• Title/Summary/Keyword: Theoretical grounding

Search Result 36, Processing Time 0.02 seconds

Analysis for the Grounding Impedance of Vertical Grounding Electrodes using the Distributed Parameter Circuit Model (분포정수회로모델을 이용한 수직 접지전극의 접지임피던스의 분석)

  • Lee, Bok-Hee;Kim, Jong-Ho;Choi, Jong-Hyuk
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.6
    • /
    • pp.1103-1108
    • /
    • 2010
  • A grounding electrode has the transient grounding impedance characteristics against lightning surges. So the performance of grounding electrodes should be evaluated as a grounding impedance as well as the ground resistance. The frequency-dependent grounding impedance is varied with the shape and size of grounding electrode and is divided into both inductive and capacitive behaviors. This paper presents a theoretical analysis for the grounding impedance determined by the size of grounding electrode using the distributed parameter circuit model. EMTP and Matlab programs were used in calculating the frequency-dependent grounding impedances of vertical grounding electrodes. It was found that the frequency-dependent grounding characteristics of vertical grounding electrodes are characterized by the distributed parameters which are changed in the dimension of grounding electrodes.

Study of Touch and Step Voltages with Grounding Grid Using Electrolytic Tank and Analysis Program

  • Gil, Hyoung-Jun;Kim, Hyang-Kon;Kill, Gyung-Suk
    • International Journal of Safety
    • /
    • v.9 no.2
    • /
    • pp.1-5
    • /
    • 2010
  • In order to analyze the potential rise of ground surface of grounding grid installed in buildings, the grounding simulator has been designed and fabricated as substantial and economical measures. This paper describes the study of touch and step voltages with grounding grid where earth leakage current is injected. To assess risk voltage of grounding grid, the grounding simulator and CDEGS program were used to obtain measured data and theoretical results of this study. The grounding simulator was composed of an electrolytic tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured by grounding simulator, and the touch and step voltages were computed by CDEGS program. As a consequence, the touch voltage and step voltage above the grounding grid were very low, but were significantly increased near the edge of grounding grid.

presumption of Earth Resistance by Water Tank Model (수조모델 실험에 의한 접지저항 추정)

  • 고희석;최종규;김주찬;이충식
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.125-131
    • /
    • 2002
  • It is very important to assume potential distribution to be generated in electrode environs and grounding resistance by current beforehand, when incoming at grounding electrode to plan efficient grounding facilities In this paper, we analyzed grounding resistance through a simulation experiment by a water tank scaled model electrode of the rectangular earth plate, a theoretical Calculation result of the rectangular earth plate and measurement of grounding resistance buried rectangular earth plate analysing earth surface potential.

  • PDF

Assumption of Grounding Electrode by Model Experiment (모델실험에 의한 접지전극의 상정)

  • Koh, Hee-Seog;Kim, Maeng-Hyun;Park, Seung-Jae;Song, Won-Pyo;Kim, Ju-Chan
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.327-329
    • /
    • 2002
  • This paper is based on model electrode by reduced scale and theoretical background of proportion factor. use building structure and mesh electrode, we get grounding electrode of building grounding structure and grounding electrode of mesh electrode by modeling experimentation and estimation coordinate geometry, we are doing practical grounding electrode assumption.

  • PDF

Comparison of Theoretical Resu Its and Measured Data Using Hemispherical Water Tank Model for Potential Rise of Structure Grounding (구조체 접지의 전위상승에 대한 반구형 수조에 의한 측정값과 계산값의 비교)

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon;Han, Woon-Ki;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.111-114
    • /
    • 2005
  • This paper presents a comparison of experimental value by hemispherical grounding simulation system and calculated value by CDEGS program for ground potential rise of structure. When a test current flowed through structure grounding electrodes, ground potential rise was measured and analyzed for types of structure using the hemispherical grounding simulation system in real time, and was computed by means of CDEGS program. The model structures were designed and fabricated with two types on a scale of one-one hundred sixty. When the experimental data were compared with the theoretical values, the similar profile was shown. Therefore, the confidence of measurement was obtained. The distributions of ground surface potential are dependent on the resistivity and absorption percentage in concrete attached to structure.

  • PDF

Analysis for the impulsive impedance of counterpoise (매설지선의 임펄스임피던스의 해석)

  • Joe, Jeong-Hyeon;Kim, Jong-Ho;Beak, Young-Hwan;Kim, Dong-Seong;Lee, Gang-Su;Kim, Ki-Bok;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.88-91
    • /
    • 2009
  • For lightning currents, a grounding system shows the transient grounding impedance characteristics. A grounding system for protection against lightning should be evaluated by the transient grounding impedance, not it's ground resistance. The transient grounding impedance varies with the shape of ground electrode and earth characteristics as well as the waveform of lightning surge current. For the analysis and practical use of transient grounding impedance, the characteristics of transient grounding impedance should be analyzed theoretically and this paper suggests the theoretical analysis for the transient grounding impedance of counterpoise by using the distributed parameter circuit model. EMTP and Matlab are used to simulate the distributed parameter circuit model of counterpoise and the adequacy of the distributed parameter model of counterpoise is examined by comparing the simulated results with the measured results.

  • PDF

A Study on Grounding Resistance by Parallel Connection (병렬 접속에 의한 접지저항에 관한 연구)

  • 고희석;최종규;류희석;김주찬
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.307-312
    • /
    • 2002
  • For accuracy of an experiment, measure changing of grounding resistance by short period after construction and investigated the efficiency of grounding's different methode of parallel connection. We could confirm on measurement's accuracy, error through comparing the theoretical value and measured value. Therefore, reduction ratio can be expected from execution measurement to receive a target resistance value. By the result, we could evaluate the method of rod grounding electrode's proper execution

  • PDF

Estimation of Groungding Registance by Water Tank Model (수조모델 실험에 의한 접지저항 추정)

  • 최종규;고희석;이충식;김주찬
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.2
    • /
    • pp.41-48
    • /
    • 2003
  • To make a efficient grounding facilities, it is very important to assume electrical potential distribution and grounding resistance previously in grounded electrode circumference, when the current flow to grounded electrode. In this paper, grounding resistance analyzed from grounding surface electrical potential in grounded rectangular electrode plate is compared to grounding resistance by theoretical expression and grounding resistance measured by simulated experiment in the water tank.

Analysis of Risk Voltage for Grounding Electrode by Injection of Earth Leakage Current

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Lee, Ki-Yeon;Moon, Hyun-Wook;Kim, Hyang-Kon;Kil, Gyung-Suk
    • International Journal of Safety
    • /
    • v.8 no.2
    • /
    • pp.9-14
    • /
    • 2009
  • This paper describes analysis of risk voltage for grounding electrode where earth leakage current is injected. To assess risk voltage of grounding electrode, the grounding simulator and CDEGS program were used to obtain measured data and theoretical results of this study. The grounding simulator was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The shapes of grounding electrode model was ground rod. The potential rise was measured by grounding simulator, and the touch and step voltages were computed by CDEGS program. As a consequence, the potential rise of ground rod abruptly decreases with increasing the distance from the grounding electrode to the point to be tested. The touch voltage above the ground rod was low, but the step voltage was high. The measured results were compared with the computer calculated data and were known in good agreement.

An Analysis of Potential Interference in the Vicinity of the Vertical Ground Rod (수직 접지전극 주변에서 전위간섭의 분석)

  • Lee, Bok-Hee;Lee, Kang-Soo;Seong, Chang-Hoon;Choi, Jong-Hyuk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.5
    • /
    • pp.85-91
    • /
    • 2011
  • A grounding system is generally composed of several vertical, horizontal electrodes or grids. Excessive ground potential rises due to adjacent grounding electrodes can cause failures or misoperation of electronic devices and control systems. It is therefore necessary for computer-related and information-oriented equipment to be placed at a sufficient distance from the areas influenced by grounding electrodes. In this paper, in order to propose a method for evaluating the ground potential rise and interference in the vicinity of vertical grounding electrodes, the experimental and theoretical results on the potential interference between vertical grounding electrodes and its frequency dependence were described. The ground potential rise is sharply decreased with increasing the distance between grounding electrodes. In case that the separation of vertical grounding electrodes is less than 1.5[m], the potential interference coefficient was greater than 0.1 and linearly increased with the frequency of the test current within the frequency of 1[MHz].