
  • It is well known that a discharge in oil is the source of various physical and chemical phenomena. One of them is ultra-sonic wave, and its detection is a useful method to the diagnosis of the transformer insulation condition. Conventionally, ultra-sonic waves are detected by Piezo-electric trans-ducer(PZT), and we use optical method that has many advantages. In this paper, we constructed a Mach-Zehnder interferometer with optical fiber and investigated the principle of operation. Test of the ultrasonic-detecting ability was performed for both of PZT and fiber-optic sensor. Discharge test arrangement is based on the needle-plane electrode system in oil and applied AC high voltage. Ultrasonic waves were detected and showed time-delay characteristics. We analyzed the data with frequency domain and wavelet transform.

  • PDF

Comparative Study on Conductivity and Moisture Content Using Polarization and Depolarization Current (PDC) Test for HV Insulation

  • Jamail, N.A.M.;Piah, M.A.M.;Muhamad, N.A.;Kamarudin, Q.E.
    • Transactions on Electrical and Electronic Materials
    • /
    • v.15 no.1
    • /
    • pp.7-11
    • /
    • 2014
  • The Polarization and Depolarization Current (PDC) measurement is an efficient and effective diagnostic technique based on time domain measurement, for evaluating the high voltage insulation condition. This paper presents a review and comparison results from several published papers on the application of the PDC method to finding the conductivity and moisture content of various types of insulators. For solid insulation, the study was focused on cable insulation, electric machine stator insulation, and paper insulator in transformer insulation with different conditions. For liquid insulation, the review and comparison was done on biodegradable and mineral transformer oils, with fresh oil condition, and aged condition. The results from previous researchers tests were complied, analyzed and discussed, to evaluate the application of the PDC method to monitor the conductivity and moisture of HV equipment insulation systems. From the review results, the PDC technique successfully gives an indication of the conductivity and moisture level of high voltage insulation.

Research of Tan$\delta$ Measurement on Pole Transformers using DSP (DSP를 이용한 주상변압기 유전정접 측정기법 연구)

  • 김재철;이보호;김언석;최도혁;이수길
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.11 no.2
    • /
    • pp.110-118
    • /
    • 1997
  • This paper describes the dissipation factor measuring techniques of insulating oil on operating pole transformers by using digital signal processor. After applying voltage to the condenser which is in¬stalled in a transformer, acquiring source voltage and current of condenser and using cross-correla¬tion techniques, we can check the dissipation factor of insulating oil. To improve measuring accuracy and the speed of process, we use hardware such as TMS320C31 DSP board and software such as cross -correlation techniques. We simulated the measuring accuracy and the degree of the noise effect of this new measuring techniques by using computer simulation, and compared the simplified measuring devices with Schering bridge on degraded insulating oil. The result showed that this measuring tech¬nique can be used as diagnostic method on the pole transformers.

  • PDF

Electrical Characteristics of Insulating Paper for Pole Transformers after Accelerated Ageing (주상변압기용 절연지의 가속화 후 전기적 특성)

  • Song, I.K.;Jung, J.W.;Lee, B.S.;Han, Y.H.;Kim, C.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1591-1593
    • /
    • 2001
  • In this paper, the electrical characteristics of Insulating paper, for pole transformers, subjected to accelerated ageing were observed and the results were compared with those of virgin insulating paper. For the experiment, insulating materials for pole transformers were enclosed together in an oil bath and thermally aged under the real pole transformer operating conditions. After the accelerated ageing of the insulating materials, the dielectrics were measured and compared with the results of the virgin ones.

  • PDF

Electric Characteristics on the Insulating Paper with Varnish-Impregnant (바니쉬 함침이 절연지에 미치는 영향)

  • Kim, Pil-Hwan;Kim, Ju-Han;Lee, Won-Yeong;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2004.05b
    • /
    • pp.180-182
    • /
    • 2004
  • We have investigated characteristics of varnish and oil impregnant. When transformers are manufactured with some moisture and varnish impregnant not entirely dried, those should be caused by factors that deteriorate the electrical or mechanical property after installation. Therefore, in this study we experienced moisture content of the new insulating paper and the varnish impregnant paper in the ratio of time for confirming factors that deteriorate the paper characteristics. Besides, we investigated a property study that was experienced the value of dielectric strength and tensile strength as no serviced insulating samples of transformer.

  • PDF

Qualitative Assessment for Hazard on the Electric Power Installations of a Construction Field using FMEA (FMEA를 이용한 건설현장 전력설비의 위험성에 대한 정성적 평가)

  • Kim Doo-hyun;Lee Jong-ho
    • Journal of the Korean Society of Safety
    • /
    • v.19 no.4 s.68
    • /
    • pp.36-41
    • /
    • 2004
  • This paper presents an qualitative assessment for hazard on the electric power installations of a construction field using FMEL The power installations have the mission to maintain the highest level of service reliability on the works. The more capital the electric power invest the higher service reliability they plausibly will achieve. However, because of limited resources, how effectively budgets can be allocated to achieve service reliability as high as possible. The assessment typically generates recommendations for increasing component reliability, thus improving the power installation safety. The FMEA tabulates the failure modes of components and how their failure affects the power installations being considered. Tn order to estimate the risks of a failures, the FMEA presents criticality estimation or risk priority number using the severity, occurrence, and detectability. The results showed that the highest components of the risk priority number among components were condenser, transformer, MCCB and LA. And In case of the criticality estimation, the potential failure modes were abnormal temperature rise, insulation oil leakage, deterioration for the transformer, overcurrent for the MCCB and operation outage fir the LA.

Clamping-diode Circuit for Marine Controlled-source Electromagnetic Transmitters

  • Song, Hongxi;Zhang, Yiming;Gao, Junxia;Zhang, Yu;Feng, Xinyue
    • Journal of Power Electronics
    • /
    • v.18 no.2
    • /
    • pp.395-406
    • /
    • 2018
  • Marine controlled-source electromagnetic transmitters (MCSETs) are important in marine electromagnetic exploration systems. They play a crucial role in the exploration of solid mineral resources, marine oil, and gas and in marine engineering evaluation. A DC-DC controlled-source circuit is typically used in traditional MCSETs, but using this circuit in MCSETs causes several problems, such as large voltage ringing of the high-frequency diode, heating of the insulated-gate bipolar transistor (IGBT) module, high temperature of the high-frequency transformer, loss of the duty cycle, and low transmission efficiency of the controlled-source circuit. This paper presents a clamping-diode circuit for MCSET (CDC-MCSET). Clamping diodes are added to the controlled-source circuit to reduce the loss of the duty ratio and the voltage peak of the high-frequency diode. The temperature of the high-frequency diode, IGBT module, and transformer is decreased, and the service life of these devices is prolonged. The power transmission efficiency of the controlled-source circuit is also improved. Saber simulation and a 20 KW MCSET are used to verify the correctness and effectiveness of the proposed CDC-MCSET.

The Study on the Monitoring and Diagnostic System for Distribution Transformer Using Wireless Communication (무선통신을 이용한 배전용 변압기 모니터링 및 진단 장치 개발에 관한 연구)

  • Moon, Jong-Fil;Kim, Jae-Chul;Choi, Joon-Ho;Kim, Oun-Seok;Yoon, Yong-Han;Min, Kyeoung-Rae
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.214-216
    • /
    • 2001
  • In this paper, we developed the on-line Diagnostic & Monitoring system of distribution transformers using wireless communication. The Diagnostic system consists of the top oil temperature sensing, ambient temperature sensing. load current sensing, acoustic emission peak-value sensing, acoustic emission pulse counter and wireless communication part. The Monitoring system consists of the communication setting, online monitoring and database construction part. The Diagnostic system send the date acquired from the some sensors of the distribution transformers to the host PC. The Monitoring program of the host PC store the data to database. And the Monitoring system estimates the loss of life from the DB. Thus it could be managed the career and the functional lifetime of the transformer more efficiently than existing methodologies.

  • PDF

The Monitoring Program and Database Construction for Diagnosing Distribution Transformer in On-line (배전용 변압기 온라인 감시와 진단을 위한 모니터링 프로그램 및 DB의 구축)

  • Moon, Jong-Fil;Kim, Jae-Chul;Kim, Dong-Hyun;Choi, Joon-Ho;Choi, Do-Hyuk;Kim, Young-Chun
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.177-179
    • /
    • 2000
  • In this paper, we developed the online Monitoring & Diagnostic(MD) system of distribution transformers. It consists of the Data Acquisition(DA) module and the DataBase(DB) module. The acquired data from the distribution transformers is stored to the DB in an on-line. The DB is planned and made to the RDBMS (Relative DataBase Management System) to manage the data efficiently. The developed MD system estimates the loss of life from the DB. Thus, it could be managed the career and the functional lifetime of the transformer more efficiently than existing systems. In the case study, the oil temperature rising experiment is performed by using the back loading method in the laboratory level. From the results, the proposed MB system can be a practical applications for the distribution transformers.

  • PDF