• Title/Summary/Keyword: Seasonal Energy Efficiency Ratio(SEER)

Search Result 6, Processing Time 0.025 seconds

Experimental Study on the Cooling seasonal Performance Factor of Room Air-conditioner (에어컨의 냉방기간 에너지 효율 산출을 위한 실험적 연구)

  • Lee, H.W.;Moon, J.H.;Bae, Y.D.;Park, J.C.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.4 no.3
    • /
    • pp.204-216
    • /
    • 1992
  • In most cases, EER(Energy Efficiency Ratio) is available to present energy efficiency of air-conditioners. But, EER is not adapt to measure energy efficiency at actual life environment because it is based on fixed temperature and humidity contditions. To overcome this disadvantage, there is need to introduce SEER(Seasonal Energy Efficiency Ratio) established at time varient temperature and humidity conditions. In this paper, SEER measurement method and conditions based on actual life environment of the country is introduced, and discussed SEER value about two air-conditioner type, that is, non inverter air-conditioner and inverter air-conditioner. As a result of, inverter air-conditioner was superior to non inverter air-conditioner at cooling seasonal energy efficiency.

  • PDF

An Experimental Study on the Performance Improvement of the Seasonal Energy Efficiency Ratio(SEER) of a Heat Pump by Optimizing Operating Parameters under Partial Load Conditions (부분부하 조건에서 히트펌프의 운전변수 최적화를 통한 냉방계절성능(SEER) 향상에 관한 실험적 연구)

  • Choi, Sungkyung;Lee, Sang Hun;Kim, Sunjae;Kim, Yongchan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.3
    • /
    • pp.111-118
    • /
    • 2017
  • Performance factors such as the EER(Energy Efficiency Ratio) and the COP (Coefficient of Performance) are being replaced by seasonal energy efficiency factors, like the SEER (Seasonal EER) and the SCOP (Seasonal COP) to evaluate the performance of a heat pump by the time of the year. Seasonal performance factors, such as the CSPF (Cooling Seasonal Performance Factor) and the HSPF (Heating Seasonal Performance Factor) are used to describe the heat pump's performance during the cool and hot seasons. In this study, the optimization of all heat pump's operating parameters was experimentally conducted to enhance the SEER based on the EU standard (EN 14825). Moreover, the SEER was improved by the compressor frequency, as well as indoor and outdoor fan speeds. In addition, the performance characteristics of the heat pump were studied under partial load conditions. As a result, the SEER was enhanced by 17% when the compressor frequency was optimized. An additional 2% improvement was achievable with the optimization of indoor and outdoor fan speeds.

The effect on the seasonal performance of an inverter compressor with higher and lower operating range (인버터 압축기의 저속과 고속운전범위가 계절성능에 미치는 영향)

  • 박윤철;하도용;민만기
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.2
    • /
    • pp.173-179
    • /
    • 1998
  • An experimental study was conducted on the effect of compressor capacity control range of heat pump on the seasonal energy efficiency ratio with variation of the maximum and minimum compressor input frequencies. To obtain seasonal energy efficiency ratio, steady state test at the maximum, minimum and intermediate compressor speed and cyclic test at the minimum compressor speed should be conducted. Maximum input frequency was varied to 95Hz, 105Hz, and 115Hz, and the minimum input frequency was varied to 35Hz, 45Hz, and 55Hz. The seasonal energy efficiency ratio increased as the input frequency of the compressor decreased. The maximum input frequency had only slight effects on the SEER.

  • PDF

A study on the Modulated Scroll Compressor by Bypass Method (바이패스방식을 이용한 용량가변 스크롤 압축기에 관한 연구)

  • Kim, Cheol-Hwan;Shin, Dong-Koo;Park, Hong-Hee
    • 유체기계공업학회:학술대회논문집
    • /
    • 2003.12a
    • /
    • pp.693-696
    • /
    • 2003
  • Hermetic Compressor circulates refrigerant with constant flow rate regardless of operation condition. so, at the operating condition requiring low cooling capacity, too much refrigerant flow deteriorates seasonal energy efficiency ratio(SEER). In this reason, modulated compressor is needed to improve SEER. Among many types of modulated compressor, non-inverter type modulated compressor is required for its low cost and easy to development. In the modulated scroll compressor by bypass method, EER steeply decreases for many loss like re-compression, changes of volume ratio, decrease of motor efficiency by torque variation. So. the range of modulation ratio for optimized SEER must be selected accompany with air conditioner set development.

  • PDF

An Overview on Standards for Seasonal Performance Evaluation of Multi-type Air Conditioners (멀티형 에어컨의 기간에너지소비효율 평가규격에 관한 연구)

  • 박윤철;문제명;홍주태
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.1
    • /
    • pp.91-100
    • /
    • 2004
  • Energy efficiency evaluation method for a multi-type air conditioning system still has not been developed. In this study, analysis on capacity range and evaluating method of standards for air conditioners was conducted with world-wide Standards. It is not a proper approach to use the standards for residential air conditioner to multi type air conditioners. Some difficulties and problems are commented in this study with overview of the standards. Through the analytic research, an evaluating method for multi type air conditioner was suggested with Integrated Part Load Value (IPLV). The suggested concept for evaluating energy efficiency during part load condition considers building load pattern and operating hours of the system at different locations. Load was weighted in IPLV to consider not only the concept of occurrence of outdoor temperature such as bin method but also operation hours of the system. An experiment about the IPLV was conducted with variable air volume ducted type air conditioning system and multi-type system through modified code tester to give a glance at quantitative value of the IPLV.

EFFECT OF DESIGN PARAMITERS ON SEASONAL PERFORMANCE OF AN A/C SYSTEM (공기조화기의 설계인자가 계절성능에 미치는 영향)

  • Park, Y.C.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2010.05a
    • /
    • pp.239-241
    • /
    • 2010
  • Performance evaluation for an air conditioning system is conducted at a specified test conditions. One is low temperature and the other is high temperature condition. Most of the manufactures tried to improve the performance at higher outdoor temperature. One of the reasons is that the customer wants to get ore capacity at high temperature climate. To cope with these kinds of demand, manufactures are tried to achieve higher capacity at high temperature with minimum power consumption even with same size of the system. Consequently, previous studies on performance of the air conditioning system are focused on capacity and performance improvement at high outdoor temperature.

  • PDF