• 제목/요약/키워드: Smoke layer

검색결과 119건 처리시간 0.021초

A Study on the Fire Safety of High-rise Apartments Based on Fire Door Switch and Automatic Fire Extinguishing System

  • Zhang, ZeChen;Kong, Ha-Sung
    • International Journal of Advanced Culture Technology
    • /
    • 제9권4호
    • /
    • pp.424-430
    • /
    • 2021
  • The purpose of this study is to analyse the characteristics and spreading laws of parameters such as fire smoke, concentration of CO, visibility, and temperature at fire scene in high-rise residential buildings under the different conditions of fire doors and automatic fire extinguishing systems. Using Pyrosim to simulate diverse fire scenes in a high-rise apartment with corridors, to analyze the changes in those parameters. The results show that when a fire occurs, closing the fire-fighting corridor will increase the smoke temperature and concentration of CO in the stairwell, and reduce the height and visibility of the smoke layer; the automatic fire extinguishing system effectively suppresses the increase in the temperature of the fire smoke and the sedimentation of the smoke layer. Reasonable setting and operation of the automatic fire extinguishing system could effectively inhibit the spread of fire. Although closing fire corridor can slow down the direct upward spread of smoke through the corridor, it will force the fire smoke into the stairwell, which will seriously affect evacuation through the stairs. Therefore, in order to reduce risks, it is forbidden to close the fire doors of the firefighting corridor and stacking combustible materials in the corridor, Also, intensifying inspections and ensuring the normal operation of the automatic fire extinguishing system are indispensable. Based on the research results, the significance of installing fire-fighting facilities in the construction of high-rise apartments was discussed and proved.

아트리움에서 화재 발생시 복사가 고려된 연기거동에 대한 수치해석 연구 (A Numerical Study of Smoke Movement with Radiation in Atrium Fires)

  • 정진용;유홍선;홍기배
    • 한국화재소방학회논문지
    • /
    • 제15권1호
    • /
    • pp.7-15
    • /
    • 2001
  • 본 연구는 3차원 아트리움 공간(일본의 SIVANS 아트리움)내에서 화재 발생시 복사가 고려된 연기의 거동을 알아보기 위해 자체개발한 SMEP(Smoke Movement Estimating Program) Held 모델을 사용하여 수치해석하였다. PISO 알고리즘과 부력항을 포함한 수정 k-$\\varepsilon$ 난류모델을 사용한 SMEP은 연속, 운동, 에너지, 농도 그리고 복사 열 전달 방정식을 풀었으며, 복사 열 전달 방정식의 해석을 위하여 S-N 구분종좌표법을 채택하여 사용하였다. 수치해석 결과 연기의 온도분포는 복사와 대류를 힘께 고려했을 경우가 대류만을 고려했을 경우 보다 실험결과와 근사한 경향을 나타내었다. 이것은 연기속에 포함되어 있는 연소생성을 중 $H_2$O와 $CO_2$ 가스의 복사 영향 때문이며, 따라서 좀더 실제적인 화재해석에 있어서 연기의 복사 영향을 고려하는 것이 필요하다. 또한 연층의 하강 복도는 약 0.l m/s이었으며 피난수준인 바닥 1.5m까지 연층이 도달하는 데에는 56 kW의 Ultra Fast Fire의 경우 약 450초의 시간이 걸렸다.

  • PDF

배연창 크기와 스프링클러 작동이 인명안전에 미치는 영향 연구 (A Study on the Effectiveness to the Life Safety by Enlarging Smoke Vent Size and/or Sprinklered System)

  • 김학중;박용환;임채현;김범규
    • 한국화재소방학회논문지
    • /
    • 제24권2호
    • /
    • pp.133-138
    • /
    • 2010
  • 최근 건축물이 대형화, 복잡화되면서 건축물내 거주자의 피난안전성이 관심의 초점이 되고 있다. 국내 건축물은 용도에 따라 관계법령에 의한 배연창 또는 기계적 배연설비를 설치하도록 규정되어 있다. 화재시 거주자의 피난안전성을 확보하기 위하여 화재실의 제연이 매우 중요하다. 본 연구에서는 배연창 크기의 변화와 스프링클러 설비의 작동이 화재실 연기층 높이와 온도 조건에 미치는 영향을 화재 시뮬레이션프로그램인 CFAST를 이용하여 평가 하였다. 연구결과 배연창 면적이 증가할수록 5MW 화재 크기 이하에서는 연기층 높이와 온도에 미치는 효과가 증가하나 화재크기가 10MW 이상 커지면 배연창의 면적과 연기배출 효과와의 상관성이 떨어진다. 스프링클러 설비가 작동하고 배연창이 열릴 경우에는 화재크기와 상관없이 인명안전기준이 만족되었다. 법규에 의한 일률적인 배연창 면적의 적용보다는 건축물의 용도 및 규모에 따라 화재시나리오를 선정하고 시나리오에 따른 화재 크기에 따라 적절한 크기의 배연창을 적용하여야 하며 실제 실험이나 시뮬레이션을 통한 검증이 이루어져야 한다.

짧은 터널 내의 연기거동에 관한 연구 (A Study of Smoke Movement in a Short Tunnel)

  • Kim, Sung-Chan;Ryou, Hong-Sun;Kim, Chung-Ik;Hong, Ki-Bae
    • 터널과지하공간
    • /
    • 제12권1호
    • /
    • pp.31-36
    • /
    • 2002
  • 터널화재시 화원의 크기에 따른 연기기동을 파악하기 위하여 모현실험 및 수치해석이 수행되었다. 모형실험의 결과를 실제 터널에 대해 적용하기 위하여 Frode상사법을 이용하였다. 터널공간내의 화재 해석에 대한 수치해석의 타간성을 입증하기 위하여 모형실험과 수치해석에서 얻어진 연층의 온도분포를 비교하였다. 터널내 온도분포를 해석함으로써 배기장치가 없는 짧은 터널에 대하여 연층은 전체 터널 높이의 절반 이하로 하강하지 않는다는 사실을 파악하였다. 또한 실험에서 얻어진 연층선단의 전파속도는 화재 발생부의 1/3 풍에 비례한다는 사실을 파악하였으며 이는 기존의 경험식 및 수치해석결과와도 잘 일치하였다. 따라서 짧은 터널에서 화재시 피난대책을 수립하는데 있어서 연층의 수평전파가 수직전파에 비해 중요한 설계변수임을 본 연구를 통하여 제시하였다.

저 레이놀즈수에서 비정상 에어포일의 흐름 가시화 (Flow Visualization of an Unsteady Airfoil at Low Reynolds Numbers)

  • 김동하;장조원
    • 한국가시화정보학회지
    • /
    • 제4권2호
    • /
    • pp.51-58
    • /
    • 2006
  • A boundary layer visualization was carried out in order to investigate the influence of Reynolds number on an oscillating airfoil. An NACA 0012 airfoil is sinusoidally pitched at the quarter chord point with oscillation amplitude of ${\pm}6^{\circ}$. A smoke-wire technique was employed to visualize the boundary layer and the near-wake. The freestream velocities are 1.98, 2.83 and 4.03m/s and corresponding chord Reynolds numbers are $2.3{\times}10^4,\;3.3{\times}10^4$, and $4.8{\times}10^4$, respectively. As the reduced frequency of K=0.1 is fixed, the corresponding frequency of an airfoil was adjusted in each case. The results reveal that the point at which the shear stress in an unsteady boundary layer separation disappears does not correspond with the position of the breakdown of the boundary layer, and that the breakdown of the boundary layer occurs further downstream.

  • PDF

A Study on Smoke Movement in Room Fires with Various Pool Fire Location

  • Jeong, Jin-Yong;Ryou, Hong-Sun
    • Journal of Mechanical Science and Technology
    • /
    • 제16권11호
    • /
    • pp.1485-1496
    • /
    • 2002
  • In order to investigate the fire-induced smoke movement in a three-dimensional room with an open door, numerical and experimental study was performed. The center, wall, and corner fire plumes for various sized fires were studied experimentally in a rectangular pool fire using methanol as a fuel. The numerical results from a self-developed SMEP (Smoke Movement Estimating Program) field model were compared with experimental results obtained in this and from literature. Comparisons of SMEP and experimental results have shown reasonable agreement. As the fire strength became larger for the center fires, the air mass flow rate in the door, average hot layer temperature, flame angle and mean flame height were observed to increase but the doorway-neutral-planeheight and the steady-state time were observed to decrease. Also as the wall effect became larger in room fires, the hot layer temperature, mean flame height, doorway-neutral-planeheight and steady-state time were observed to increase. In the egress point of view considering the smoke filling time and the early spread of plume in the room space, the results of the center fire appeared to be more dangerous as compared with the wall and the corner fire. Thus it is necessary to consider the wall effect as an important factor in designing efficient fire protection systems.

대공간 화재시 배연효율 정의에 관한 수치해석적 연구 (Numerical Study on the Definition of the Exhaust Effectiveness of Smoke under Fire in a Large Space)

  • 김정엽;장경진;한화택
    • 설비공학논문집
    • /
    • 제26권11호
    • /
    • pp.535-540
    • /
    • 2014
  • This paper investigates the exhaust effectiveness of smoke, in the case of fire in a large atrium space. Numerical analysis was conducted to simulate transient fire growth in a test room, modeled by the Murcia atrium fire test. Various indices representing the exhaust performance of the exhaust system were obtained, such as the height of the smoke layer, and the instantaneous and accumulative capture efficiency of the smoke. The residual life time of smoke from the fire was also obtained, by injecting tracer gases at the fire location, depending on the airflow rate, and the location of the exhausts. The capture efficiency based on smoke concentration at the exhausts exhibits how much smoke can be removed by the exhaust system; whereas, the exhaust effectiveness based on residual life time indicates how rapidly the smoke can reach the exhaust locations, before being exhausted. The definitions and meanings of the indices to be used in representing the exhaust performance of a smoke exhaust system installed in a large space are discussed.

터널화재시 자연환기에 의한 연기거동에 관한 실험적 연구 (An Experimental Study of Smoke Movement in Tunnel Fires with Natural Ventilation)

  • 김충익;유홍선;이성룡;박현태
    • 설비공학논문집
    • /
    • 제14권3호
    • /
    • pp.247-253
    • /
    • 2002
  • In this study, reduced-scale experiments were conducted to analyze smoke movement in tunnel fire with roof vent. The 1/20 scale experiments were carried out under the Froude scaling using gasoline pool fire ranging from 7.3 to 15.4 cm in diameter with total heat release rate from 1.0 to 8.46kw. In case of 1 m high vent, smoke front reached to the tunnel exit at about 16 sec delayed with ventilation. The delay time grew longer with the vent height. The temperature after the vent was lower than that without the vent. The exit temperature declined maximum of $20^{\circ}C$ after passing the vent. It was confirmed that the thickness of smoke layer was maintained uniformly under the 25% height of the tunnel through the visualized smoke now by a laser sheet and the digital camcorder.

터널 화재시 자연 배기에 의한 연기 거동에 관한 실험적 연구 (An Experimental Study of Smoke Movement in Tunnel Fires with Natural Ventilation)

  • 이성룡;김충익;유홍선
    • 한국화재소방학회논문지
    • /
    • 제15권1호
    • /
    • pp.1-6
    • /
    • 2001
  • 본 연구는 터널내 화재발생시 자연 배기에 의한 연기의 거동을 해석하기 위하여 축소모형 실험을 수행하였다. 터널내 연기의 유동은 부력에 의해 지배되므로 Froude scaling에 의해 실물 터널을 1/20로 축소한 모형터널에서 실험을 수행하였으며 배기구의 위치변화에 따른 영향을 평가하기 위하여 화원으로부터 각각 1m, 2m, 3m 떨어진 곳에 배기구를 대칭으로 위치시켜 세가지 경우에 대해 실험을 실시하였다. 지름이 4.36 cm인 화원의 경우, 배기구의 위치에 관계없이 배기구 통과 후 연층의 온도가 배기를 실시하지 않은 경우와 비교하여 약 7~$8^{\circ}$ 낮게 유지되었다. 지름이 5.23cm인 화원의 경우, 배기구가 화원에 가까울수록 배기구 통과 후 연기의 평균속도가 감소하였으며 최대 3.86초가 지연되었다. CASE 1에서는 배기구 통과 후 천장에서 약 $8^{\circ}c$, 수직온도가 약 $7^{\circ}c$ 감소하였으며, CASE 2에서는 천장과 수직온도가 약 $3^{\circ}c$ 감소하였으며, CASE 3에서는 각각 약 $2^{\circ}c$가 감소하였다. 레이저와 디지털 캠코더를 이용하여 배기구 주위의 연기 유동을 가시화하여 화재발생 약 1분 후부터 연층의 두께가 터널높이의 25%이하로 일정하게 유지되는 것을 확인할 수 있었다.

  • PDF

구획화재의 출입구를 통한 광학적 연기밀도 측정의 불확실성 해석 (Uncertainty Analysis of the Optical Smoke Density Measurement through the Doorway in a Compartment Fire)

  • 김성찬
    • 한국화재소방학회논문지
    • /
    • 제27권2호
    • /
    • pp.75-79
    • /
    • 2013
  • 본 연구는 구획화재의 출입구를 통한 연기밀도를 정량적으로 측정하고 측정기법의 신뢰성을 평가하기 위해 불확실성 해석을 수행한다. 메탄 화재 강도에 따른 축소모형 구획공간의 출입구 상층부를 통해 유출되는 연기 유동에 대해 광소멸 측정을 수행하고 Bouguer's의 법칙을 적용하여 연기밀도를 산정하였다. 광투과율, 경로길이, 질량비광소멸상수에 대하여 연기밀도의 측정 불확실도를 평가하였으며 계산된 연기밀도 측정의 확장불확실도는 20% 정도이며 신뢰수준은 95% 이다. 준정상상태의 화재 발열량에 대하여 출입구에서의 평균 연기밀도를 산정하였으며 구획공간내부의 총괄당량비 증가에 따라 출입구의 연기농도가 선형적으로 증가하는 경향을 보였다.