• 제목/요약/키워드: Smoke Height

검색결과 94건 처리시간 0.022초

옥내화재시 급기구의 높이에 따른 암흑화에 관한 연구 (A Study of Obscuration on Height of Air Supply in Indoor Fire)

  • 이창섭
    • 한국화재소방학회논문지
    • /
    • 제15권3호
    • /
    • pp.1-6
    • /
    • 2001
  • 옥내화재에서 높이에 따른 암흑화의 정도를, 본 연구를 목적으로 제작된 스모크박스를 이용한 실험을 통해 측정하였다. 연기로 인한 암흑화의 정도는 높이에 따라서 결정되는데, 높은 곳일수록 그 정도가 심했다. 그러나 급기구가 있는 높이에서는 암흑화가 심해지는 변이가 일어났다.

  • PDF

터널화재시 자연환기에 의한 연기거동에 관한 실험적 연구 (An Experimental Study of Smoke Movement in Tunnel Fires with Natural Ventilation)

  • 김충익;유홍선;이성룡;박현태
    • 설비공학논문집
    • /
    • 제14권3호
    • /
    • pp.247-253
    • /
    • 2002
  • In this study, reduced-scale experiments were conducted to analyze smoke movement in tunnel fire with roof vent. The 1/20 scale experiments were carried out under the Froude scaling using gasoline pool fire ranging from 7.3 to 15.4 cm in diameter with total heat release rate from 1.0 to 8.46kw. In case of 1 m high vent, smoke front reached to the tunnel exit at about 16 sec delayed with ventilation. The delay time grew longer with the vent height. The temperature after the vent was lower than that without the vent. The exit temperature declined maximum of $20^{\circ}C$ after passing the vent. It was confirmed that the thickness of smoke layer was maintained uniformly under the 25% height of the tunnel through the visualized smoke now by a laser sheet and the digital camcorder.

대공간 축연실험 (Experiments on Smoke Filling in a Large Space)

  • 한용식;김명배;장용재;윤명오;김진곤
    • 한국연소학회:학술대회논문집
    • /
    • 한국연소학회 1998년도 제17회 KOSCI SYMPOSIUM 논문집
    • /
    • pp.37-46
    • /
    • 1998
  • In this experiments, smoke filling behaviors in a large space were investigated. Also, it found that the smoke filling time can be predicted with a simplified zone model. Thermocouples were used to measure the temperature of the hot gases layer and also later to determine the smoke layer depth. Height markers were also hung from the roof so that observers could visibly assess the smoke layer depth.

  • PDF

배연창 크기와 스프링클러 작동이 인명안전에 미치는 영향 연구 (A Study on the Effectiveness to the Life Safety by Enlarging Smoke Vent Size and/or Sprinklered System)

  • 김학중;박용환;임채현;김범규
    • 한국화재소방학회논문지
    • /
    • 제24권2호
    • /
    • pp.133-138
    • /
    • 2010
  • 최근 건축물이 대형화, 복잡화되면서 건축물내 거주자의 피난안전성이 관심의 초점이 되고 있다. 국내 건축물은 용도에 따라 관계법령에 의한 배연창 또는 기계적 배연설비를 설치하도록 규정되어 있다. 화재시 거주자의 피난안전성을 확보하기 위하여 화재실의 제연이 매우 중요하다. 본 연구에서는 배연창 크기의 변화와 스프링클러 설비의 작동이 화재실 연기층 높이와 온도 조건에 미치는 영향을 화재 시뮬레이션프로그램인 CFAST를 이용하여 평가 하였다. 연구결과 배연창 면적이 증가할수록 5MW 화재 크기 이하에서는 연기층 높이와 온도에 미치는 효과가 증가하나 화재크기가 10MW 이상 커지면 배연창의 면적과 연기배출 효과와의 상관성이 떨어진다. 스프링클러 설비가 작동하고 배연창이 열릴 경우에는 화재크기와 상관없이 인명안전기준이 만족되었다. 법규에 의한 일률적인 배연창 면적의 적용보다는 건축물의 용도 및 규모에 따라 화재시나리오를 선정하고 시나리오에 따른 화재 크기에 따라 적절한 크기의 배연창을 적용하여야 하며 실제 실험이나 시뮬레이션을 통한 검증이 이루어져야 한다.

지하철 화재시 제연모드에 따른 열 및 연기 배출 특성 연구 (A Study on Heat and Smoke Exhaust Characteristics from the Subway Fire for Different Ventilation Modes)

  • 장희철;윤경범;박원희;김태국
    • 한국방재학회 논문집
    • /
    • 제8권3호
    • /
    • pp.37-42
    • /
    • 2008
  • 본 연구는 지하철에서 화재발생시 최적의 제연모드 예측을 목적으로 수치해석을 수행하였다. 현재 국내 지하철 화재발생시 제연모드는 승강장 내 화재구역 배기, 비화재구역 급기 또는 정지로 설정 되어있다. 수치해석 조건은 2가지 국내 비상시 제연모드 및 발화 4분(승강장 피난허용시간, NFPA 130) 이전까지 승강장에서 배기를 하며, 발화 4분이 후 터널 배기로 전환되는 스위치모드의 3가지 경우에 대하여 비교 분석하였다. 승객 호흡높이(1.7 m)를 기준으로 열, 일산화탄소 및 가시거리를 비교하였다. 수치해석 결과 급기팬 작동은 연기를 교란시키고 확산시킬 수 있으며, 또한 승강장 및 터널 제연모드로 작동할 경우 승강장의 제연모드로만 작동한 경우에 비하여 연기 배출에 효과적임을 확인할 수 있었다.

거실 제연설비 성능 개선을 위한 국내·외 기준 비교 분석에 관한 연구 (A Comparative Analysis of Domestic and Foreign Standards to Improve the Performance of Zone Smoke Control System)

  • 허예림;김윤성;김혜원;진승현;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2022년도 봄 학술논문 발표대회
    • /
    • pp.83-84
    • /
    • 2022
  • In Korea, smoke control measures through NFSC 501 are proposed to reduce human casualties caused by smoke in the event of a fire. However, as a result of investigating and analyzing domestic and foreign standards, it was found that domestic regulations do not set fire source, but simply set smoke emissions by floor area or height of smoke boundary. Foreign regulations set fire source. Therefore, it is judged that it is necessary to review whether the current domestic regulations can be applied in the event of an actual building fire. So, this paper aims to identify the differences in domestic and foreign standards through investigation and analysis of related standards for fire zone smoke control system in each country and use them as basic data to improve the performance of zone smoke control system.

  • PDF

A Study on Smoke Movement in Room Fires with Various Pool Fire Location

  • Jeong, Jin-Yong;Ryou, Hong-Sun
    • Journal of Mechanical Science and Technology
    • /
    • 제16권11호
    • /
    • pp.1485-1496
    • /
    • 2002
  • In order to investigate the fire-induced smoke movement in a three-dimensional room with an open door, numerical and experimental study was performed. The center, wall, and corner fire plumes for various sized fires were studied experimentally in a rectangular pool fire using methanol as a fuel. The numerical results from a self-developed SMEP (Smoke Movement Estimating Program) field model were compared with experimental results obtained in this and from literature. Comparisons of SMEP and experimental results have shown reasonable agreement. As the fire strength became larger for the center fires, the air mass flow rate in the door, average hot layer temperature, flame angle and mean flame height were observed to increase but the doorway-neutral-planeheight and the steady-state time were observed to decrease. Also as the wall effect became larger in room fires, the hot layer temperature, mean flame height, doorway-neutral-planeheight and steady-state time were observed to increase. In the egress point of view considering the smoke filling time and the early spread of plume in the room space, the results of the center fire appeared to be more dangerous as compared with the wall and the corner fire. Thus it is necessary to consider the wall effect as an important factor in designing efficient fire protection systems.

지하철터널 환기변환모드에 따른 안전성 평가에 관한 연구 (A study on safety evaluation by changing smoke ventilation mode in subway tunnels)

  • 이동호
    • 한국터널지하공간학회 논문집
    • /
    • 제5권4호
    • /
    • pp.389-400
    • /
    • 2003
  • 본 연구는 지하철방재대책의 일환으로 터널구간에 설치된 환기기의 제연절환 운전모드 및 승강장 선로부 환기장치를 포함한 6종류의 제연운전모드를 대상으로 승강장에 정차된 열차화재 시나리오에 따라 3차원 실시간 화재 시뮬레이션을 수행하여 제연방식별 열 및 연기전파특성을 규명함으로서, 승강장에서 열차 화재 발생시, 승객이 안전하게 최적 대피가 가능한 환기기의 제연절환 조합운전의 도출을 목표로 한다.

  • PDF

공연장 무대 화재 시 방화막과 강제 배연구가 객석으로의 연기 확산에 미치는 영향 (Effects of Fire Curtain and Forced Smoke Ventilation on Smoke Spread to Auditorium in Stage Fire of Theater)

  • 김재한;김동균;이치영
    • 한국화재소방학회논문지
    • /
    • 제31권5호
    • /
    • pp.28-36
    • /
    • 2017
  • 본 논문에서는 공연장 무대 화재 시 객석으로의 연기 확산에 방화막 및 강제 배연구가 미치는 영향에 대하여 Fire Dynamics Simulator (FDS)를 이용하여 연구를 수행하였다. 폭 31 m, 깊이 34 m, 높이 32 m의 무대에 대하여, 10 MW의 열방출률과 화재성장속도가 fast인 화재를 적용하였다. 강제 배출량은 화재안전기준과 기존 연구를 토대로 설정하였으며, 방화막과 프로시니움 (Proscenium) 벽 사이 간격은 0 m, 0.5 m인 경우를 대상으로 하였다. 방화막과 프로시니움 벽이 완벽하게 밀착되어 있는 경우, 강제 배연구와는 상관없이 객석으로의 연기 확산은 일어나지 않았다. 방화막과 프로시니움 벽 사이의 간격이 0.5 m인 경우, 방화막이 없는 경우에 비해 무대 공간 내에서 연기층이 더욱 낮은 높이까지 하강하였으며, 이는 방화막에 의해 객석으로의 연기 확산이 방해받았기 때문이다. 한편, 동일한 방화막 조건에서, 강제 배연구가 있는 경우가 없는 경우에 비해 방화막과 프로시니움 벽 사이 간격을 통한 유출 질량유량이 작았다. 본 연구를 통하여 방화막과 강제 배연구가 공연장 무대 화재 시 객석으로의 연기 확산을 억제할 수 있는 효과적인 방법임을 확인하였다.

업무용 빌딩의 피난 성능 검토에 관한 연구 (A Study on the Evacuation Performance Review for the Office Buildings)

  • 오혁진;백승태;김우석;이수경
    • 한국화재소방학회논문지
    • /
    • 제17권3호
    • /
    • pp.1-6
    • /
    • 2003
  • 본 연구에서는 특정의 업무용 건축물에 대해서 화재 및 피난 시나리오를 선정하여 FAST 3.1.7(전실화재 예측), SIMULEX 32-bit(피난시간의 예측), JASMINE 3.25d(특정시간까지의 연기 유동성 평가)등의 S/W를 이용하여 이를 평가했으며 그 결과는 다음과 같다. Scenario #1 결과, 화재실에서 전실화재가 발생하지 않았고, 층 피난시간은 25.2 sec로 나타났으며 이때까지의 FAST 3.1.7결과에서 연기층은 2.4m를 기록, 연기유동성 평가에서도 재실자들은 연기의 피해(가시거리, 독성)없이 피난이 완료될 것으로 나타났다. Scenario #2 결과, 화재실에서 6 min 33.2 sec에 전실화재가 발생했으며, 수계산에 의한 피난시간은 5 min 23sec로 나타났다. 본 대상건물에 대해서 선정한 Scenario #1, #2 모두 인명안전설계는 적정하게 설계되었다고 판단된다.