• 제목/요약/키워드: SCW GHX

검색결과 3건 처리시간 0.019초

SCW형 지중 열교환기의 지중 열전도도 해석에서 초기제외시간 결정에 관한 연구 (A Study on the Determining Initial Ignoring Time for the Analysis of Ground Thermal Conductivity of SCW Type Ground Heat Exchanger)

  • 장근선;김민준;김영재
    • 설비공학논문집
    • /
    • 제26권10호
    • /
    • pp.453-459
    • /
    • 2014
  • This paper presents an analysis on the initial ignoring time of SCW type GHX using Mean Square Error method. Line source method is a useful method for estimating the ground thermal conductivity for the vertical type and SCW type GHX in Korea. The line source method for ground thermal conductivity of geothermal in-site test is the basis of linear approximation between the temperature of a borehole and logarithmic time in a GHX. To apply the line source method to the estimation of SCW type GHX, it is necessary to ignore the initial time of data at the stage of a linear approximation. This paper proposed a new initial ignoring time of SCW type GHX among various initial ignoring time at the time for reaching MSE of $0.02^{\circ}C^2$.

다양한 형상의 SCW형 지중 열교환기 열전달 특성에 관한 연구 (A Study on the Heat Transfer Characteristics of Various Construction of SCW Type Ground Heat Exchanger)

  • 장근선;김민준
    • 설비공학논문집
    • /
    • 제26권10호
    • /
    • pp.460-466
    • /
    • 2014
  • This paper uses in-situ thermal response tests to present the characteristics of the ground thermal conductivities of three different SCW GHX. These SCW GHXs were installed in the same site in Seojong City. The three different cases are distinguished by the flow direction and the presence of a filler. The first type (A) is constructed for water to flow downstream. The second (B) and third (C) types are designed for water to flow upstream, and a filler is additionally inserted into the third type. The results of the in-situ thermal response tests, indicate that the ground thermal conductivity for types (A), (B) and (C) are of $4.84W/m{\cdot}K$, $3.40W/m{\cdot}K$, and $11.62W/m{\cdot}K$, respectively.

열응답시험 데이터를 이용한 SCW형 지중열교환기 블리딩 효과 분석 (An Analysis on the Bleeding Effect of SCW Ground Heat Exchanger using Thermal Response Test Data)

  • 장근선;김민준
    • 한국산학기술학회논문지
    • /
    • 제21권1호
    • /
    • pp.512-520
    • /
    • 2020
  • 개방형 지중열교환기(SCW)는 수직 밀페형 지중열교환기에 비해 높은 용량과 효율을 갖고 있어 최근에 우리나라에서 많이 보급되고 있는 추세이다. SCW형 지중열교환기의 여러 설계 및 운전변수 중 블리딩 운전이 지중 열전도율, 보어홀 열저항 등 열성능 개선에 가장 효과가 큰 것으로 보고되고 있다. 본 연구에서는 SCW형 지중열교환기가 설치된 현장의 열응답시험 결과를 기반으로 블리딩해석 모델을 정립하고 블리딩율 및 지하수 유입수의 위치변화가 SCW형 지중열교환기 열성능에 미치는 영향을 수치해석을 통하여 고찰하였다. 해석결과 지하수가 지중열교환기 상부에서 유입될 경우 지중열교환기 순환수의 시간에 따른 온도증가는 블리딩율이 증가함에 따라 낮아지는 경향을 보였으며, 지중 열전도율은 30% 블리딩율에서 179% 증가하는 결과를 보였다. 반면에 지하수가 지중열교환기 하부에서 유입될 경우 지중열교환기 순환수는 지중과 먼저 열교환을 한 후 유입수와 하단에서 혼합되기 때문에 지중열교환기 순환수의 온도증가는 상부 유입의 경우보다 적으며 블리딩율이 약 10%를 초과하면 일정하게 유지되는 경향을 보였다.