• 제목/요약/키워드: SFCL, Protection

검색결과 32건 처리시간 0.024초

고온 초전도 한류기가 설치된 전력 시스템의 안정도 해석 (The Stability Analysis of Power System Installed Superconducting Fault Current Limiter)

  • 이승제;이찬주;고태국
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제48권5호
    • /
    • pp.227-232
    • /
    • 1999
  • The stability of Power system installed Hi-Tc Superconducting Fault Current Limiter(SFCL) is analyzed as a process of developing SFCL. For investigation, a simple mimic system(only one generator) is assumed and then the circuit with SFCL in that system is solved for transient performance. In case the SFCL is installed in the power system, it protected synchronization more effectively both in symmetrical 3-phase fault and single phase line to ground fault in that the machine remains in synchronism for the more time than of without superconducting fault current limiter. It shows that the superconducting fault current limiter not only limits fault current but also protest synchronism. So for design of this SFCL, its synchronism protection property must be considered.

  • PDF

MTR 중성점 접지에 초전도 전류제한기 적용시 지락과전류계전기 동작 분석 (Analysis on the Protective Coordination on Neutral Line of Main Transformer in Power Distribution Substation with Superconducting Fault Current Limiter)

  • 김진석;임성훈;문종필;김재철;현옥배
    • 전기학회논문지
    • /
    • 제58권11호
    • /
    • pp.2089-2094
    • /
    • 2009
  • The fault current has increased due to growth of distributed generations for the large power demand in power distribution system. To solve some problem such as excess of the circuit breaker's cut-off ratings, the superconducting fault current limiter(SFCL) has been progressed. However, the operational characteristics of the relay is changed by SFCL. Therefore, the proper impedance for the SFCL should be selected to keep protective coordination with the SFCL when SFCL is introduced on the neutral line of main transformer in distribution system. In this paper, the proper normal conducting resistance was suggested to solve the problem in case of the protection coordination with SFCL.

배전계통에 초전도한류기 적용시 OCR 및 Recloser 동작특성 분석 (Analysis of Operation Characteristics of OCR and Recloser in Power Distribution System with SFCL)

  • 문종필
    • 전기학회논문지P
    • /
    • 제61권4호
    • /
    • pp.214-219
    • /
    • 2012
  • In this paper, the method of protective coordination is studied to install Superconducting Fault Current Limiter (SFCL) to power distribution system. If SFCL is installed, the protective coordination is not operated well because of the decreased fault current. Thus, the resetting method of protective devices is presented to coordinate protection system in power distribution system with resistor-type SFCL. The presented methods are divided into three parts; OCR, OCR-Recloser, OCR-Recloser-Recloser. The presented methods are proved through case studies using PSCAD/EMTDC simulation.

배전계통에 대용량변압기 교체 적용시 초전도 한류기의 임피던스에 따른 순간전압 분석 (Analysis on Voltage Sag in Power Distribution System according to SFCL's Impedance for Protective Coordination with Large Transformer)

  • 김진석;문종필
    • 전기학회논문지P
    • /
    • 제63권4호
    • /
    • pp.312-316
    • /
    • 2014
  • In this paper, a voltage sag is analyzed in case of superconducting fault current limiter (SFCL) installed in power distribution system where replaces the main power transformer to large one to meet the power demand. First, the power system is configurated to analyze the operation characteristics of the protective relay with replacement of the main transformer and application of the SFCL. Next, the method to meet the protection coordination is analyzed with large transformer using PSCAD/EMTDC. Finally, the bus voltage is investigated according to the impedance of both main transformer and SFCL in case that the SFCL is applied into feeder.

계통보호릴레이와의 협조를 고려한 SFCL의 동작파라메타 설정방법에 대한고찰 (On Setting Method of the operating Parameters of SFCL in Transmission Systems Considering Power Protection Relay)

  • 홍원표
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 C
    • /
    • pp.1231-1234
    • /
    • 1998
  • Design & Operation of power system for meeting increase of electric power demand is becoming more difficult and complex. One of reasons is increase of fault current. As one of the most effective methods for suppressing the fault current, installation of SFCL is expected. This paper describes a method of fault analyses of power system with SFCLs, and also discusses determination of specification of SFCLs, effects of limiting the fault current due to SFCLs by use of the model system of two - bus electric power system with parallel circuit model transmission line. Also, describes the definition of six specific parameters of SFCL for power system application & a proposal of design method of specific parameter of a resistance type SFCL in overhead transmission lines considering operation of protective relays.

  • PDF

국내 실계통에서의 22.9 kV 초전도케이블/한류기 시범적용을 위한 보호시스템 설계 (Protection system for the application of 22.9 kV HTS cable and FCL to real power grid in Korea)

  • 이승렬;윤재영;양병모
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제12권3호
    • /
    • pp.25-28
    • /
    • 2010
  • 22.9 kV HTS cable and FCL will be installed in 154 kV Icheon substation. It is necessary to design a protection system of the substation for a successful application of the HTS devices. This paper proposes a new power protection system for the application of 22.9 kV HTS cable and SFCL to 154 kV Icheon substation in Korea.

배전계통에 초전도 전류 제한기 적용시 보호협조 분석 (Analysis on the Protective Coordination in Power Distribution System with Superconducting Fault Current Limiter)

  • 안재민;김진석;문종필;임성훈;김재철;김철환;현옥배
    • 전기학회논문지
    • /
    • 제57권5호
    • /
    • pp.755-760
    • /
    • 2008
  • The increase of fault current due to larger power demand has caused the capacity of power machines in grid to increase. To protect the power system effectively from the larger fault current, several countermeasures have been proposed. Among them, the superconducting fault current limiter (SFCL) has been expected as one of the most effective solutions. Therefore, to introduce SFCL into power distribution system, the analysis on protection in power distribution system with SFCL is essential. In this paper, the problems of the protective coordination in power distribution system with SFCL were described.

22.9kV 초전도 한류기 실계통 적용을 위한 절연협조 검토 (The Study on Insulation Coordination on 22.9kV SFCL for Applying to Real Grid)

  • 김태훈;강지원;강연욱;박진우;이한상;양병모
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제14권1호
    • /
    • pp.20-24
    • /
    • 2012
  • This paper proposes an insulation coordination and surge arrester design for superconducting power system with SFCL(Superconducting Fault Current Limiter) in Icheon substation. In the aspect of the economic analysis, since the superconducting devices are very expensive, the insulation coordination to prevent the dielectric breakdown caused by the lightning surge should be considered carefully. In this paper, the insulation coordination for real grid including SFCL and the design of the protection devices against lightning surge is verified using PSCAD/EM TDC.

국내 실계통 적용을 위한 22.9kV 복합형 초전도한류기 동작전류 검토 (Operating Current for the application of 22.9kV hybrid SFCL to real power grid in Korea)

  • 이승렬;윤재영;양병모
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제12권3호
    • /
    • pp.39-43
    • /
    • 2010
  • In Korea, 22.9kV hybrid SFCL (Superconducting Fault Current Limiter) has been developed and carried out long-term field tests in Gochagn power test center of KEPCO through DAPAS program. The SFCL will be installed at a distribution line of Icheon substation in Korea. For the successful application, we have to design the specifications considering real power system operation. This paper proposes a concept of the operating current based rms value for the protection coordination with protective delays and studies a proper range of the current in Korean distribution power system.