• Title/Summary/Keyword: Simulated Blow Mold Machine(BMM) System

Search Result 1, Processing Time 0.018 seconds

Design and Economics of HVAC System for Reduction of Power Consumption in Blow Mold Machine (플라스틱 연료탱크 생산 설비에서의 소비 전력 저감을 위한 공조 시스템 설계 및 경제성 평가)

  • Lee, Youngjae;Choi, Seukcheun
    • Journal of Power System Engineering
    • /
    • v.21 no.4
    • /
    • pp.84-93
    • /
    • 2017
  • This study was carried out to improve the electric power consumption of HVAC in the blow mold machine(BMM) and work environment. The experiment was conducted with the simulated HVAC system of 1/15 of the actual BMM. The temperature of main facility and two preheaters was fixed at 200 and $60^{\circ}C$ respectively in all test conditions. The measured points of temperature were chosen as critical locations considering the work environment. The tendency of temperature distributions decreases as the duct was closed to the main facility. The reduction rate of power consumption of HVAC increases up to 32.3% when both duct and cooling systems are operated. Also the efficiency of HVAC is improved about 9% through the modified design of duct system. It notes that the electric power consumption of HVAC can be reduced by the optimum design and operating condition of duct and cooling system.