• 제목/요약/키워드: Pole Transformer

검색결과 108건 처리시간 0.026초

주상변압기 과부하 및 고장보호장치 개발에 관한연구 (A study for the overload and fault protective device of pole transformers)

  • 최봉일;임창호;김창경;김영래;송일근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1992년도 하계학술대회 논문집 A
    • /
    • pp.67-69
    • /
    • 1992
  • This paper presents the new protective device which is developed specifically for use in oil filled distribution transformers. This device is mounted Inside of the transformer and connected between the secondary winding and the secondary bushings. It provides both fault and overload protection to the transformer, and visual warning of the existence of uneconomical loading conditions. It Is available in thermal/magnetic operating device depending upon fault duty required.

  • PDF

신경회로망을 이용한 변압기의 단기부하예측 (Short-Term Load Forecasting of Transformer Using Artificial Neural Networks)

  • 김병수;송경빈
    • 조명전기설비학회논문지
    • /
    • 제19권7호
    • /
    • pp.20-25
    • /
    • 2005
  • 신경회로망을 이용한 변압기의 단기 부하예측 알고리즘을 제안한다. 변압기에 대한 단기부하예측은 그 필요성에도 불구하고 연구자들에게 많은 관심을 받지 못했다. 제안된 알고리즘은 입력값으로 예측일 이전의 변압기 최대부하와 해당지역의 최고온도, 최저온도 그리고 예측일의 최고온도, 최저온도로 구성하고 적절한 학습케이스를 선택하여 신경회로망의 학습을 통해 배전용 변압기의 단기부하예측을 수행하였다. 제안된 방법은 서울 남현동의 배전용 변압기를 샘플로 추출하여 예측하였다. 예측결과 배전용 변압기의 부하예측에 대한 정확도의 우수성을 확인했다. 제안된 알고리즘은 배전용 변압기의 과부하에 의한 사고 예방에 도움을 줄 것이다.

차단기의 투입성능 평가를 위한 최적 합성투입시험설비 (Optimized Synthetic Making Test Facilities for Estimating the Making Performance of Circuit Breaker)

  • 서윤택;김맹현;송원표;고희석;박승재
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제54권6호
    • /
    • pp.284-292
    • /
    • 2005
  • Because all of the short-circuit testing laboratories have the limitation of test facilities, the synthetic making test methods have been used to estimate the short-circuit making performance of the ultra high-voltage circuit breaker as the alternative to direct test methods. So, KERI(Korea Eelctrotechnology Research institute) has completed the construction of the synthetic making test facilities using the low capacity step-up transformer method which fulfill the requirements specified in newly revised IEC 62271-100 Edition 1.1(2003) and have the testing capability up to 550kV, 63kA full-pole circuit breaker. The test facilities using the low capacity step-up transformer method presented in this paper are made up of the unit equipments such as HCS(High-speed Closing Switch), ITMC(Initial Transient Making Current) circuit and UP TR(low capacity step-up transformer) and have the operating range of 17.6$^{\circ}$ $\~$ 145.1$^{\circ}$ for testing the circuit breaker rated on up to 50kA and 43.1$^{\circ}$ $\~$ 119.6$^{\circ}$ for more than 50kA.

Solid State Transformer를 위한 양방향 Dual Active Bridge DC-DC 컨버터의 설계 기법 (Practical Design Methodology of Dual Active Bridge Converter as Isolated Bi-directional DC-DC Converter for Solid State Transformer)

  • 최현준;이원빈;정지훈
    • 전력전자학회논문지
    • /
    • 제22권2호
    • /
    • pp.102-108
    • /
    • 2017
  • Proper design guides are proposed for a practical dual-active bridge (DAB) converter based on the mathematical model on the steady state. The DAB converter is popular in bidirectional application due to its zero-voltage capability and easy bidirectional operation for seamless control, high efficiency, and performance. Some design considerations are taken to overcome the limitation of the DAB converter. The practical design methodology of power stage is discussed to minimize the conduction and switching losses of the DAB converter. Small-signal model and frequency response are derived and analyzed based on the generalized average method, which considers equivalent series resistance, to improve the dynamics, stability, and reliability with voltage regulation of the practical DAB converter. The design of closed-loop control is discussed by the derived small-signal model to obtain the pertinent gain and phase margin in steady-state operation. Experimental results of a 3.3 kW prototype of DAB converter demonstrate the validity and effectiveness of the proposed methods.

개스분석에 의한 주상변압기의 예방진단에 관한 연구 -자외-가시선 흡수분광광도법에 의한 절연유의 열화도 측정- (A Study on Preventive Diagnosis of the Pole Transformer by Gas Analysis -Measurement of Aging of Insulating Oil by UV-Visible Spectrophotometric Method-)

  • 곽희로;남영우;윤영자;남궁미옥;이동준
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제10권5호
    • /
    • pp.94-100
    • /
    • 1996
  • 자외- 가시선 흡수분광광도법을 적용하여 주상변압기 절연유의 판정기준을 제시하였다. 절연유가 열화하면 절연유의 전기적 특성치가 저하할 뿐만 아니라 흡광도값도 변하게 된다. tan$\delta$와 절연파괴전압과 같은 전기적 특성치를 흡광도값과 비교하여 흡광도값에 의한 절연유의 판정기분을 설정하였다. 흡광도값이 0.580 이하는 양호, 요주의는 0.580~0.900, 불량은 0.900이상이다. 자외-가시건 흡수분광광도법은 절연유의 열화분석에 적용할 수 있으며, 기존의 육안에 의한 절연유 검사 방법을 대체할 수 있을 것으로 기대된다. 그러나 분광광도법을 현장에 적용하려면 저렴하고 경량화된 휴대용 분광광도계의 개발이 필요하다.

  • PDF

부하관리 개선을 위한 부하 상관계수 산정에 관한 연구 (Adjustment of load correlation coefficient for advanced load management)

  • 박창호;조성수;김기현;임진순;김두봉;김재철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1267-1269
    • /
    • 1999
  • This paper studies on arrangement of load correlation coefficient for advanced load management. To accurate load correlation coefficient, we used two real factors, electrical energy(kWh) and peak load current of pole transformers, acquired by measuring instrument. Out of several correlation equations, we find that the quadratic equation is the most accurate to express peak load current and working electrical energy. If the data is located in the outside of ${\pm}3{\sigma}$ it is discarded. For load management, we rearranged load correlation coefficient considering +2${\sigma}$ at load correlation equation. Comparing conventional load correlation coefficient with rearranged one, we can get the result of error reduced and it is adjacent to the actual data. It will be used peak load forecasting from working electrical energy and we are able to prevent from the damaging of pole transformer due to overload.

  • PDF

분산전원이 연계된 배전계통에 있어서 선로전압조정장치(SVR)의 전압제어 개선방안 (Improvement Method of SVR Control in Power Distribution System Interconnected Distributed Generator)

  • 이현옥;허재선;김병기;노대석;김재철
    • 전기학회논문지
    • /
    • 제63권2호
    • /
    • pp.224-229
    • /
    • 2014
  • This paper presents the novel voltage control method in power distribution system with distributed generators. The voltage in distribution systems is regulated by Under Load Tap Changer(ULTC) of substation and pole transformer of primary feeders. Recently, Step Voltage Regulator(SVR) is getting located at distribution feeders to regulate effectively voltage of primary feeders. But the effectiveness of SVR decreases due to independent operation between SVR and ULTC, and also the existing Line Drop Compensator(LDC) method considering the distributed generators may be not able to regulate the proper voltage in a permissible range. Thus, this paper presents a optimal voltage control algorithm of SVR by using the secondary voltage data of main transformer in substation.

초고압 현수애자의 Pin 형상에 따른 응력해석 (The Temperature Distribution Analysis and Temperature Rise Test of Pole Mold Transformer)

  • 조한구;박기호;한세원;윤문수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.155-157
    • /
    • 2001
  • Various types suspension insulators made of toughness glass or porcelain are used in the power transmission. And, Insulators are continually subject to mechanical and electrical stresses which depend on the characteristics of the line. The main factor that influence the increase in reliability of insulators. In operation is the capacity of the design to withstand the certain load over a long time, the mechanical strength of the insulators. This paper describes the results of a study on the stress analysis of suspension insulator based on the finite element analysis using NASTRAN. And, the mechanical strength was evaluated through such as kinds of pin type.

  • PDF

가스켓용 고무소재의 특성수명 예측 (Prediction of Characteristics Life of the Rubber Gasket)

  • 박준형;이세희;장현덕;김광섭;양정삼
    • 한국신뢰성학회지:신뢰성응용연구
    • /
    • 제10권4호
    • /
    • pp.213-235
    • /
    • 2010
  • In this paper, we carried out an accelerated degradation test that is commonly used to predict characteristics life of rubber gaskets for a pole transformer. The potential failure mode applied for the test is rubber elongation and the corresponding failure mechanism is heat. From the result, we found that Weibull distribution is the fatigue life distribution in NBR and H-NBR. After estimating characteristics life in commonly used temperature, the average life span of $B_{50}$ in NBR is 7.7 years under $50^{\circ}C$ and the life span in H-NBR is 28 years.

열 열화에 의한 주상변압기의 수명 손실 (Life Loss of Pole Mounted Transformers by Thermal Aging)

  • 정종만;이병성;송일근
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.209-213
    • /
    • 2005
  • To enhance the reliability of distribution transformers in service and to reduce the cost of maintaining and replaceing these, the condition and life of those insulating system should be evaluated accurately and the time to replace should be determined economically. Since the transformer failures related to insulation failure indicates that the primary cause is normally mechanical failure of integrity due to loss of mechanical strength as a result of degradation, the tensile strength characteristics of paper during ageing under accelerated conditions in insulating oil and research trends for assessing the life of insulating paper were investigated.

  • PDF