• Title/Summary/Keyword: R-22 대체냉매

Search Result 86, Processing Time 0.018 seconds

The Condensation Heat Transfer of Alternative Refrigerants for R-22 in Small Diameter Tubes (세관내 R-22 대체냉매의 응축열전달에 관한 연구)

  • Son, Chang-Hyo;Jeong, Jin-Ho;O, Jong-Taek;O, Hu-Gyu
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.25 no.2
    • /
    • pp.180-186
    • /
    • 2001
  • The condensation heat transfer coefficients of pure refrigerants R-22, R-134a, and a binary refrigerant mixture R-410A flowing in a small diameter tube were investigated. The experiment apparatus consists of a refrigerant loop and a water loop. The main components of the refrigerant loop consist of a variable-speed pump, a mass flowmeter, an evaporator, and a condenser(test section). The water loop consists of a variable-speed pump, an isothermal tank, and a flowmeter. The condenser is a counterflow heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus. The test section consists of smooth, horizontal copper tube of 3.38mm outer diameter and 1.77mm inner diameter. The length of test section is 1220mm. The refrigerant mass fluxes varied from 450 to 1050kg/(㎡$.$s) and the average inlet and outlet qualities were 0.05 and 0.95, respectively. The main results were summarized as follows ; in the case of single-phase flow, the heat transfer coefficients increase with increasing mass flux. The heat transfer coefficient of R-410A was higher than that of R-22 and R-134a, and the heat transfer for small diameter tubes were about 20% to 27% higher than those predicted by Gnielinski. In the case of two-phase flow, the heat transfer coefficients also increase with increasing mass flux and quality. The condensation heat transfer coefficient of R-410A was slightly higher than that of R-22 and R-134a. Most of correlations proposed in the large diameter tube showed significant deviations with experimental data except for the ranges of low quality and low mass flux.

Study on the Condensation Heat Transfer Characteristics in Small Diameter Tubes (세관 내 응축 열전달 특성에 관한 연구)

  • 박기원;노건상;홍진우;오후규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.28 no.1
    • /
    • pp.29-38
    • /
    • 2004
  • The Condensation heat transfer coefficients of R-22 and R-l34a were measured in smooth horizontal copper tubes with inner diameters of 1.77. 3.36 and 5.35 mm. respectively. The experiments were conducted in a closed loop. which was driven by a magnetic gear pump. They were Performed for the following ranges of variables: mass flux (200 to $500\;kg/\textrm{m}^2{\cdot}s$) saturation temperature $30^{\circ}C$ and quality (0 to 1.0). The main results obtained are as follows Condensation heat transfer coefficients in the small diameter tubes (ID < 7 mm) were observed to be strongly affected by inner diameter change and to differ from those in the large diameter tubes. The heat transfer coefficients in the small diameter tubes were 20 ~ 40 % higher than those in the large diameter tubes as the inner diameter of the tube was reduced. Also. it was very difficult to apply some well-known previous predictions (Cavallini-Zecchin's. Haraguchi's and Dobson's correlation) to small diameter tubes. Based on an analogy between heat and mass transfer the new correlation is Proposed to predict the experimental data more accurately.

Study on the Performance of the Cascade System Using Alternative Refrigerants (대체냉매를 사용한 이원냉동 시스템의 성능에 관한 연구)

  • 박종훈;조금남
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.7
    • /
    • pp.564-571
    • /
    • 2001
  • The present study investigated the effect of key parameters on the performance of a cascade system using R-22 and R-23 refrigerants. Experimental data for the cascade system have been compared with simulation results using thermodynamic analysis. The cascade system tested at the evaporating temperature of $-80^{\circ}C $ and the condensing temperature of$40^{\circ}C $. The key experimental parameters were the evaporating temperature of the HTC(-35, -30, -25, -20, $-15^{\circ}C $) and mass flux of the HTC(200, 250, 300kg/$m^2$s). As the evaporating temperature and the mass flux of the HTC were increased respectively, the COP and the refrigerating efficiency were increased and then decreased while the volume flow rate per unit refrigeration capacity showed the opposite trend. The maximum COP and refrigerating efficiency were obtained at the evaporating temperature of the HTC of $-25^{\circ}C $ and the mass flux of 250 kg/$m^2$s.

  • PDF

Effect of Refrigeration Oil on the Condensation Heat Transfer for Alternative Refrigerant in Microfin Tube with a U-bend (마이크로핀관 곡관부내 대체 냉매의 응축 열전달에 미치는 냉동기유의 영향)

  • 태상진;조금남
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.6
    • /
    • pp.541-549
    • /
    • 2000
  • The present study experimentally investigated the effect of refrigeration oil on the condensation heat transfer for R-407C and R-22 in a microfin tube with a U-bend. POE oil ($74.1\;\textrm{mm}^2/s,\;40^{\circ}C$,) and mineral oil $62.5\;\textrm{mm}^2/s,\;40^{\circ}C$,) were used for R-407C and R-22 respectively Experimental parameters were an oil concentration from 0 to 5%, a mass flux from 100 to $400kg/m^{2}s sand an inlet quality from 0.5 to 0.9. The enhancement factors for both R-22 and R-407C refrigerants at the first straight section decreased continuously as the oil concentration increased. They decreased rapidly as the mass flux decreased and the inlet quality increased. The heat transfer coefficients in the U-bend showed the maximum at the $90^{\circ}$/TEX> position. The heat transfer coefficients at the second straight section within the dimensionless length of 48 were larger by a maximum of 33% than the average heat transfer coefficient at the first straight section.

  • PDF

Pool boiling heat transfer coefficients of alternative refrigerants in enhanced tubes (열전달 촉진관에서 대체냉매의 비등열전달계수)

  • Lee, Jun-Gang;Go, Yeong-Hwan;Jeong, Dong-Su;Song, Gil-Hong;Kim, Jong-Bo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.22 no.7
    • /
    • pp.980-991
    • /
    • 1998
  • In this study, nucleate pool boiling heat transfer coefficients of alternative refrigerants on a plain, low fin, and two enhanced tubes were measured and compared against each other. To obtain data at conditions similar to the actual evaporator, a fluid heating method was employed instead of an electric heating method in the experiments. R123, R134a, R22 and R410a were used as working fluids and data were taken at 7 deg.C ar heat fluxes of 20 ~ 100 kW/m$\^$2/. Comparison of the plain tube data against some correlations showed that the simplest correlation of Cooper based on reduced pressure predicted the data for all fluids tested with a 10% deviation. For all refrigerants, enhanced tubes composed of subsurface and subtunnels, especially Thermoexcel-E tube, showed the highest heat transfer coefficients among the tubes tested with one exception that the low fin tube's performance was better than those of enhanced tubes for high vapor pressure fluid such as R410a at high heat flux. Finally, a low fin and enhanced tubes showed higher heat transfer enhancement for low vapor pressure of R123 than for high vapor pressure fluisd. For R123, the enhancement factors for Turbo-B and Thermoexcel-E tubes were 2.8 ~ 4.8 and 4.6 ~ 8.1 respectively.

Evaporation heat transfer characteristics inside the U-bend of the smooth and the microfin tube using alternative refrigerant (대체냉매를 사용한 평활관 및 마이크로핀관 곡관부내 증발 열전달 특성)

  • Jo, Geum-Nam;Kim, Byeong-Gi
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.21 no.9
    • /
    • pp.1207-1217
    • /
    • 1997
  • The present work experimentally investigated the effects of mass flux, heat flux, inlet quality on the heat transfer performance inside the U-bend of smooth and microfin tube using R-22 and R-407C refrigerants. The parameters were 200 and 400 kg/m$^{2}$ s for mass flux, 6 and 12 kw/m$^{2}$ for heat flux, 0.1 and 0.2 for inlet quality under the pressure of 0.65 MPa. The apparatus consisted of the test section of four straight sections and three U-bends, preheater, condenser, refrigerant pump, mass flow meter etc. The average heat transfer coefficient at the downstream straight section after U-bend was affected by U-bend due to the centrifugal force and mixing of two-phase flow in the U-bend. The average heat transfer coefficient at the U-bend was 4 ~ 33 % higher than that at the straight section. The average heat transfer coefficients were affected in the order of mass flux, heat flux and inlet quality. The average heat transfer coefficients in the microfin tube were lager by 19 ~ 49% and 33 ~ 69% than that in the smooth tube at the straight section and at the U-bend separately. The average heat transfer coefficients for R-407C were larger by 33 ~ 41% and 17 ~ 29% than that for R-22 in the smooth tube and the microfin tube separately.