• Title/Summary/Keyword: Rated Sensitivity Current

Search Result 14, Processing Time 0.022 seconds

Improvement of Circuit-Time Product through Analysis of Operating Time of Earth Leakage Circuit-Breakers (누전차단기의 트립 동작시간 분석을 통한 전류·시간적(積) 개선)

  • Kim, Ju-Chul;Lee, Sang-Joong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.12
    • /
    • pp.44-49
    • /
    • 2012
  • The earth leakage circuit-breakers installed to protect the human body against electrical shock have conventionally had a sensitivity current of 30 mA and an operating time of 30 ms or less. No reviews are found, however, on the operating time of the current conducting through the human body due to the electrical shock or ground fault. This paper measures the trip-operating time against the earth leakage under the condition of increased current as well as under the condition of rated sensitivity current of the earth leakage circuit-breakers. Further measurement with a prototype model showed an improved operating time of 16 ms or less under the condition of rated sensitivity current. It is expected that development of circuit-breakers with higher safety is possible if the performance of the electronic circuit can be improved.

A Compensating Algorithm for the Secondary Current of Iron-cored Current Transformers (철심 변류기 2차 전류 보상 알고리즘)

  • Kang, Yong-Cheol;Park, Jong-Keun;Kang, Sang-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1995.07b
    • /
    • pp.628-630
    • /
    • 1995
  • CT saturation may cause protective relays to malfunction. The conventional method to deal with the problem is overdimensioning of the core so that CTs can carry up to 20 times the rated current without exceeding 10 % ratio correction. However, this not only reduces the sensitivity of relays, but also increases the CT core size. This paper presents a technique of estimating the secondary current corresponding to the CT ratio under CT saturation using the magnetization curve. The proposed algorithm can improve the sensitivity of relays to low level faults and minimize the instability of relays for external faults.

  • PDF

Hardware implementation and error analysis of an algorithm for compensating the secondary current of iron-cored current transformers (철심 변류기의 2차 전류 보상 알고리즘의 실시간 구현 및 오차 분석)

  • 강용철;김성수;박종근;강상희;김광호
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.45 no.4
    • /
    • pp.490-500
    • /
    • 1996
  • The conventional method to deal with current transformer (CT) Saturation is over dimensioning of the core so that CTs can carry up to 20 times the rated current without exceeding 10% ratio correction. However, this not only reduces the sensitivity of relays as some errors may still be present in the secondary current when a severe fault occurs, but also increases the CT size. This paper presents an algorithm for compensating the distorted secondary current of iron-cored CTs under CT saturation using the magnetization (flux-current : .lambda.-i) curve and its performance is examined for fault currents encountered on a typical 345[kV] Korean transmission system, under a variety of different system and fault conditions. In addition, the results of hardware implementation of the algorithm using a TMS320C10 digital signal processor are also presented. The proposed algorithm can improve the sensitivity of relays to low level internal faults, maximize the stability of relays for external faults, and reduce the required CT core cross-section significantly. (author). refs., figs.

  • PDF

A Study on the Operating Characteristic of RCB by Synthesize Harmonic Current (복합고조파에 의한 누전차단기의 동작 특성 연구)

  • Yoo, Jae-Geun;Choi, Myung-Il;Park, Chee-Hyun;Son, Jae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.1
    • /
    • pp.59-63
    • /
    • 2008
  • This paper analyze the operating characteristic of RCB due to the synthesize harmonic current. The RCB of rated sensitivity electric current with 30[mA] test to operating characteristic by synthesize harmonic current and it analyzed the tripping operation due to a harmonic current. The test result, the operating current of RCB changed by synthesize harmonic current.

A Study on Joule Heating Simulation Method to Prevent Sensitivity Current Trip of Electric Vehicle Charger (전기자동차 충전기의 누전차단기 감도 전류 Trip 방지를 위한 Joule Heating 시뮬레이션 방안연구)

  • Lee, Beoung-Kug;Eo, Ik-soo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.22 no.4
    • /
    • pp.150-159
    • /
    • 2021
  • This study aimed to prevent inconvenience to electric vehicle users caused by an interruption of charging by the earth leakage breaker trip that occurs during charging. As a field case study, it was confirmed that during the battery charger failure type, leakage current measurement experiment by vehicle type, and leakage current breaker operation experiment, the internal temperature of the charger rose to more than 60 ℃ in summer, and the earth leakage circuit breaker stopped charging by tripping at 80% of the rated sensitivity current. Through Joule heating modeling, 32A is energized at the reference temperature of 30 ℃ at the initial time t=0 (s). After t=3000 (s), the heat generated around the charging part of the earth leakage breaker increased to 32.4 ℃. The temperature and time factors correlated with the amount of heat generated according to the statistical verification tool with a correlation coefficient of 0.97. Overall, it is possible to prevent the leakage breaker sensitivity current trip due to an increase in temperature inside the charger in summer by performing a Joule heating simulation according to the material of the charging case, the arrangement of the internal wiring, and the dielectric medium when developing the charger device.

A Current Compensating Algorithm with Small Iron-cored CTs (작은 변류기 사용이 가능한 전류 보상 알고리즘)

  • Kang, Sang-Hee;Kang, Yong-Cheol;Park, Jong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 1995.07b
    • /
    • pp.476-478
    • /
    • 1995
  • The conventional technique to deal with CT saturation is overdimensioning of the core so that CTs can carry up to 20 times the rated current without exceeding 10% ratio correction. However, this not only reduces the sensitivity of relays, but also increases the CT core size in proportion to the expected maximum fault current to avoid CT saturation. This paper presents a technique of estimating the secondary current corresponding to the CT ratio which can reduce the required CT core cross section significantly.

  • PDF

A Study on the Current Minimization of a Outer-Rotor Type BLDC Motor for Low Voltage Application (저전압용 외전형 BLDC 전동기의 소비전류 최소화에 대한 연구)

  • Kim, Han-Deul;Chung, Gyo-Bum;Shin, Pan Seok
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.21 no.2
    • /
    • pp.211-216
    • /
    • 2018
  • This paper presents a numerical optimization technique and switching phase control technique aiming at improvement of efficiency of the low voltage BLDC motor. The optimization technique is performed using the generalized sensitivity technique, response surface method(RSM) and sampling minimization technique. In order to minimize current consumption of the BLDC motor, the switching method of the driving device is optimized using RSM with finite element analysis. The ratings of BLDC motor are 50 W, 24 V, 1200 rpm. As optimizing results, the input current is reduced from 2.78 to 2.51 [A] when the switching phase is shifted by -2.65 [DEG_ELC] at the rated driving speed of 1200 [rpm]. It is confirmed that the proposed method reduces the consuming current of the low voltage BLDC motor through switching phase control method using the numerical optimization method.

Rotor Slot Shape Optimization for the Improvement on Slip-Torque Characteristics (속도-토오크 특성개선을 위한 회전자 슬롯 형상 최적화)

  • Kwak, I.G.;Lee, H.B.;Park, I.H.;Hahn, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07a
    • /
    • pp.208-210
    • /
    • 1994
  • In this paper, the design sensitivity evaluation based on the 2-dimensional finite clement discretization is presented for the voltage source and eddy current problem. And it is applied to the two shape design problems of the rotor slot of 3-phase squirrel cage induction motors. The first is to increase the starting torque while keeping the rated torque fixed. The other is only to increase the torque at the rated speed while keeping the starting torque fixed. As an optimization method, the Gradient Projection method is used to control casily the torques for various speeds of rotor. One fourth of rotor is analyzed by using a semi-periodic boundary condition. Because the shape of rotor slot has much influence on the slip torque characteristic, the 10 design parameters are taken on the interface between rotor core and rotor bar. The initial shape of rotor slot is the trapezoidal typo with rounding corners.

  • PDF

L2 proficiency and effect of auditory source in processing L2 stops

  • Kong, Eun Jong;Kang, Jieun
    • Phonetics and Speech Sciences
    • /
    • v.7 no.3
    • /
    • pp.99-105
    • /
    • 2015
  • The current study investigates whether Korean-speaking adults show differential sensitivities to the sources of auditory stimuli (L1 Korean and L2 English) in utilizing VOT and f0 in the perceptual mode of L2 stops, and how the L2 proficiency interacts with the learners' low-level phonetic sensitivities in L2 perceptual mode. 48 Korean learners of English participated in the perception experiments where they rated the goodness of English /t/ and /d/ using an analogue scale. Two sets of stimuli (English and Korean sources) were prepared by manipulating VOT (6-steps) and f0 (5-steps) values of productions by an English male (L2 source condition) and a Korean male (L1 source condition). Findings showed that, in judging /t/-likeness, the listeners responded differently to the two auditory stimulus conditions by relying on VOT significantly more in English source condition than in Korean source condition. The listeners' English proficiency did not interact with these differential sensitivities to the auditory stimulus source either along the VOT dimension or the f0 dimension. The results of the current study suggest that low-level contextual information of the auditory source can affect the learners in faithfully being in the L2 perceptual mode.

A Delphi Survey on Performance Indicators of Korean Advanced Practice Nurses (전문간호사 성과지표에 관한 델파이 조사)

  • Kim, Keum Soon;Kang, Ji Yeon;Kim, Bok Ja;Lee, Young Hee;Lee, Eun Nam
    • Journal of Korean Clinical Nursing Research
    • /
    • v.16 no.1
    • /
    • pp.131-143
    • /
    • 2010
  • Purpose: The purpose of this survey was to identify a set of performance indicators for Korean APNs (Advanced Practice Nurses). Methods: A convenience sample of 78 APNs working in 2 leading hospitals in south Korea participated in the three-round Delphi survey. In the first round, subjects were asked to propose performance indicators to evaluate the effectiveness of their practice. They rated the relevancy of each indicator during the second round. In the final round of survey, subjects rated the relevancy of indicators again in the light of second round's overall results and they also were asked to check on current and future use of indicators. Results: After 5 months of three-round Delphi survey, 60 performance indicators were identified. In regard to relevancy, the 10 highly ranked indicators were patient satisfaction, self-care ability, expertise of service, family satisfaction, nurse satisfaction, satisfaction in nursing education, advanced nursing service count, education for patient/ family, education for nurse, and compliance. Advanced nursing service count, education for patient/ family, and education for nurse are currently used as indicators by more than 70% of respondents. Conclusion: Additional research is needed to identify subsets of performance indicators for specialized areas and to determine the validity and sensitivity of indicators.