• 제목/요약/키워드: Switchboard

검색결과 53건 처리시간 0.04초

22.9kV 폐쇄 배전반내의 사고모델을 통한 실험적 검증 (Experimental Verification According to an Accident Model in a Metal-Clad Switchgear at 22.9kV)

  • 송길목;한운기;최충석
    • 전기학회논문지P
    • /
    • 제55권2호
    • /
    • pp.110-114
    • /
    • 2006
  • This paper describes the accident analysis by modelling the current transformer mounting in a metal-clad switchgear at 22.9kV. In analyzing the accident, the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault occurring between the end plate of 22.9kV lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, Its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was chanted into an insulation.

퍼지알고리즘을 이용한 유증 변압기의 안전진단 및 평가에 관한 연구. (A Study on Safty Diagnosis and Evaluation of Oil Transformer using Fuzzy Algorithm)

  • 김영일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 전기설비
    • /
    • pp.67-68
    • /
    • 2006
  • In this paper, we introduced about safety algorithm of transformer for MV/LV distribution customers using by fuzzy theory. Overload of transformer becomes different by surrounding temperature. And parameters about overload of transformer are connection each other. Therefore, we organize safety algorithm consider overload of transformer and surrounding temperature in this research. And we induce the relational expression of each parameters using experiment data of IEEE std C57.91-1995. Deduction of result used fuzzy reasoning. We guess the safety algorithm suggested in this paper shows the new direction that heavy electrical equipments including switchboard are going to develop in the future.

  • PDF

애스터리스크(*) 배열구조 기반 전력저감 수배전반 (Asterisk(*) Array structure based power reduction power distribution board)

  • 김미숙;박동삼
    • 한국산학기술학회논문지
    • /
    • 제18권11호
    • /
    • pp.138-144
    • /
    • 2017
  • 오늘날 전력수요 급증에 따른 전력소비량이 증가하고 있어 전력손실을 줄일 수 있는 에너지 저감을 위한 설계 또는 설비 대체로 전력의 고품질화가 필요하다. 배전반이란 한전의 발전설비로부터 전기를 공급받아 각 건물에 필요한 설비에 계통별 또는 용도별로 나누어 주는 기계장치이다. 배전반은 일반적으로 외함, 개폐기, 전력용 도체, 제어부분으로 구성된다. 본 연구는 배전반내의 메인 요소인 통전을 위한 전력용 도체에 관한 것이다. 실효교류저항 측정시험을 통해 기존방식 판상도체의 수직 배열구조가 비효율적 구조임을 입증해 본다. 실효교류저항이 많이 증가하면 표피효과로 인해 상대적으로 도체의 단면적이 커지게 된다. 본 연구는표피효과를 줄여 실효교류저항을 최소화시키는 애스터리스크(*) 배열구조를 기반으로 설계하여 에너지 절약과 원자재 절감을 연구하였다. 본 연구의 핵심기술 원리는 애스터리스크 배열구조를 적용하여 도체저항 감소기술 기반 에너지 절감 수배전반이다. 수배전반의 교류전력 공급용 판상도체 각각(rst 또는 abc)의 상에서 발생한 자기장이 상호작용으로 상쇄 소멸될 수 있도록 한 판상도체 배열구조에 관한 것으로 효과로는 판상도체에서 유도성 리액턴스의 발생량이 줄어들면서 유효단면적이 증가, 실효교류저항을 줄인다.

상하굴절형 내진패드를 설치한 수배전반 방재기술에 관한 연구 (A Study on the Disaster Prevention Technology of the Switchboard with Upper and Lower Bending Type Seismic Pads)

  • 이태식;석금철;이재원;김태진;김재권;조원철
    • 한국방재안전학회논문집
    • /
    • 제10권1호
    • /
    • pp.85-90
    • /
    • 2017
  • 본 연구는 빌딩과 공공시설에 설치되는 중요 전기 시설물인 수배전반이, 규모 8.3급 지진에도 국내최초로 정상적으로 작동될 수 있도록, 전기를 사용하는 각종 시설물 및 기계장치의 전원공급 및 제어하는 수배전반 하부에 상하굴절형 내진패드를 설치하여, 수배전반 하부구조 보호와 상부에 케이블 단락방지 등이 가능하도록 하여, 상하좌우 모든 지진파에 잘 적응되는 내진형 수배전반 제조기술로 한국전력이 기준으로 제시한 GR-63-CORE(규모 8.3 급) 내진성능을 만족하는, 내진형 수배전반 방재기술이다. 연구 성과로서, 전기 및 통신 기반시설을 보호할 수 있게 되어 지진발생시 전기시설을 정상상태로 복구하는 시간을 단축하는데 기여할 수 있고, 지진발생시 전기공급 시설의 파괴로 인한 화재발생을 방지할 수 있어 일본의 경우처럼 대규모 지진 발생시 발생하는 화재의 확산을 최소화하여 인명피해와 재산피해를 최소화할 수 있으며, 시민들이 대규모 지진을 겪은 후에도 일상생활로 신속히 복구할 수 있는 전기기반시설을 확보 등에 기여할 수 있다. 또한, 통신 및 전산실의 장비의 내진을 확보하기 위하여, 본 기술이 적용될 수 있고, 나아가 지진시 기반이 흔들려 시설기능이 정지될 수 있는 분야에도 다양하게 적용될 수 있을 것이다.

양자화 된 범용 화자모델을 이용한 연속적 화자분류 (Sequential Speaker Classification Using Quantized Generic Speaker Models)

  • 권순일
    • 전자공학회논문지CI
    • /
    • 제44권1호
    • /
    • pp.26-32
    • /
    • 2007
  • 연속적 화자 분류에 있어서 분류 대상이 되는 화자에 대한 정보가 없거나 부족할 경우 정확한 연속적 분류가 어렵다. 이러한 문제를 해결하기 위해 표본 화자모델을 이용하는 방법이 제안되었는데, 이 방법을 이용하면 미리 준비된 화자의 데이터가 없이 화자모델 초기화와 화자분류가 가능해진다. 하지만 여전히 화자모델의 표본을 얻는 방법에 어려움이 따른다. 이 문제를 해결하기 위해 벡터 양자화에서 비롯된 화자 양자화를 제안한다. 유선전화 데이터를 이용한 실험에서 화자 양자화를 이용한 표본 화자모델 방법은 무작위 표본추출 방법을 이용할 경우 보다 25%의 성능 향상을 보였다.

SMPS방식을 적용한 의료기기용 전원모듈 개발 (Development of the SMPS Power Module for the Medical Kit)

  • 이상식;이기영
    • 한국정보전자통신기술학회논문지
    • /
    • 제2권1호
    • /
    • pp.11-15
    • /
    • 2009
  • 본 연구에서 전원이 공급되는 의료기기들에서 공통적으로 사용되며, 성능, 안전성과 신뢰성 측면에서 기존 전원모듈보다 우수한 250 W SMPS방식을 적용한 의료용 전원모듈의 개발하였다. SMPS의 특성상 AC전원의 50 ~ 60 Hz 라인 주파수를 DC로 변환하는 회로의 설계와 높은 주파수로 변경하기 위한 전자회로로 구성하였고, 완전한 방사노이즈 흡수회로를 구성하여 의료기기 오동작을 방지하기 하도록 설계하였다. SMPS 전원모듈은 의료기기뿐만 아니라 PC, 가정용 기기 및 전자 교환기 등의 제품에도 확대 적용이 가능하다.

  • PDF

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Electric Discharges

  • Park, Dae-Won;Kil, Gyung-Suk;Cheon, Sang-Gyu;Kim, Sun-Jae;Cha, Hyeon-Kyu
    • Journal of Electrical Engineering and Technology
    • /
    • 제7권3호
    • /
    • pp.389-395
    • /
    • 2012
  • In this paper, we analyzed the frequency spectrum of the electromagnetic waves radiated by an electric discharge as a basic study to develop an on-line diagnostic technique for power equipment installed inside closed-switchboards. In order to simulate local and series arc discharges caused by an electric field concentration and poor connections, three types of electrode systems were fabricated, consisting of needle and plane electrodes and an arc generator meeting the specifications of UL 1699. The experiment was carried out in an electromagnetic anechoic chamber, and the measurement system consisted of a PD free transformer, a loop antenna with a frequency bandwidth of 150 kHz-30 MHz, an ultra log periodic antenna with a frequency bandwidth of 30 MHz-2 GHz, and an EMI test receiver with a frequency bandwidth of 3 Hz-3 GHz. According to the experimental results, the frequency spectra of the electrical discharges were widely distributed across a range of 150 kHz-400 MHz, depending on the defects, while commonly found between 150 kHz and 10 MHz. Therefore, considering the ambient noise and antenna characteristics, the best frequency bandwidth for a measurement system to monitor abnormal conditions by detecting electromagnetic waves in closedswitchboards is 150 kHz-10 MHz.

Characteristics of Lightning Overvoltages Coming in Low-Voltage Power Distribution Systems

  • Lee, Bok-Hee;Lee, Dong-Moon;Lee, Su-Bong;Jeong, Dong-Cheol;Lee, Jae-Bok;Myung, Sung-Ho
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제3C권3호
    • /
    • pp.91-98
    • /
    • 2003
  • The importance of improving the quality of electric power is being strongly raised, owing to an increasing use of sensitive and small-sized electronic devices and systems. The transient over-voltages on low-voltage power distribution systems are induced by direct or indirect lightning return strokes. These can cause damage and/or malfunction of the utility systems for home automation, office automation, factory automation, medical automation, etc. The behaviors of lightning overvoltages transferred through the transformer to the low-voltage distribution systems using a Marx generator were experimentally investigated. Furthermore, the coupling mechanisms of lightning overvoltages transferred to the low-voltage systems were clearly illustrated through a theoretical simulation using a Pspice program. The overvoltages in low-voltage ac power systems are rarely limited by the application of the surge arrester to the primary side of the distribution transformer. A superior surge protection scheme is to install surge protection devices at the service entrance switchboard and/or at the load devices in TN power systems.

전기철도용 소규모SCADA 시스템 설계방안에 관한 연구 (A Study on the Design of Small Unit SCADA System for Electric Railroad)

  • 이승철;신관우;이윤섭
    • 전기학회논문지P
    • /
    • 제53권2호
    • /
    • pp.89-93
    • /
    • 2004
  • Supervisory Control And Data Acquisition(SCADA) of electric power system refersto the system that displays, monitors and executes the control commands for remote electric power system. KNR's existing electric power control system is built on UNIX platform such that it costs more for system construction, and people with UNIX skills can only be an operator who controls and manages the system. Moreover, since the system is mainly operated in local offices, system operators must communicate with local operators to investigate the cause of the accident and react the accident every time the system fails. As a new integrated SCADA system is constructed, establishment of small-unit electric power control system, that alters local electric power control system in designated stations, is required. In this study, the electric power control system, which accommodates all functions of UNIX-based SCADA system and facilitates operation and even maintenance for local operators, is to be developed. In order to develop small-unit electric power control system, the industrial automation program, "Cimon", is used. The small-unit electric power control system that accommodatesRTU and newly installed electronic switchboard is being developed and tested at Chulam station of KNR.

고압폐쇄분전반의 전력케이블 헤드와 안전셔터에서의 사고위험 평가 (Accident Risk Assessment between Power Cable Head and Safety Shutter in Medium Voltage Metal-Clad Switchgear)

  • 송길목;한운기;김영석
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.264-267
    • /
    • 2006
  • This paper describes the accident analysis by modeling the current transformer mounting in meaium voltage metal-clad switchgear(MCSG). In analyzing the accident the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault mounting between the end plate of a high voltage lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was changed into an insulation.

  • PDF