• Title/Summary/Keyword: Self-regulating heating cable

Search Result 3, Processing Time 0.019 seconds

Fire Cause Reasoning of Self-regulating Heating Cable by a Fire Investigation Applying the Scientific Method and Fault Tree Analysis (과학적 방법을 적용한 화재조사와 결함수 분석을 이용한 정온전선의 발화원인 추론)

  • Kim, Doo-Hyun;Lee, Heung-Su
    • Fire Science and Engineering
    • /
    • v.30 no.4
    • /
    • pp.73-81
    • /
    • 2016
  • A self-regulating heating cable is an electrical heating element by flowing an electric current between parallel conductors filled with an extruded semi-conductive polymer. Self-regulating heating cables are used mainly for frost protection purposes because the construction is convenient and the price is low. On the other hand, structural problems with imperfections of the insulation can cause a fire despite their usefulness. This paper deduced a direct method to derive the cause by investigating the scene of a fire due to a self-regulating heating cable and analyzed the basic problem using fault tree analysis. In this paper, the actual fire scene was a cold storage warehouse, and fire investigation was conducted. After investigating the fire scene and fault tree analysis, the cause of the fire could be attributed to dielectric breakdown of the self-regulating heating cable. This paper could be utilized in the fire safety activities and similar fire investigations.

Effect of Crosslinking on the PTC Stability Carbon Black Filled HDPE/EEA Copolymer Composite (카본블랙 충전 HDPE/EEA Copolymer 복합재료에 있어서 가교구조가 PTC 특성에 미치는 영향)

  • Lee, Gun-Joo
    • Proceedings of the KIEE Conference
    • /
    • 2001.11a
    • /
    • pp.140-145
    • /
    • 2001
  • In order to apply for silane crosslinking process to PTC products, especially. self-regulating heater, silane crosslinked samples were compared with radiation crosslinked sample in terms of PTC characteristic and PTC stability. Silane crosslinked samples have lower PTC intensity than radiation crosslinked sample. It can be explained that multiple networks of silane crosslink restrict the movement of molecules in the composite as the sample is heating. As a result of heat cycles at $140^{\circ}C$, the changes of volume resistivity and PTC intensity for radiation crosslinked sample were higher than those of silane crosslinked samples. Whereas, in the case of heat cycles at $85^{\circ}C$, which is limiting temperature for self-regulating heater, both silane and radiation crosslinked samples show stable results without pronounce changes of resistivity up to five cycles.

  • PDF