• Title/Summary/Keyword: Post-quake functional

Search Result 1, Processing Time 0.015 seconds

Case Study On The Seismic Design Strategy For Post-Quake Functional Buildings In China

  • Peng Liu;Xue Li;Yu Cheng;Xiaoyu Gao;Jinai Zhang;Yongbin Liu
    • International Journal of High-Rise Buildings
    • /
    • v.12 no.3
    • /
    • pp.251-262
    • /
    • 2023
  • In response to China's "Regulations on the Management of Earthquake Resistance of Building Constructions" on the provision of eight types of important buildings to maintain functional after fortified earthquakes occur, "Guidelines for Seismic Design of post-quake functional buildings (Draft for Review)" distinguishes Class I and Class II buildings, and gives the performance objectives and seismic verification requirements for design earthquakes and severe earthquakes respectively. In this paper, a hospital and a school building are selected as examples to design according to the requirements of fortification of Intensity 8 and 7 respectively. Two design strategies, the seismic isolation scheme and energy dissipation scheme, are considered which are evaluated through elastic-plastic dynamic time-history analysis to meet the requirement of post-quake functional buildings. The results show that the seismic isolation design can meet the requirements in the above cases, and the energy dissipation scheme is difficult to meet the requirements of the "Guidelines" on floor acceleration in some cases, for which the scheme shall be made valid through the seismic resilience assessment. The research in this paper can provide a reference for designers to choose schemes for post-quake functional buildings.