A study on the Analysis of Insulation Aging for Generator stator windings (수력발전기 고정자권선의 절연열화 분석)

  • Byun, D.G.;Oh, B.K.;Kang, D.S.;Lim, K.J.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2072-2074
    • /
    • 2005
  • This test was performed to assess the insulation condition of the stator winding of 3.45kV hydro generator in insulation deterioration condition which was due to long service period(30years) since installed We extracted 12 stator wingdings from the hydro generator core, cut the stator windings into three parts(Middle winding part, slot winding part, end wingding part), and evaluated the insulation condition to know the deterioration condition of each parts. This insulation diagnostic tests include AC current, dissipation factor, and partial discharg test.

  • PDF

A Method for Indentifying Broken Rotor Bar and Stator Winding Fault in a Low-voltage Squirrel-cage Induction Motor Using Radial Flux Sensor

  • Youn, Young-Woo;Hwang, Don-Ha;Sun, Jong-Ho;Kang, Dong-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.5
    • /
    • pp.666-670
    • /
    • 2011
  • In this paper, a method for detecting broken rotor bar and stator winding fault in a low voltage squirrel-case induction motor using an air-gap flux variation analysis is proposed to develop a simple and low cost diagnosis technique. To measure the leakage flux in radial direction, a radial flux sensor is designed as a search coil and installed between stator slots. The proposed method is able to identify two kinds of motor faults by calculating load condition of motors and monitoring abnormal signals those are related with motor faults. Experimental results obtained on 7.5kW three-phase squirrel-cage induction motors are discussed to verify the performance of the proposed method.

A Study On The Stator Slot Shape Design of BLDC Motor (BLDC 모터 고정자 슬롯 형상설계에 관한 연구)

  • Han, Sang-Rog;Lee, Kang-Yeon;Jeong, Byeong-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.5
    • /
    • pp.41-49
    • /
    • 2015
  • In this paper, we studied an optimal design and efficiency improvement of the BLCD motor used in home electronic appliance. The number of stator slots is chosen depending on the rotor poles, phase number, and the winding configuration. In general, a fractional slots/pole design is preferred to minimize cogging torque. To reduce the winding resistance, we reduced the coil length and we improved the coil space factor. We proposed three types of stator slot shape design for the optimal BLDC motor design. One of them, U-type slot shape is a best optimal design, it proved by the simulated and tested. Optimal design of essential parameters aiming at high winding factor are presented to create for a high-quality system implementation. Design analysis is verified by testing and building a prototype motor.

A Study on Insulation Diagnosis by Partial Discharge Spectroscopy of Generator Stator Winding (발전기 고정자 권선의 부분방전 특성을 이용한 절연진단 연구)

  • Kang, D.S.;Kim, Y.J.;Kim, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1993.07b
    • /
    • pp.584-587
    • /
    • 1993
  • Mica, which have a good thermal and electrical characteristics, while will cleave easily at these layers. In order to bond mica materials soldily, mica/epoxy composite insulation materials were developed for generator stator winding. There are lots of problems such as delamination and partial discharge of these insulation materials caused by mechanical, electrical and thermal aging. Several experiments have been conducted in order to find the useful diagnostic parameters from the partial discharge phenomena by applying a new measurement techniques. this paper deals with the partial discharge pulse characteristics, which may be a useful diagnostic concept in predicting insulation condition of generator stator insulation materials. Long term insulation aging test shows that partial discharge phase angle an magnitude are identified as one of the main key techniques for insulation diagnosis on generator stator winding.

  • PDF

A Study on Insulation Properties of Global VPI Type Generator through Replacement of Stator Windings

  • Kong, Taesik;Kim, Heedong;Lee, Sooho;Park, Jaehyun
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.3 no.2
    • /
    • pp.113-117
    • /
    • 2017
  • As the competition in the manufacturing market for small and medium sized generators is intensifying, there is increasing pressure to reduce production cost. Manufacturing the generator stator windings with global vacuum pressure impregnation (GVPI) is a very effective way to reduce costs. However, the stator winding has a fatal disadvantage in that the insulation wears due to vibration in the slot. KEPRI (KEPCO Research Institute) conducted insulation diagnosis for three generators in KOMIPO (Korea Midland Power Co., Ltd.) which were manufactured by GVPI and operated for about 17 years. Insulation diagnosis showed that deterioration of insulation has progressed significantly. Therefore, KEPRI recommended replacing the stator windings of all three generators. In this paper, the insulation properties of the generator stator winding with global GVPI are described by comparing and analyzing the insulation diagnosis results and visual inspection for stator windings.

Assessment of Insulation Deterioration in Stator Windings of High Voltage Motor (고압전동기 고정자 권선의 절연열화 평가)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.5
    • /
    • pp.711-716
    • /
    • 2012
  • To assess the insulation deterioration of stator windings, diagnostic and AC breakdown tests were performed on the eleven high voltage (HV) motors rated at 6kV. After completing the diagnostic tests, the AC overvoltage test was performed by gradually increasing the voltage applied to the stator windings until electrical insulation failure occurred, to obtain the breakdown voltage. Stator winding of motors 1, 3, and 8 failed at above rated voltage at 14 kV, 13.8kV, and 16.4kV, respectively. The breakdown voltage of three motors was higher than expected for good quality windings in 6kV motors. Based on deterioration evaluation criteria, the stator winding insulation of eleven HV motors are confirmed to be in good condition. The turning point of the current, $P_{i2}$, in the AC current vs. voltage characteristics occurred between 5kV and 6kV, and the breakdown voltage was low between 13.8kV and 16.4kV. There was a strong correlation between the breakdown voltage and various electrical characteristics in diagnostic tests including Pi2.

On-Line Insulation Diagnosis Techniques for Stator Winding of Rotating Machines (회전기 고정자 권선에서의 운전 중 절연열화 진단기법)

  • 윤대희;황돈하;신병철;김용주;이광식
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.89-93
    • /
    • 2000
  • Recently many research activities on the diagnosis of stator winding insulation of large rotating machines have been reported. Capacitive couplers are widely used as sensors for on-line partial discharge (PD) measurement of high voltage rotating machines. This paper presents laboratory test to compare Stator Slot Coupler (SSC), Resistance Temperature Detector (RTD), 80 [pF] coupler and 500 [pF] coupler for on-line PD measurement of rotating machines. And a novel on-line monitoring system for an insulation diagnosis is proposed.

  • PDF

Stator winding faults diagnosis system of induction motor using LabVIEW (LabVIEW를 이용한 유도전동기 고정자 권선 고장진단시스템)

  • Song, Myung-Hyun;Park, Kyu-Nam;Lee, Tae-Hun;Han, Dong-Gi;Park, Kyung-Han
    • Proceedings of the KIEE Conference
    • /
    • 2005.07d
    • /
    • pp.2658-2660
    • /
    • 2005
  • This paper presents a stator winding fault diagnosis technique of induction motor on the PC - based virtual instrumentation system designed using the graphical programming language LabVIEW. This method collects the 3-phase current signals using the current probe amplifier and PXI/DAQ system then the preprocessing removes the noise using LPF, after then this method transforms the stator current to Park's vector and obtains the each Park's Vector pattern and detects stator winding fault by comparing the obtained faulted pattern with the healthy pattern. This proposed LabVIEW based diagnosis system is applied to the 3 phase 1 hp induction motor and obtained the reasonable results under no load condition. The test results give us the possibility a simple and realistic on-line winding fault diagnosis system.

  • PDF

A Study on the Polarity Discrimination Method of the Stator Windings for 3 Phase Induction Motors based on the Residual Magnetism and I Winding Connection (잔류자기와 I 결선에 의한 3상유도전동기 고정자 권선의 극성판별법에 대한 연구)

  • Choi, Soon-Man
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.1
    • /
    • pp.72-77
    • /
    • 2015
  • When connecting 6 lead wires from stator windings to the terminals of 3 phase induction motors for Y or ${\triangle}$ connection, it is feared that the polarities of windings could be reversed each other if the wire tags are lost or erased, resulting in inadmissibly high current to motors in case of starting. To protect motors against such situations, some test procedures are necessary during wire connection which need to be easy ways to electricians without particular tools except a general multi-tester and with less time-consuming in the field. This study focuses on a test measure to satisfy these requirements which is able to provide them a convenient procedure for winding polarity discrimination considering the field condition. Here, the proposed measure utilizes the residual magnetism of the rotor and checks the indication of voltage or current at windings which are induced by the residual flux of rotor when rotating it by hands with 3 stator windings connected in the form of I connection. Principle characteristics and experiment results for this method are analyzed in the view of the effectiveness and applicability for the winding polarity discrimination.

The Characteristics Analysis of a PMSM with Current Angle Variations according to Stator Winding Arrangements (전류위상 변화 시 고정자 권선방법에 따른 이중 3상 영구자석 동기 전동기의 특성 해석)

  • Kim, Tae Heoung
    • Journal of IKEEE
    • /
    • v.24 no.2
    • /
    • pp.441-445
    • /
    • 2020
  • A Permanent Magnet Synchronous Motor (PMSM) for an electrical power steering system (EPS) is adopting various dual three-phase type stator windings to get the high fault tolerance capability when the motor runs at the failure condition. In this paper, we analyze the effects of stator winding arrangements on the characteristics such as torque and efficiency of the PMSM with leading and lagging current angle variations using finite element method. As a result, the most valuable design criteria are proposed to select stator winding method. Especially, we suggest the most appropriate winding method in terms of torque and efficiency, extending constant output area and decreasing noise and torque ripples.