• Title/Summary/Keyword: Saturation current

Search Result 656, Processing Time 0.025 seconds

An Algorithm for Detecting CT Saturation (변류기 2차전류의 포화 여부 판단 알고리즘)

  • Gang, Yong-Cheol;Ok, Seung-Hun;Gang, Sang-Hui
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.6
    • /
    • pp.275-278
    • /
    • 2001
  • This paper presents an algorithm for detecting current transformer (CT) saturation. At the instants of beginning (or end) of saturation, as a magnetizing inductance of the core is changed significantly, the shapes of the secondary current are also changed significantly though secondary currents are continuous the instants. At the instants, the second-order of third-order difference of the secondary current has big values. Thus, the third difference of the current is used to detect the beginning/end of CT saturation in this paper. If the magnitude of third-order difference of the secondary current is larger than a threshold value, the CT begins of ends saturation at the instants. The proposed detection method is unaffected by the amount of residual flux. The results of various tests with residual flux from -80% to +80% indicate satisfactory performance of the method.

  • PDF

Method for Detection of Saturation of a Current Transformer (전류변성기의 포화 검출을 위한 알고리즘 개발)

  • Nam, Soon-Ryul;Choi, Joon-Ho;Kang, Sang-Hee;Min, Sang-Won
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.5
    • /
    • pp.879-884
    • /
    • 2009
  • A Method for detection of saturation of a current transformer(CT) is proposed. The algorithm is initiated when the end point of a saturation period is detected. This detection is achieved by checking the time interval between the adjacent zero-crossing points of the second derivative of the secondary current. Once the end point of the saturation period is detected, the beginning point of the corresponding saturation period is determined by backward examination of the sum of the secondary current from the end point. The performance of the algorithm was evaluated for a-g faults on a 345 kV 100km overhead transmission line. The Electromagnetic Transient Program(EMTP) was used to generate fault current signals for different fault inception angles and different remanent fluxes. The performance evaluation shows that the proposed algorithm successfully detects the saturation period even in the presence of a remanent flux.

A Busbar Current Differential Relay with a Compensating Algorithm (보상 알고리즘을 적용한 모선보호용 전류차동 계전기)

  • 강용철;윤재성
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.4
    • /
    • pp.214-220
    • /
    • 2004
  • This paper describes a busbar current differential relay in conjunction with a current transformer(CT) compensating algorithm irrespective of the level of the remanent flux. The compensating algorithm detects the start of first saturation if the third-difference function of the current exceeds the threshold; it estimates the core flux at the first saturation start by inserting the negative value of the third-difference function of the current into the magnetization curve; thereafter, it calculates the core flux during the fault and compensates the distorted current using the magnetization curve. The algorithm estimates the correct secondary current irrespective of the level of the remanent flux and needs no saturation point of the magnetization curve. The proposed relay can improve not only security of the relay on an external fault with CT saturation but sensitivity of the relay on an internal fault; the relay can improve the operating speed on n internal fault with CT saturation. This paper concludes by implementing the relay into a digital signal processor based prototype relay.

The Effect of Surface Recombination Current on the Saturation Current in Si Solar Cell (Si 태양전지(太陽電池)의 표면재결합(表面再結合) 전류(電流)가 포화전류(飽和電流)에 미치는 영향(影響))

  • Shin, Kee-Shik;Lee, Ki-Seon;Choi, Byung-Ho
    • Solar Energy
    • /
    • v.8 no.2
    • /
    • pp.12-18
    • /
    • 1988
  • The effect of surface recombination current density on the saturation current density in Si solar cell has been studied. Theoretical model for surface recombination current was set up from emitter transparent model of M.A. Shibib, and saturation current of Si solar cell made by ion implantation method was also measured by digital electrometer. The theoretical surface recombination current density which is the same as saturation surface recombination current density in Shibib model was $10^{-11}[A/cm^2]$ and the measured value was ranged from $8{\times}10^{-10}$ to $2{\times}10^{-9}[A/cm^2]$. Comparing with the ideal p-n junction of Shockley, transparent emitter model shows improved result by $10^2$ order of saturation current density. But there still exists $10^2$ order of difference of saturation current density between theoretical and actual values, which are assumed to be caused by 1) leakage current through solar cell edge, 2) recombination of carriers in the depletion layer, 3) the series resistance effect and 4) the tunneling of carriers between states in the band gap.

  • PDF

A Busbar Current Differential Relay with a Compensating Algorithm (보상 알고리즘을 적용한 모선보호용 전류차동 계전기)

  • 강용철;윤재성
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.4
    • /
    • pp.214-214
    • /
    • 2004
  • This paper describes a busbar current differential relay in conjunction with a current transformer(CT) compensating algorithm irrespective of the level of the remanent flux. The compensating algorithm detects the start of first saturation if the third-difference function of the current exceeds the threshold; it estimates the core flux at the first saturation start by inserting the negative value of the third-difference function of the current into the magnetization curve; thereafter, it calculates the core flux during the fault and compensates the distorted current using the magnetization curve. The algorithm estimates the correct secondary current irrespective of the level of the remanent flux and needs no saturation point of the magnetization curve. The proposed relay can improve not only security of the relay on an external fault with CT saturation but sensitivity of the relay on an internal fault; the relay can improve the operating speed on n internal fault with CT saturation. This paper concludes by implementing the relay into a digital signal processor based prototype relay.

Analysis for Electrical Fire Possibility Using Fuzzy Logic with Input Variables of Overcurrent and Saturation Time in the Indoor Wiring (전기배선에서 과전류와 포화시간을 입력변수로 갖는 퍼지기반 전기화재가능성 분석)

  • Kim, Eun-Jin;Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.6
    • /
    • pp.34-39
    • /
    • 2015
  • The study is aimed to develop fuzzy logic system that has overcurrent and saturation time as input variable and possibility of electrical fire as output variable by making bad conductor area with physical damage to indoor wiring. Most previous studies focused on thermal characteristics depending on the current size and no study considered the current size and saturation time at the same time. Therefore, the paper made into account current value and saturation time together. To this end, it created bad conductor area half the size of IV conductor (1.6 mm) on purpose and transmit electrical current from 10A to 60A by unit of 2A to find out the thermal characteristics and saturation time for current. Based on the data that came out, the study applied fuzzy logic and established the current and saturation time as input variable and chance of fire as output variable. As a result, the center of area of the system that depended only on the existing current value was 75 while the system that applied both current and saturation time presented the chance of fire at 92. It is found that the chance of bad conductor area and deteriorated insulation of electrical wire had current and saturation time as important variables. The data can be used as basic data like deteriorated wire insulation or operation features of circuit breaker in investigating the cause of electrical fire.

A Percentage Differential Current Relaying Algorithm for Bus Protection Using Current Transformer Saturation Detecting Algorithm (변류기 포화검출 알고리즘을 적용한 모선보호용 비율전류차동 계전방식)

  • Kang, Yong-Cheol;Yun, Jae-Sung;Ok, Seung-Hun
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.115-117
    • /
    • 2001
  • A percentage current differential relaying algorithm is widely used for bus protection. However, it may maloperate external faults with CT saturation. This paper proposes a percentage current differential relaying algorithm for bus protection using CT saturation detecting algorithm. The CT saturation detecting algorithm uses difference of secondary current of CT and detects CT saturation. The proposed method distinguishes percentage differential relay operation caused by faults from percentage differential relay operation caused by CT saturations.

  • PDF

A Percentage Current Differential Relaying Algorithm for Bus Protection Blocked by a CT Saturation Detection Algorithm (변류기 포화 곤단 알고리즘으로 억제된 모선보호용 비율 전류차동 계전방식)

  • 강용철;윤재성
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.1
    • /
    • pp.44-49
    • /
    • 2003
  • This paper describes a percentage current differential relaying algorithm for bus protection blocked by a CT saturation detection algorithm. The detection algorithm blocks the output of a current differential relay only if a differential current is caused by CT saturation in the case of an external fault. Moreover, if a current differential relay operates faster than the detection algorithm, the blocking signal is not ignited. On the other hand. if the detection algorithm operates faster than a current differential relay, the output of the relay is blocked. The results of the simulation show that the proposed algorithm can discriminate internal faults from external faults ever when a CT is saturated in both cases. This paper concludes by implementing the algorithm into the TMS320C6701 digital signal processor. The results of hardware implementation are also satisfactory The algorithm can not only increase the sensitivity of the current differential relay but Improve the stability of the relay for an external faults.

Observation of saturation transfer characteristics in solution processed vertical organic field-effect transistors (VOFETs) with high leakage current

  • Sarjidan, M.A. Mohd;Shuhaimi, Ahmad;Majid, W.H. Abd.
    • Current Applied Physics
    • /
    • v.18 no.11
    • /
    • pp.1415-1421
    • /
    • 2018
  • Unlike ordinary organic field-effect transistors (OFETs), saturation current is hardly to be found in vertical OFETs (VOFETs). Moreover, the fabrication process of patterned sourced for VOFETs is quite complex. In this current work, a simple solution processed VOFET with directly deposited intermediate silver source electrode has been demonstrated. The VOFET exhibits a high leakage current that induces an inversion polarity of its transistor behavior. Interestingly, a well-defined saturation current was observed in the linear scale of transfer characteristic. The VOFET operated with high-current density > $280mA/cm^2$ at $V_d=5V$. Overview potential of the fabricated device in display application is also presented. This preliminary work does open-up a new direction in VOFET fabrication and their application.

Discrimination Method of Internal and External Fault of Current Differential Relay using Instantaneous Value of Current in Case of Fault with One end CT Saturation (편단 CT 포화 고장 발생시 양단 전류 순시치를 이용한 전류차동계전기의 내·외부 고장위치 판별방안)

  • Lee, Myoung-Hee;Choi, Hae-Sul;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.12
    • /
    • pp.1801-1806
    • /
    • 2012
  • This paper presents a simple and practical method which enables to prevent malfunction of protection relay due to differential current caused by one end CT saturation in case of external fault. This method uses difference of magnitude(instantaneous value) between the both end current just before the occurrence of differential current without a separate method to CT staturation detection. One end CT saturation is simulated by current transformer model using type-96 component and the presented method is verified by using EMTP MODELS with respect to internal and external fault with one end CT staturation. The presented method distinguished rightly bewteen external and internal fault with one end CT saturation. This information can be used to prevent malfunction of current differential protection relay in case of external fault. And this method is not affected by sampling rate and has no calculation burden, so it will be applicable to differential current protection relay with ease.