• Title/Summary/Keyword: RSET(Required Safety Egress Time)

Search Result 21, Processing Time 0.015 seconds

A Study on ASET Elongation & Notification Time to Fire Stations for the Escape Safety of Aged Bedridden Patients in Elderly Long-term Medical Care (노인의료복지시설 화재 시 와상노인의 피난안전성 제고를 위한 피난허용시간 연장과 소방기관으로의 통보시간 연구)

  • Park, Hyung-Joo;Lee, Young-Jae
    • Fire Science and Engineering
    • /
    • v.32 no.4
    • /
    • pp.50-59
    • /
    • 2018
  • Recently, huge life losses occurred in the elderly long-term medical care fires due to lack of escape safety. As part of the measures to enhance the effectiveness of fire escape safety, while they prolong the available safe egress time (ASET) of non fire compartments, a measure to shorten fire-fighter's arrival time by fire alarm notifying device should be implemented in these facilities. The four categories from the aspects of fire prevention/protection engineering were provided with the necessary component technologies for carrying out these helper-guided evacuations. Fire prevention engineered technology was presented by two provisions; one for ensuring small compartment sections by installing the fire rated wall between bed rooms and another for ensuring the fire retardant or/and non-flammable performance of finishing materials. Also fire protection engineered technology was presented by two items; one for imposing cooling effects by sprinklers and another for providing automatic fire alarm notifying functions to fire stations. In order to improve the escape safety of these facilities in Korea, alternative revisions may presented by considering insufficient provisions in the architectural/fire law provisions by analyzing the provisions of Japanese and domestic laws in detail.