• Title/Summary/Keyword: Reactive Method

Search Result 1,512, Processing Time 0.026 seconds

Active Frequency Drift Method for Islanding Detection Applied to Micro-inverter with Uncontrollable Reactive Power

  • Kwak, Raeho;Lee, June-Hee;Lee, Kyo-Beum
    • Journal of Power Electronics
    • /
    • v.16 no.5
    • /
    • pp.1918-1927
    • /
    • 2016
  • This paper proposes active frequency drift (AFD) as an anti-islanding method applied to micro-inverters with uncontrollable reactive power. When using ordinary inverter topologies, such as full bridge inverters in photovoltaic systems, the islanding phenomenon can be detected with reactive power-based methods, such as reactive power variation. However, when the inverter topology cannot control the reactive power, conventional anti-islanding methods with reactive power cannot be utilized. In this work, the topology used in this paper cannot control the reactive power. Thus, an anti-islanding method that can be used in topologies that cannot control the reactive power is proposed. The conventional anti-islanding method of the topology that cannot control reactive power is introduced and analyzed. Unlike the conventional AFD method, the proposed method extends a zero current interval every predetermined cycle. The proposed method offers certain advantages over conventional AFD methods, such as total harmonic distortion. The proposed method is validated through simulation and experiment.

Proposing a New Method for Calculating Reactive Power Service Charges using the Reactive Power Market

  • Ro, Kyoung-Soo;Park, Sung-Jin
    • KIEE International Transactions on Power Engineering
    • /
    • v.4A no.4
    • /
    • pp.262-267
    • /
    • 2004
  • With the advent of electric power systems moving from a vertically integrated structure to a deregulated environment, calculating reactive power service charges has become a new and challenging theme for market operators. This paper examines various methods for reactive power management adopted throughout various deregulated foreign and domestic markets and then proposes an innovative method to calculate reactive power service charges using a reactive power market in a wholesale electricity market. The reactive power market is operated based on bids from the generating sources and it settles on uniform prices by running the reactive OPF programs of the day-ahead electricity market. The proposed method takes into account recovering not only the costs of installed capacity but also the lost opportunity costs incurred by reducing active power output to increase reactive power production. Based on the result of the reactive OPF program, the generators that produce reactive power within the obligatory range do not make payments whereas the generators producing reactive power beyond the obligatory range receive compensation by the price determined in the market. A numerical sample study is carried out to illustrate the processes and appropriateness of the proposed method.

Development of Optimal Power Flow for the Ancillary Service of Reactive Power Generation under Restructuring Environment (전력산업 구조개편 환경 하에서 무효전력 보조서비스 운용을 위한 최적조류계산법 개발)

  • Lee, Seung-Ryeol;Lee, Byeong-Jun;Song, Tae-Yong;Jeong, Min-Hwa;Mun, Yeong-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.1
    • /
    • pp.37-44
    • /
    • 2002
  • This Paper suggests reasonable pricing mathod fur Reactive Power in Optimal Power Flow for the system analysis. Under restructuring, not only real power pricing but also reactive power pricing is important for the system analysis and operation. If people just focus on real power pricing, the Generators may no generate reactive power voluntarily, because the Generators may not recover the cost of the reactive power generation. So making a reasonable reactive power pricing is becoming more important than any other time. In this paper, the authors set a Proper Power factor and price the portion of the reactive power that exceeds the power factor using Interior Point Method. By applying this method, the System operator can use this strategy for the analysis of reactive power generation pricing and the Generator can get the motivation to generate reactive power. The author develops fully optimized fast Primal Dual Interior Point Method with sparsity technique and applies this method to Reliability Test System (RTS24) and KEPCO 674 bus system (684 buses. 1279 lines). It shows adaptability and usefulness.

Reactive Power P&O Islanding Detection Method using Positive Feedback (Positive Feedback을 이용한 무효전력 P&O 단독운전 검출기법)

  • Lee, Jong-Won;Park, Sung-Youl;Lee, Jae-Yeon;Choi, Se-Wan
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.27 no.5
    • /
    • pp.410-416
    • /
    • 2022
  • A grid-connected inverter with critical loads uses mode transfer control to supply stable voltage to the load. An islanding detection method should also be used to quickly detect the grid fault and disconnect the inverter from the grid. However using the existing islanding detection method to detect islanding is difficult due to the small fluctuation of the voltage and frequency of the point of common coupling. This study proposes a reactive power P&O islanding detection method by using the positive feedback technique. The proposed method always injects a small variation of reactive power. When a grid fault occurs, the injected reactive power accelerates the reactive power injection reference. As a result, the reactive power reference value and the sensed reactive power become mismatched, and islanding is detected. Reducing the amount of real-time injected reactive power results in high efficiency and power factor. The simulation and experimental results of a 3 kW single-phase inverter are provided to verify the proposed islanding detection method.

Film Properties of TiO2 Made by Activated Reactive Evaporation (활성화 반응으로 제작된 TiO2의 박막특성)

  • Park, Yong-Gwon;Choi, Jae-Ha
    • Journal of the Korean Society for Heat Treatment
    • /
    • v.14 no.3
    • /
    • pp.151-154
    • /
    • 2001
  • $TiO_2$ thin film has wide application because of its high capacitanca, reflection, and good transmissivity in visible range. $TiO_2$ thin film can be made by thermal deposition method, reactive evaporation method, activated reactive evaporation(ARE) method. In the case of thermal deposition, the oxygen deficiency can occur because the melting point of Ti is very high. While in the case of reactive evaporation, high density $TiO_2$ can not be made, because reactive gas($O_2$) and evaporated material(Ti) are not fully combined, activated reactive evaporation, $TiO_2$ is easily deposited at lower gas pressure compared with reactive evaporation because the ionized reactive gas is made by plasma. Therefore, activated reactive evaporation is very useful to deposit the material having the high melting point. In this work, we formed $TiO_2$ thin film by activated reactive evaporation method. The surface of $TiO_2$ thin film was analyzed by X-ray photoelectron spectroscopy. The surface morphology which was analyzed by atomic force microscopy(AFM) shows that feature of the film surface is uniform. The dielectric capacitance, withstanding voltage were $600{\mu}F/cm^2$, 0.4V respectively. In further work, we can increase the withstanding voltage by improving the deposition parameter of substrates.

  • PDF

Local Coordinative Reactive Power Control Method to Manage Voltage/Momentary Reactive Reserve (전압 및 순동무효예비력 확보를 위한 지역 변전소에서의 무효전력제어장치 협조방식 연구)

  • Lee, Geun-Joon;Yoon, Jong-Soo;Jang, Byung-Hoon;Jung, Sung-Won;Yoon, Sun-Ho;Lee, Hyun-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.115-116
    • /
    • 2008
  • This paper discusses local reactive power control method of substation which has FACTS controller(STATCOM) and other reactive power controllers. Not only The relation between entral control and local control method was discussed, but also local STATCOM control methd was done. With this results, revised coordinative control method which can implement system voltage sensitivity characteristics of each control devices. Also, this method can give proper solution for system status which requires momentary reactive reserve. This method is expected to be applied to control multiple substation reactive power devices which is combined with SCADA system.

  • PDF

The Anti-Islanding Method with Compensation of Load Reactive Power for Grid-connected Photovoltaic Generation System (계통 연계형 태양광 발전 시스템의 부하 무효전력 보상이 적용된 단독운전 인지법)

  • Jeong, Jin-Beom;Shin, Dong-Hyun;Kim, Hee-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.1
    • /
    • pp.58-64
    • /
    • 2008
  • In this paper, we present an active anti-islanding method with a load monitoring system using reactive power control. The proposed method, which is based on reactive power control, has fewer harmonics components than those in conventional methods, and it can minimize the reactive power component of the grid because it compensates the reactive power component with the load monitoring. The proposed quick islanding detection method was confirmed from the experimental results with an inverter for a 3kW photovoltaic system.

The Development of the Transmission Marginal Loss Factors with Consideration of the Reactive Power and its Application to Energy Spot Market (무효전력을 고려한 한계송전손실계수 산정 방법론 개발 및 현물시장에의 적용)

  • 박종배;이기송;신중린;김성수
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.7
    • /
    • pp.429-436
    • /
    • 2003
  • This paper presents a new approach for evaluating the transmission marginal loss factors (MLFs) considering the reactive power. Generally, MLFs are represented as the sensitivity of transmission losses, which is computed from the change of the generation at reference bus by the change of the load at the arbitrary bus-i. The conventional evaluation method for MLFs uses the only H matrix, which is a part of jacobian matrix. Therefore, the MLFs computed by the existing method, don't consider the effect of the reactive power, although the transmission losses are a function of the reactive power as well as the active power. To compensate the limits of the existing method for evaluating MLFs, the power factor at the bus-i is introduced for reflecting the effect of the reactive power in the evaluation method of the MLFs. Also, MLFs calculated by the developed method are applied to energy spot markets to reflect the impacts of reactive power. This method is tested with the sample system with 5-bus, and analyzed how much MLFs have an effect on the bidding/offer price, market clearing price(MCP), and settlement in the competitive energy spot market. This paper compared the results of MLFs calculated by the existing and proposed method for the IEEE 14-bus system, and the KEPCO system.

A Study on Efficient Calculation of Effective Reactive Power Reserves Using Sensitivity Analysis

  • Bae, Moonsung;Lee, Byongjun
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.5
    • /
    • pp.1689-1696
    • /
    • 2017
  • In recent academic and industrial circles of the Republic of Korea, the securement of available reactive power reserve against the line faults is at issue. Thus, simulations have been performed for the securing of effective reactive power reserve (effective Q) to prepare for the line faults and improve reactive power monitoring and control methods. That is, a research has been conducted for the fast-decoupled Newton-Raphson method. In this study, a method that distinguishes source and sink regions to carry out faster provision of information in the event of line fault has been proposed. This method can perform quantification with the formula that calculates voltage variations in the line flow. The line flow and voltage changes can be easily induced by the power flow calculation performed every second in the operation system. It is expected that the proposed method will be able to contribute to securement of power system stability by securing efficient reactive power. Also, the proposed method will be able to contribute to prepare against contingencies effectively. It is not easy to prepare quickly for the situation where voltage drops rapidly due to the exhaustion of reactive power source by observing voltage information only. This paper's simulation was performed on the large scale Korean power system in steady state.

Coordination of UPFC and Reactive Power Sources for Steady-state Voltage Control (정상상태 전압제어를 위한 UPFC와 조상설비의 협조)

  • Park, Ji-Ho;Lee, Sang-Duk;Jyung, Tae-Young;Jeong, Ki-Seok;Baek, Young-Sik;Seo, Gyu-Seok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.5
    • /
    • pp.921-928
    • /
    • 2011
  • This paper presents a new method of local voltage control to achieve coordinative control among UPFC(Unified Power Flow Controller) and conventional reactive compensation equipments, such as switched-shunt and ULTC(Under-Load Tap Changing) transformer. Reactive power control has various difficult aspects to control because of difficulty of system analysis. Recently, the progress of power electronics technologies has lead to commercial availability of several FACTS(Flexible AC Transmission System) devices. The UPFC(Unified Power Flow Controller) simultaneously allows the independent control of active and reactive power flows as well as control of the voltage profile. When conventional reactive power sources and UPFC are used to control system voltage, the UPFC reacts to the voltage deviation faster than the conventional reactive power sources. Keeping reactive power reserve in an UPFC during steady-state operation is always needed to provide reactive power requirements during emergencies. Therefore, coordination control among UPFC and conventional reactive power sources is needed. This paper describe the method to keep or control the voltage of power system of local area and to manege reactive power reserve using PSS/E with Python. The result of simulation shows that the proposed method can control the local bus voltage within the given voltage limit and manege reactive power reserve.