  • This paper presents a novel reset scheme for mm-scale sensing systems with stringent volume and area constraints. In such systems, multi-layer structure is required to maximize the silicon area per volume and minimize the system size. The multi-layer structure requires wirebonding connections for power delivery and communication among layers, but the area overhead for wirebonding pads can be significant. The proposed reset scheme exploits already existing power wires and thus does not require additional wires for system-wide reset operation. To implement the proposed reset scheme, a power management unit is designed to impose reset condition, and a reset detector is designed to interpret the reset condition indicated by the power wires. The reset detector uses a coupling capacitor for the initial power-up and a feedback path to hold the developed supply voltage. The prototype reset detector is fabricated in a $180-{\mu}m$ CMOS process, and the measurement results with the prototype mm-scale system confirmed robust reset operation over a wide range of temperatures and voltages.

Experimental Study on Energy Saving Performance of Outdoor Temperature Reset Control Strategy for Central Cooling System (중앙 냉방시스템에 대한 외기보상제어의 절약 성능에 관한 실험적 연구)

  • Kim, Dong-Cheol;Song, Jae-Yeob;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.7 no.2
    • /
    • pp.30-36
    • /
    • 2011
  • In this study, energy saving performance of outdoor temperature reset control strategy for central cooling system is researched by experiments. Outdoor temperature reset control is the control method to change indoor air set temperature according to outdoor air temperature change. The range of indoor air set temperature is represented by the comfort temperature range of indoor air temperature offered from ASHRAE and indoor air set temperature is programmed between $22^{\circ}C$ and $27^{\circ}C$ by outdoor air temperature $20^{\circ}C{\sim}32^{\circ}C$ in summer. As a result of applying outdoor temperature reset control to central cooling system, the suggested control method shows better performances of energy savings than the conventional method which indoor temperature maintains constantly.

The EEV Control of the Multi-type Air-conditioning System by using a Fuzzy Logic Superheat Temperature Setpoint Reset Algorithm (퍼지로직 과열도 재설정 알고리즘을 사용한 멀티형 냉방시스템의 전자팽창밸브 제어)

  • 한도영;이상원
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.5
    • /
    • pp.382-388
    • /
    • 2003
  • Refrigerant flow rates of the multi-type air-conditioning system can be regulated by electronic expansion valves (EEV). The performance of the multi-type air-conditioning system may be improved by lowering the superheat at the compressor suction side. In this study, a superheat temperature setpoint reset algorithm was developed by using fuzzy logics, and a PI algorithm was applied to control the superheat temperature near setpoints. Experimental results showed energy savings and stable operations at a multi-type air-conditioning system. Therefore, the developed setpoint reset algorithm may be effectively used for the EEV superheat temperature control of the multi-type air-conditioning system.

Actual Energy Consumption Analysis of Temperature Control Strategies for Secondary Side Hot Water District Heating System with an Inverter (인버터시스템 적용 지역난방 시스템의 2차측 공급수 온도 제어방안에 따른 에너지사용량 실증 비교)

  • Cho, Sung-Hwan;Hong, Seong-Ki
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.27 no.4
    • /
    • pp.179-186
    • /
    • 2015
  • In this study, the actual energy consumption of the secondary side District Heating System (DHS) with different hot water supply temperature control methods is compared. The two methods are Outdoor Temperature Reset Control and Outdoor Temperature Predictive Control. While Outdoor Temperature Reset Control has been widely used for energy savings of the secondary side system, the results show that the Outdoor Temperature Predictive Control method saves more energy. In general, the Outdoor Temperature Predictive Control method lowers the supply temperature of hot water, and it reduces standby losses and increases the overall heat transfer value of heated spaces due to more flow into the space. During actual energy consumption monitoring, the Outdoor Temperature predictive Control method saves about 6.6% of energy when compared to the Outdoor Temperature Reset Control method. Also, it is found that at partial load condition, such as during daytime, the fluctuation of hot water supply temperature with Outdoor Temperature Reset Control is more severe than that with Outdoor Temperature Predictive Control. Thus, it proves that Outdoor Temperature Predictive Control is more stable even at partial load conditions.

The Effects of Prediction and Reset Control of Outdoor Air Temperature on Energy Consumption for Central Heating System (외기온도 예측 및 보상제어가 난방시스템의 에너지 소비량에 미치는 영향)

  • Ahn, Byung-Cheon;Hong, Sung-Suk
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.12 no.4
    • /
    • pp.8-14
    • /
    • 2016
  • In this study, the effects of prediction and reset control of outdoor air temperature on energy consumption for central heating system are researched by using TRNSYS program package, and the control performances with the suggested methods of prediction and reset control of outdoor air temperature are compared with the existing ones. As a result, the value of coefficient of determination $R^2$ for the predicted outdoor temperatures is improved and the suggested control method shows maximum 21.8% energy saving in comparison with existing control ones.

A Basic Study on Implementing Optimal Function of Motion Sensor for Bridge Navigational Watch Alarm System

  • Jeong, Tae-Gweon;Bae, Dong-Hyuk
    • Journal of Navigation and Port Research
    • /
    • v.38 no.6
    • /
    • pp.645-653
    • /
    • 2014
  • A Bridge Navigational Watch Alarm System (hereafter 'BNWAS') is to monitor and detect if an officer of watch(hereafter 'OOW') keeps a sharp lookout on the bridge. The careless lookout of an OOW could lead to marine accidents. For this reason on June 5th, 2009, IMO decided that a ship is equipped with a BNWAS. However, an existing BNWAS gives the OOW a lot of inconvenience and stress in its operation. It requires that the OOW should press reset buttons to confirm their alert watch on the bridge at every three to twelve minute. Many OOWs have complained that at some circumstances they cannot focus on their bridge activities including watch-keeping due to a lots of resetting inputs of BNWAS. Accordingly, IMO has allowed the use of a motion sensor as a resetting device. The motion sensor detects the movements of human body on the bridge and subsequently sends reset signals directly to BNWAS automatically. As a result, OOWs can work uninterrupted. However, some of classification societies and flag authorities have a slightly different stance on the use of motion sensor as a resetting method for BNWAS. The reason is that the motion sensor may trigger false reset signals caused by the motion of objects on the bridge, especially a slight movement such as toss and turn of human body which can extend the period of careless watch. As a basic study to minimize the false reset signals, this paper proposes a simple configuration of BNWAS, which consists of only three motion sensors associated with 'AND' and 'OR' logic gates. Additionally, several considerations are also proposed for the implementation of motion sensors. This study found that the proposed configuration which consists of three motion sensors is better than an existing one by reducing false reset signals caused by a slight movement of human body in one's sleep. The proposed configuration in this paper filters false reset signals and is simple to be implemented on existing vessels. In addition, it can be easily installed just by a basic electrical knowledge.

Automatic Recovery and Reset Algorithms for System Controller Errors

  • Lee, Yon-Sik
    • Journal of the Korea Society of Computer and Information
    • /
    • v.25 no.3
    • /
    • pp.89-96
    • /
    • 2020
  • Solar lamp systems may not operate normally in the event of some system or controller failure due to internal or external factors, in which case secondary problems occur, which may cost the system recovery. Thus, when these errors occur, a technology is needed to recover to the state it was in before the failure occurred and to enable re-execution. This paper designs and implements a system that can recover the state of the system to the state prior to the time of the error by using the Watchdog Timer within the controller if a software error has occurred inside the system, and it also proposes a technology to reset and re-execution the system through a separate reset circuit in the event of hardware failure. The proposed system provides stable operation, maintenance cost reduction and reliability of the solar lamp system by enabling the system to operate semi-permanently without external support by utilizing the automatic recovery and automatic reset function for errors that occur in the operation of the solar lamp system. In addition, it can be applied to maintain the system's constancy by utilizing the self-operation, diagnosis and recovery functions required in various high reliability applications.

Influence of reset pulse form on electrical characteristics in AC-PDP

  • Cho, T.S.;Ko, J.J.;Lee, C.W.;Cho, G.S.;Choi, E.H.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.04a
    • /
    • pp.159-161
    • /
    • 2000
  • After the square type reset pulse, the condition of remaining wall charge has been experimentally investigated in AC-PDP with VDS (Versatile Driving Simulator) system, in which arbitrary driving waveform and sequence can be used. After the self-discharge process, almost wall charges are eliminated. But some wall charges are not and its quantity is dependent on the voltage of the reset pulse. When the voltage of the reset pulse is growing, its quantity is decreased. But if the voltage of the reset pulse is above 300V, the wall voltage due to remaining wall charge is constant and its value is found out 6V. Also it is found that its polarity is always same with the one made by the reset pulse. It means that the polarity is not changed by the self-discharge.

  • PDF

A Resetting Scheme for Process Parameters using the Mahalanobis-Taguchi System

  • Park, Chang-Soon
    • The Korean Journal of Applied Statistics
    • /
    • v.25 no.4
    • /
    • pp.589-603
    • /
    • 2012
  • Mahalanobis-Taguchi system(MTS) is a statistical tool for classifying the normal group and abnormal group in multivariate data structures. In addition to the classification itself, the MTS uses a method for selecting variables useful for the classification. This method can be used efficiently especially when the abnormal group data are scattered without a specific directionality. When the feedback adjustment procedure through the measurements of the process output for controlling process input variables is not practically possible, the reset procedure can be an alternative one. This article proposes a reset procedure using the MTS. Moreover, a method for identifying input variables to reset is also proposed by the use of the contribution. The identification of the root-cause parameters using the existing dimension-reduced contribution tends to be difficult due to the variety of correlation relationships of multivariate data structures. However, it became possible to provide an improved decision when used together with the location-centered contribution and the individual-parameter contribution.

An Experimental Study on Control Performance of Radiant Floor Cooling Using Ondol (온돌을 이용한 바닥복사냉방의 제어성능에 관한 실험적 연구)

  • 김용이;임재한;한여명;김광우
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.11
    • /
    • pp.1165-1173
    • /
    • 2001
  • The objectives of this study are to analyze the application of radiant floor cooling and to evaluate the control methods through experiments when the radiant heating system is used for cooling. Through the experiment analysis the control methods such as on/off control, variable flow control and outdoor reset with indoor temperature feedback control are evaluated and compared. The cooling curve (reset ratio) is found for radiant cooling, which shows tole relation between outside air temperature and supply water temperature. Comparison of cooling methods shows that outdoor reset with indoor temperature feedback control is more appropriate than on/off control and variable flow control with regard to prevention of the condensation and thermal comfort.