• 제목/요약/키워드: Repulsion Force

검색결과 40건 처리시간 0.028초

3차원 유한요소 해석을 이용한 배선용 차단기의 전자반발력 계산 (Calculation of Electrodynamic Repulsion Force in Molded Case Circuit Breakers Using the 3-D Finite Element Analysis)

  • 김용기;박홍태;송중천;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.137-140
    • /
    • 2003
  • To the optimization design of molded case circuit breakers(MCCBs), it is necessary and important to calculate the electro-dynamic repulsion force acting on the movable conductor. With 3-D finite element nonlinear analysis, according to the equations among current-magnetic field-repulsion force and taking into account the ferromagnet, contact bridge model is introduced to simulate the current constriction between contacts, so Lorentz and Holm force acting on the movable conductor and contact, respectively, can be integrated to calculate. Coupled with circuit equations, the opening time of movable contact also can be obtained using iteration with the restriction of contact force. Simulation and experiment for repulsion forte and opening time of five different configuration models have been investigated. The results indicate that the proposed method is effective and capable of evaluating new design of contact systems in MCCBs.

  • PDF

Contact Parameter Computation and Analysis of Air Circuit Breaker with Permanent Magnet Actuator

  • Fang, Shuhua;Lin, Heyun;Ho, S.L.;Wang, Xianbing;Jin, Ping;Huang, Yunkai;Yang, Shiyou
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권3호
    • /
    • pp.595-602
    • /
    • 2013
  • An air circuit breaker (ACB) with novel double-breaker contact and permanent magnet actuator (PMA) is presented. Three-dimensional (3-D) finite element method (FEM) is employed to compute the electro-dynamic repulsion forces, including the Holm force and Lorentz force, which are acting on the static and movable contacts. The electro-dynamic repulsion forces of different contact pieces are computed, illustrating there is an optimal number of contact pieces for the ACB being studied. The electro-dynamic repulsion force of each contact, which varies from the outer position to the inner position, is also computed. Finally, the contacts of the double-breaker are manufactured according to the analyzed results to validate the simulations.

진공인터럽터용 다극 종자계전극의 전자반발력 해석 (The Electromagnetic Repulsion Force Analysis of Multipolar Axial Magnetic Field type Electrodes for Vacuum Interrupter)

  • 김성일;박홍태;안희일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.95-97
    • /
    • 1999
  • This paper describes electromagnetic repulsion force of multipolar axial magnetic field type electrodes for vacuum interrupter used in vacuum circuit breaker. It was distinguished that repulsion force of multipolar axial magnetic field type electrode in consideration of eddy current effect between upper electrode and lower electrode by finite element method. And it was found out that suitable contact weight of multipolar axial magnetic field type electrode for vacuum circuit breaker from repulsion force analysis results by finite element method.

  • PDF

ANSYS를 이용한 전기 접촉 기구의 전자 반발력 분석 및 온도 상승 예측 (Prediction of Electromagnetic Repulsion Force and Temperature Rise in Electric Contact Mechanism Using ANSYS)

  • 박우진;김기환;안길영;오일성
    • 한국정밀공학회:학술대회논문집
    • /
    • 한국정밀공학회 2005년도 추계학술대회 논문집
    • /
    • pp.666-669
    • /
    • 2005
  • As computer power increased, the system with complex phenomenon has been analyzed with the help of CAE software which can handle the coupled physics, such as electromagnetic, structure, thermal and fluid physics. To predict the electromagnetic repulsion force and the temperature distribution of an air circuit breaker with electric contact mechanism, ANSYS/EMAG, FLOTRAN can be used. Although some assumptions and simplifications were introduced to simulate the model, results from the computational model were in good agreement with actual measurements obtained from experiments.

  • PDF

교류 전자 접촉기의 접점 전자반발력에 관한 연구 (A Study on Magnetic Repulsion Force in Electromagnetic Contactors)

  • 류종상;김견묵;이경구;조현길;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.364-367
    • /
    • 2001
  • In this paper, an analysis of electromagnetic repulsion force is presented using 3D FEM considering eddy current. It is important for the optimum design of switching device to analysis electromagnetic repulsion forces generated by the interaction of the electric current and its own magnetic field on the closed electric contacts flowing over current. The validity of our analysis is confirmed by comparing analytic and experimental results.

  • PDF

영구자석을 이용한 와전류 자기반발식 부상장치의 성능 향상 설계 (Improved Efficiency Design of Eddy-current Magnetic Repulsion System Using Permanent Magnets)

  • 장석명;권정기;성호경;김봉섭;이성호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 B
    • /
    • pp.1076-1078
    • /
    • 2004
  • This paper deals with eddy-current magnetic repulsion system. The passive system employing permanent magnets on the moving part maximizes levitation forces by using Halbach array and conducting plate. We predict force characteristics according to permanent magnet array and conducting bar

  • PDF

영구자석을 이용한 와전류 자기반발식 부상장치에 관한 연구 (A study on Eddy current Magnetic Repulsion System Using Permanent Magnets)

  • 성호경;조정민;김봉섭;조흥제;김동성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 B
    • /
    • pp.1613-1615
    • /
    • 2005
  • Maglev equipped with permanent magnets on the moving part can be levitated by the magnetic repulsion between Halbach array and conducting plate when this vehicle is running. This paper deals with the fundamental principles of the eddy-current magnetic repulsion system and the force characteristics to the change of the permanent magnet array and conduction bar.

  • PDF

3D FEM해석을 통한 배선용 차단기의 가동자 거동해석 (Dynamic Motion Analysis of a Moving Contact by Electromagnetic Repulsion Force in MCCB)

  • 송중천;김용기;유만종;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 B
    • /
    • pp.786-789
    • /
    • 2002
  • The behaviour of contactors protected by arcs under short-circuit currents is analysed using a simple model to represent the electric circuit and the contactor. In most cases, the protection of contactors against short-circuit currents is entrusted to fuses. Fuses are suitable for preventing excessive damage to the contactor, or parts of the contactor, under short-circuit conditions. In particular, they are capable of limiting the thermal and electrodynamic stresses which can lead to arcing or welding together of the contacts of a contactor. This paper is the Dynamic Motion Analysis of a Moving Contact by Electromagnetic Repulsion Force in Molded Case Circuit Breaker(MCCB)

  • PDF