• 제목/요약/키워드: Streaming Electrification

검색결과 55건 처리시간 0.024초

초고압 대용량 모델변압기의 유동대전 현상에 관한 연구(전압무인가) (A Study on the Streaming Electrification in the Super-high Voltage Model Transformer)

  • 이덕출;박재윤
    • 대한전기학회논문지
    • /
    • 제40권6호
    • /
    • pp.619-625
    • /
    • 1991
  • Phenomena of streaming electrification of insulting oil(T.O) is studied where the oil is contacted with solid insulating materials when it is pumped through a circulating system in a large power transformer. The leakage current, the electrical potential at the neutral terminal point of the transformer and the surface electrical potential of the oil are investigated. And the leakage current from the neutral terminal point is measured as a function of a bias polarity applied to a transformer case to investigate the polarty of ion which is absorbed in the case at the interface between the case and oil. As a result, it is found that insulating materials, and it is suggested that the leakage current is the sum of the relaxation current by positive charge from insulating oil to the neutral terminal point and by electrification current from negative charge electrified by the contact with solid insulating materials.

  • PDF

변압기유의 유동대전 현상에 관한 연구 (A Study on the Streaming Electrification Phenomena of the Transformer Oil)

  • 강성화;임기조;주상범;김명녕;강도열;김봉협
    • 대한전기학회논문지
    • /
    • 제39권6호
    • /
    • pp.568-576
    • /
    • 1990
  • Recently, streaming electrification in forced oil cooled power transformer has been taken up as a serious problem. In this paper, the charging tendency of various insulation oils, such as mineral oil, polybutene and silicone oil has been measured by means of an injection type charging tendency measuring apparatus under various condition. The experimental data of the dependence of the leakage current on flow velocity and temperature of oil can be explained by considering the flow state such as laminar and turbulent flow. The effect of additives on the charging tendency of mineral oil has been investigated. BTA is regarded as the most effective retardant to electrification of oil among the additives chose for this investigation.

  • PDF

합성절연유의 전기적 특성에 미치는 BTA의 영향 (The Influence of the BTA on Electrical Properties of Synthetic Fluids)

  • 신종열;신현택;홍진웅
    • 한국전기전자재료학회논문지
    • /
    • 제11권2호
    • /
    • pp.162-166
    • /
    • 1998
  • Synthetic fluid, class 7 group 2, as an insulating and cooling material is selected as. specimen, arid it is studied for the physical and electrical properties. Also, Benzotriazole(following as BT A) known as a suppressant of streaming electrification is added to it, and the change of physical and electrical properties by addition of BT A is investigated. From the spectrum of FT-IR, it is confirmed that the absorption peak in wavenumbers $3400{\sim}3450[cm^{-1}]$ is small or disappears when BTA is added. AC breakdown strength and volume resistivity of each specimen are investigated. It is considered that the effective content of BTA is about 10[ppm] for the suppression of electrification in this experiment.

  • PDF

고전압 인가 Couette Charger의 유동대전현상에 관한 연구 (A Study on the Streaming Electrification of the Energized Couette Charger)

  • 전상준;정용기;강창구;이강수;곽희로
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1848-1850
    • /
    • 1996
  • A Couette Charger was used to simulate streaming electrification process in transformer. This paper describes the electrification characteristics of the energized and unenergized Couette Charger. By applying low frequency and high voltage across the cylinder of the Couette Charger, the measured short circuit current$i_{sc}$) is compared with the measured values of unenergized Couette Charger. As a result, short circuit current was increased with voltage.

  • PDF

산화방지제 및 대전방지제의 첨가에 따른 유동대전특성에 관한연구 (The Effect of antioxidant or anti-static agent on the streaming electrification of insulating oil)

  • 최창락;박재윤;박상현;나동근;김영일;이덕출
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 C
    • /
    • pp.1045-1047
    • /
    • 1995
  • The effects of temperature ana additive on the streaming electrification of insulating oil have been investigated. The streaming current increases below the temperature of $45{\sim}50[^{\circ}C]$ and decreases above that. The inverse phenomenon of steaming current is exhibited as the concentration of anti-static agent increases.

  • PDF

유동 절연유의 전기전도에 관한 연구 (A study on electrical conduction of streaming insulating oil)

  • 심재홍;박재윤;이덕출;김왕곤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1991년도 추계학술대회 논문집 학회본부
    • /
    • pp.296-298
    • /
    • 1991
  • When insulating oil was flowed through a pipe, the electrostatic charge in the oil was increased using inflammability oil, an electrostatic phnomena which may cause significantly problems as explosion must be circumvented by some methods. In this paper, Streaming insulating oil electrificated by streaming electrification of electrification pipe and standing insulating oil were affected under the high field strength, temperature of insulating oil, and concentration of surfactant. The electrical conduction was compared and analysed by these influence.

  • PDF

전계가 가해진 절연유의 유동대전 특성 고찰 (Study on the Streaming Electrification of Insulating oil Under Electricfield)

  • 허창수;정중일
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제10권4호
    • /
    • pp.334-341
    • /
    • 1997
  • Streaming electrification on insulating paper and pressboard under D.C. and A.C. electric field was investigated by using paper tubes and oil circulation apparatus. At first, flowing of static charges as measured with no electric field. As the temperature of oil increased, the measured current curve hows peak. As the velocity increased, it shows increasing exponential curve. Then, we applied A.C. and D.C. electric field on paper tube and the current from relaxation tank to earth was measured, which other factors such as temperature and velocity were varied like case of no electric field. The ions in oil carry the charges. So electric field makes asymmetry effect, and electrophoretic effect on ions in oil. We find that as the electric field intensity increased, the charges which were made by electric double layer were increased. The charge vs. velocity curve made peak point at a velocity.

  • PDF

변압기 절연유의 순환 계통에서의 흐름 조건의 개선에 의한 유동대전현사의 완화 방법에 관한 연구 (A Study on the Method for Mitigation of Streaming Electrifiction by the Improvement of Flow Condition in the Oil Folw System of Transformer)

  • 권석두;남상천
    • 대한전기학회논문지
    • /
    • 제43권4호
    • /
    • pp.594-600
    • /
    • 1994
  • The maximum charge accumulation in transformers caused by streaming electrification is commonly observed on the bottom area of transformer winding(i.e.the oil inlet of transformer winding). It is because turbulent flows occur in this portion of transformers. Consequently, if we are to reduce the maximum charge accumulation of transformers, it is important that we should have a good understanding of the conditions of the occurence of partial turbulent flows in the oil inlet of transformer winding. With this point in mind, a simple flow model was designed in this study in order to simulate oil flow in the insulation ducts of power transformers. As a method for mitigating charge accummulation, attention was given to (a) a flow path design for the improvement of flow conditions, and (b) the charge tendency of the material used this design. The results of this study show that the above method is useful for mitigating charge accumulation.

  • PDF

친환경 식물성절연유의 유동대전현상 연구 (Research of Flow Electrification Phenomena of the used Environment-Friendly Vegetable Insulating Oils)

  • 최순호;허창수
    • 전기학회논문지
    • /
    • 제61권4호
    • /
    • pp.580-584
    • /
    • 2012
  • The insulating oils perform a cooling and insulation action in electric power transformer. The mineral oil has immanent fire dangerousness and environmental contamination problem. Vegetable insulating oil has higher ignition point, flash point and more excellent biodegradability than conventional mineral oil. In a real oil-filled transformers, some of the power is dissipated in the form of heat. And transformer require the heat to be removed from the winding and insulator by forced convection of the insulating oil. The flow electrification occurs when insulating oil was forced to be circulated. In this paper, influence of temperature, velocity of flow, and insulating pipe and diameter on streaming electrification of vegetable insulating oil was investigated using forced circulation apparatus. Temperature effects were most significant, and it showed a peak in the temperature $30^{\circ}C$ to $35^{\circ}C$ at insulating and copper pipe. The change of flow electrification according to area variety could be checked by change of diameter.

이온성 및 양성 계면 활성제가 변압기유의 화학적 특성 및 유동대전에 미치는 영향 (Influence of Interface Active substances(Ionic and Amphoteric) on Chemical property and Streaming Electrification of Transformer Oil)

  • 김용운;이덕출
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제10권7호
    • /
    • pp.719-726
    • /
    • 1997
  • This research was conducted to analyze the change of surface tension, viscosity, streaming current and conductivity of transformer oil when it were injected with the interface active substances.(anionic:S-111, cationic:S-121, amphoteric:S-131) The changes properties of the surface tension and viscosity of the oil which were injected with the interface active substances were divided into the changes area and the minimum reduction area. The surface tension and viscosity of the oil which were injected with three different kinds of interface active substances showed remarkable change at the point where the concentration of the substance in anionic, in cationic and in amphoteric were 100[ppm], 10[ppm] and 1[ppm] respectively. The streaming current and conductivity of the same sample oil were also changed at the same densities of the surface tension and viscosity. For this factor, it was possibile for us to interpret the mechanism of the streaming current and conductivity. Therefore the interface active substances of the three kinds were injected into the oil within the limit of optimal volume, prevention effects of electrification were showed more excellence than unmixed insulating oil.

  • PDF