• 제목/요약/키워드: Steam Overpressurization

검색결과 2건 처리시간 0.013초

OVERVIEW OF CONTAINMENT FILTERED VENT UNDER SEVERE ACCIDENT CONDITIONS AT WOLSONG NPP UNIT 1

  • Song, Y.M.;Jeong, H.S.;Park, S.Y.;Kim, D.H.;Song, J.H.
    • Nuclear Engineering and Technology
    • /
    • 제45권5호
    • /
    • pp.597-604
    • /
    • 2013
  • Containment Filtered Vent Systems (CFVSs) have been mainly equipped in nuclear power plants in Europe and Canada for the controlled depressurization of the containment atmosphere under severe accident conditions. This is to keep the containment integrity against overpressure during the course of a severe accident, in which the radioactive gas-steam mixture from the containment is discharged into a system designed to remove the radionuclides. In Korea, a CFVS was first introduced in the Wolsong unit-1 nuclear power plant as a mitigation measure to deal with the threat of over pressurization, following post-Fukushima action items. In this paper, the overall features of a CFVS installation such as risk assessments, an evaluation of the performance requirements, and a determination of the optimal operating strategies are analyzed for the Wolsong unit 1 nuclear power plant using a severe accident analysis computer code, ISAAC.

APR1400 IRWST Pool 온도분포 해석 (A Numerical Study on the IRWST Pool Temperature Distributionin in APR1400)

  • 강형석;배윤영;박종균
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.813-820
    • /
    • 2001
  • The Safety depressurization System(SDS) of KNGR prevents RCS from overpressurization by discharging high pressure and temperature coolant through the I-sparger into the IRWST during an accident. If IRWST water temperature rise locally, around the sparger, beyond $200_{\circ}$2000 F by the discharged coolant, unstable steam condensation can cause large pressure load on the IRWST wall. To investigate whether this condition can be avoided for the design basis event IOPOSRV(Inadvertent Opening of one Pilot Operated Safety Relief Valve), the flow and temperature distribution of water in the IRWST is calculated by using CFX 4.3 computational fluid dynamic code. According to the results, since pool water temperature does not exceeds temperature limit within 50 seconds after the opening of one POSRV, it can be assured that the integrity of IRWST wall is maintained.

  • PDF