• Title/Summary/Keyword: Surge protective device

Search Result 62, Processing Time 0.036 seconds

Influences of the Length of Connecting Leads on the Energy Coordination in Coordinated SPD Systems (협조된 SPD시스템에서 접속선의 길이가 에너지협조에 미치는 영향)

  • Lee, Bok-Hee;Shin, Hee-Kyung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.6
    • /
    • pp.91-98
    • /
    • 2014
  • For the purpose of designing and applying the optimum surge protection scheme, multi-stage coordinated surge protective device(SPD) system is suitable to successfully fulfill its tasks; first, to divert a large amount of the transient energy, second, to clamp the overvoltage to the level below the withstand impulse voltage of the equipment to be protected. The length of SPD connecting leads shall be as short as possible. Long connecting leads will degrade the protection effect of SPDs. In this paper, the influences of the length of connecting leads on the energy sharing in a coordinated SPD system were investigated experimentally, and the simulation of determining the energy sharing and protection voltage level of each SPD depending on the length of connecting leads was carried out by using P-spice program. It was confirmed that the protection voltage level and energy sharing in coordinated SPD systems are strongly influenced by the length of connecting leads.

Protection of MOV Thermal Runaway and Safety Improvement of SPD using Built-in Instantaneous Trip Device (내장 순시 트립장치를 이용한 MOV의 열폭주 보호와 SPD의 안전성 개선)

  • Kim, Ju-Chul;Jeon, Joo-Sool;Ki, Che-Ouk;Choi, Gyung-Ray;Lee, Sang-Joong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.2
    • /
    • pp.120-125
    • /
    • 2011
  • SPDs are increasingly being used against lightning and switching surge according to the applicable revised standard and equipotential grounding system. SPDs are equipped usually with a MOV voltage regulating element. The MOV, however, always is exposed to the danger of thermal runaway resulting from inrushing temporary overvoltage and deterioration. In this paper, the authors made two prototype SPDs built-in Instantaneous trip device and analyzed their limiting voltage through test of the MOV breakdown. As the result of the analysis, the SPDs built-in Instantaneous trip device was proven to be effective for protecting MOV against thermal runaway and Instantaneous trip device react for limiting voltage is considered that is applicable to SPD.

Manufacture and Performance Evaluation of Insulating Transformer for surge protection under Electric Railway Environments (전기철도환경하에서의 서지방호용 절연변압기 제작 및 성능평가)

  • Lee, K.W.;Kim, M.Y.;Ohn, J.G.;Park, D.W.;Park, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2006.10a
    • /
    • pp.176-177
    • /
    • 2006
  • The main aim of the paper is the study of the surge voltages in electric railway signal security system. Hence these studies will provide means of introducing a suitable protective device insulating transformer. This influences the surge voltage interrupting capacity using surge arresters and bypass capacitors. This circuit can be used for investigating surge phenomenon in electric railway signal security system. In this paper a insulating transformer has been introduced for the reduction of surge voltages in the above circuit model and performance evaluation.

  • PDF

Thermal Stability Evaluation of SPDs with Parallel or Series Circuit Assemblies (SPD 직병렬 조합회로의 열적 안정성 평가)

  • Eom, Ju-Hong;Cho, Sung-Chul
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.265-269
    • /
    • 2005
  • Surge protective devices can be divided into three categories based on the circuit assembly: a parallel circuit type that considers the surge current amount within the device, a series circuit type that considers the voltage and single circuit type that uses a single element. However, when assembling SPDs, there are many things including function and safety to be taken into consideration because they are directly related to the performance and safety of the device. In this paper, we executed an experimental comparative study of performance and thermal stability of each SPD type using lightning surge generator and thermal image camera.

  • PDF

Energy Coordination between Cascaded Voltage Limiting Type SPDs in Surge Currents due to Direct Lightning Flashes (종속 접속된 전압제한형 SPD의 직격뢰 서지전류에 대한 에너지협조)

  • Lee, Bok-Hee;Um, Sang-Hyun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.5
    • /
    • pp.68-75
    • /
    • 2014
  • Cascaded applications of surge protective devices(SPDs) are required in order to reduce the stress on the electrical and electronics equipment being protected, and the energy coordination between the cascaded SPDs is very important. This paper deals with the experimental results obtained from the installation conditions of full-scale SPDs. The energy coordination between the upstream Class I SPD and the downstream Class II SPD was measured using a $10/350{\mu}s$ impulse current due to direct lightning flashes. The distances between the cascaded SPDs were 3, 10, and 50m, and the maximum test current was 12.5kA. As a result, the energy sharing between cascaded SPDs was dependent on the voltage protection level of each SPD and the distance between two SPDs. An overview of how to select SPD ratings in applications of cascaded SPDs system was discussed based on the energy coordination between the two SPDs. The proposed test results for the energy coordination between two-stage cascaded SPDs can be used in effective applications of SPDs.

Transient Voltage's Breaking by Development of High Performance SPD (고성능 서지보호기 개발을 통한 과도 이상전압 차단)

  • Kim, Jae-Hoon;Han, Sang-Ok;Kim, Sun-Ho;Koo, Kyung-Wan;Lee, Sei-Hyun;Park, Kang-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2065_2066
    • /
    • 2009
  • In this paper, we have developed high performance SPD(surge protective device) and evaluated the characteristics in comparison with typical SPD used in the inside and outside of the country. The new SPD was composed of MOV(metal oxide varistor), GDT(gas discharge tube) and impedance such as resistors, capacitors or varistors. To estimate operating the characteristic of the SPD which was developed, it was measured surge voltage caused by fault current or surge according to IEC 61000-4-5. As a result it was found that the power supply was cut off by high performance SPD when caused a short-circuit. In addition we could know that it could prevent ELB(earth leakage breaker)'s malfunction caused by surge.

  • PDF

The characteristic of leakage current in ZnO surge arrestor elements with mixed direct and 60Hz voltage (중첩전압(직류+교류 60Hz)에서 산화아연 피뢰기 소자의 누설전류 특성)

  • Lee, B.H.;Pak, K.Y.;Kang, S.M.;Choi, H.S.;Oh, S.K.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.186-188
    • /
    • 2003
  • The ZnO surge arrester is the protective device for limiting surge voltages on equipment by diverting surge current and returning the device to its original status. The occurrence of overvoltage appears in any phase to AC power supply system and it appears in mixing AC and impulse voltages, moreover because HVDC power supply system uses converter in semiconductor, it makes mixed DC and high harmonics voltages. In this study, the various mixed AC and DC voltages was made for investigating the degradation effect of ZnO arrester according to mixed voltage. As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current to ZnO block. In changing V-I curve for mixed voltages, the cross-over point acts a factor as making the proper capacitor size of an equivalent circuit for ZnO block.

  • PDF

Surge Protective Device(1) (서지보호장치(1))

  • Lee, Gi-Hong
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.1
    • /
    • pp.68-71
    • /
    • 2012
  • 금년부터 SPD가 KS제품으로 인정받을 수 있게 됩니다. 이러한 기술적 환경변화에 따라 SPD 기술에 대한 이해를 돕고자, 금번 호부터는 SPD에 대해서 연재하도록 하겠습니다.

  • PDF

A Protection Technique Against the Damages Caused by Lightning Surges on Information and Communication Facilities

  • Lee, Bok-Hee;Kang, Sung-Man;Ahn, Chang-Hwan
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.4
    • /
    • pp.117-122
    • /
    • 2003
  • The AC power lines and signal lines of info-communication networks are routed on overhead poles and are highly exposed to lightning strikes. Due to the potential difference between grounding points of AC power lines and signal lines, the electronic equipments connected to the signal lines can easily be damaged by lightning surges. In this work, in order to develop reliable methods of protecting information and communication facilities from lightning surges, the reliability and performance of SPDs (surge protective devices) were experimentally investigated in an actual-sized test circuit. The behaviors of SPDs against lightning surges from AC power lines and signal lines and the coordinated effects of SPD installation methods were evaluated. As a consequence, it was confirmed that the bypass arrester methods and common grounding system are both highly effective.

Coordination of Cascaded Metal Oxide Varistor-Based Surge Protective Devices (종속 접속된 산화아연바리스터 기반의 서지방호장치의 협조)

  • Kim, Tae-Ki;Shin, Hee-Kyung;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.6
    • /
    • pp.70-77
    • /
    • 2015
  • This paper describes the experimental results obtained from various installation conditions of cascaded metal oxide varistor(MOV)-based SPDs with the objectives to analyze the coordination of the cascaded surge protective devices(SPDs) and to propose the proper selection and installation methods of the cascaded SPDs. The residual voltage, discharge current and energy sharing between the upstream and downstream SPDs in the $10/350{\mu}s$ direct lightning current wave were measured and discussed. The coordination of cascaded MOV-based SPDs is closely related to the varistor voltage and installation methods of SPDs. In cascaded SPDs without dedicated decoupling elements, the natural impedance of leads connecting two SPDs can act as a decoupler for the coordination of MOV-based SPDs. Even if the varistor voltage of the upstream SPD is higher than that of the downstream SPD at long distances between two SPDs, the energy coordination of cascaded SPDs could effectively be fulfilled in the conditions of large surge currents and the optimum voltage protection level can be achieved. Consequently, if the distance between voltage limiting type SPDs is long, the coordination of the cascaded SPDs should be determined by taking into account the decoupling effects due to the intrinsic inductance of leads connecting the upstream and downstream SPDs.