• 제목/요약/키워드: Technical Advisory Committee(TAC)

검색결과 3건 처리시간 0.02초

TAC를 반영한 BIN 데이터 기반의 냉난방 부하 변화에 관한 연구 (Heating and Cooling Load Evaluation Study with TAC Based BIN Data)

  • 이광섭;김유진;민경천;이의준;강은철
    • 설비공학논문집
    • /
    • 제29권9호
    • /
    • pp.463-471
    • /
    • 2017
  • According to the Korea industrial standard of air conditioning systems (KS C 9306), cooling and heating loads for buildings can be calculated by using maximum and minimum temperature in BIN data. Cooling and heating loads can be determined by building set temperature and ambient temperature. Cooling and heating system capacity of buildings can be normally designed according to determined heating and cooling loads. Cooling and heating system capacity can be reduced by updated BIN data, applying TAC (Technical Advisory Committee) values. In this study, updated BIN data have been analyzed using ambient temperature of 19 areas in Korea for the last 10 years (2005~2014) provided by KMA (Korea Meteorological Administration). Building cooling and heating loads have been calculated following TAC based BIN data. As a result, designed system capacity decreased depending on applying TAC. Those were reduced as 7.1% ($100m^2$ building), 8.7% ($1,000m^2$ building) in cooling capacity, 11.7% in heating capacity when TAC 2.5% applied. And also, it is expected system initial and operating cost by decreasing system capacity.

A Study on Weather Data for Air Conditioning Equipment Design Report I - Weather Data in Busan from 1970 through 2003

  • Kim Jong-Ryeol;Kum Jong-Soo;Choi Kwang-Hwan
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제14권1호
    • /
    • pp.1-6
    • /
    • 2006
  • For the purpose of processing weather data for air conditioning equipment de sign in Busan area Korea, this study collected weather observations made by Busan weather Administration from 1970 to 2003, and then established external conditions for heating and air-conditioning design. For changes of temperature in external conditions for design, the highest temperature had little changed, whereas the lowest had been on the rise as the years went by through the 1970s, 1980s, 1990s, and 2000s, but insolation has a little lessened. Absolute humidity does not show a significant change but an incessant rise.

기상 데이터 산정 기간에 따른 국내의 설계용 외기온도 분석 (Analysis of South Korea Outdoor Design Temperature with respect to Assigned Period of the Weather Data)

  • 남아영;김영일;정광섭
    • 한국지열·수열에너지학회논문집
    • /
    • 제13권2호
    • /
    • pp.1-8
    • /
    • 2017
  • Outdoor design temperature is important for selecting proper capacity of heating and cooling systems of a building to implement indoor thermal comfort and save energy consumption. The purpose of this study is to investigate the change of South Korea outdoor design temperature according to the assigned period. When outdoor design temperature of 8 locations calculated with the latest weather data during 2008~2015 years using ASHRAE Bin method are compared to the standard temperature of Ministry of Land, Infrastructure and Transport which is widely used for designing South Korea air-conditioning system at present, the maximum temperature difference becomes $0.97^{\circ}C$ for cooling, and $1.94^{\circ}C$ for heating. Due to wide outdoor temperature variation, update of outdoor design temperature based on recent weather data is recommended.