• Title/Summary/Keyword: Pipe failure

Search Result 352, Processing Time 0.027 seconds

Deterioration Prediction Model of Water Pipes Using Fuzzy Techniques (퍼지기법을 이용한 상수관로의 노후도예측 모델 연구)

  • Choi, Taeho;Choi, Min-ah;Lee, Hyundong;Koo, Jayong
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.30 no.2
    • /
    • pp.155-165
    • /
    • 2016
  • Pipe Deterioration Prediction (PDP) and Pipe Failure Risk Prediction (PFRP) models were developed in an attempt to predict the deterioration and failure risk in water mains using fuzzy technique and the markov process. These two models were used to determine the priority in repair and replacement, by predicting the deterioration degree, deterioration rate, failure possibility and remaining life in a study sample comprising 32 water mains. From an analysis approach based on conservative risk with a medium policy risk, the remaining life for 30 of the 32 water mains was less than 5 years for 2 mains (7%), 5-10 years for 8 (27%), 10-15 years for 7 (23%), 15-20 years for 5 (17%), 20-25 years for 5 (17%), and 25 years or more for 2 (7%).

Failure Mode and Fracture Behavior Evaluation of Pipes with Local Wall Thinning Subjected to Bending Load (감육배관의 굽힘하중에 의한 손상모드와 파괴거동 평가)

  • Ahn, Seok-Hwan;Nam, Ki-Woo;Kim, Seon-Jin;Kim, Jin-Hwan;Kim, Hyun-Soo;Do, Jae-Yoon
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.27 no.1
    • /
    • pp.8-17
    • /
    • 2003
  • Fracture behaviors of pipes with local wall thinning are very important for the integrity of nuclear Power Plant. In Pipes of energy Plants, sometimes, the local wall thinning may result from severe erosion-corrosion (E/C) damage. However, the effects of local wall thinning on strength and fracture behaviors of piping system were not well studied. In this paper, the monotonic bending tests were performed of full-scale carbon steel pipes with local wall thinning. A monotonic bending load was applied to straight pipe specimens by four-point loading at ambient temperature without internal pressure. From the tests, fracture behaviors and fracture strength of locally thinned pipe were manifested systematically. The observed failure modes were divided into four types; ovalization. crack initiation/growth after ovalization, local buckling and crack initiation/growth after local buckling. Also, the strength and the allowable limit of piping system with local wall thinning were evaluated.

Waterhammer Caused by Startup and Stoppage of a Centrifugal Pump (원심펌프의 시동 및 정지에 따른 수격현상)

  • Kim, Kyung-Yup;Kim, Joum-Bea
    • The KSFM Journal of Fluid Machinery
    • /
    • v.7 no.1 s.22
    • /
    • pp.51-57
    • /
    • 2004
  • The waterhammer has recently become more important because the pumping stations were big and the systems conveying the fluid through the large and long transmission pipelines were complex. When the pumps are started or stopped for the operation or tripped due to the power failure, the hydraulic transients occur as a result of the sudden change in velocity As the pressure waves are propagating between the pumping station and the distributing reservoir, the pressure inside the pipe drops to the liquid vapor pressure with the pipeline profile, at which time a vapor cavity forms, and finally the column separation occurs. If the pressure in the pipe is less than the atmospheric pressure, the pipe can be collapsed and destroyed after the water columns separated by the vapor cavity rejoin. During the reverse flow, the pressure is so abnormally increased at the pumping station that the accident of flooding may happen due to the failure of system. In this paper, the field tests on the waterhammer by the startup, stoppage, and power failure of a centrifugal pump were carried out for Yongma transmission pumping station in Seoul. The experimental results were compared with that of the numerical calculations, in which results the procedure of controlled pump normal shut-down and the two-step closing mode of controlling the ball valve for pump emergency stop are proposed to reduce the pressure surge.

Failure Criteria of a 6-Inch Carbon Steel Pipe Elbow According to Deformation Angle Measurement Positions (변형각의 측정 위치에 따른 6인치 탄소강관엘보의 파괴 기준)

  • Yun, Da Woon;Jeon, Bub Gyu;Chang, Sung Jin;Park, Dong Uk;Kim, Sung Wan
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.26 no.1
    • /
    • pp.13-22
    • /
    • 2022
  • This study proposes a low-cycle fatigue life derived from measurement points on pipe elbows, which are components that are vulnerable to seismic load in the interface piping systems of nuclear power plants that use seismic isolation systems. In order to quantitatively define limit states regarding leakage, i.e., actual failure caused by low-cycle fatigue, in-plane cyclic loading tests were performed using a sine wave of constant amplitude. The test specimens consisted of SCH40 6-inch carbon steel pipe elbows and straight pipes, and an image processing method was used to measure the nonlinear behavior of the test specimens. The leakage lines caused by low-cycle fatigue and the low-cycle fatigue curves were compared and analyzed using the relationship between the relative deformation angles, which were measured based on each of the measurement points on the straight pipe, and the moment, which was measured at the center of the pipe elbow. Damage indices based on the combination of ductility and dissipation energy at each measurement point were used to quantitatively express the time at which leakage occurs due to through-wall cracking in the pipe elbow.

THERMAL ANALYSIS OF SURFACE HEAT PIPE INSTALLED PANEL OF GEOSTATIONARY SATELLITE (외장형 HEAT PIPE 가 장착된 정지궤도 위성 패널의 열해석)

  • Jun H.Y.;Kim J.H.
    • Journal of computational fluids engineering
    • /
    • v.11 no.3 s.34
    • /
    • pp.8-13
    • /
    • 2006
  • The north panel of a geostationary satellite is used as one of the main radiators, on which communication equipment or bus equipment are installed. The thermal control of panel is designed by using embedded heat pipes and surface heat pipes (or external heat pipes) to spread out heat dissipated from equipment all over the radiator evenly and finally to reject the heat to the space through the radiator efficiently. This panel is also divided by several areas based on the operating temperature and dissipation of equipment in order to increase heat rejection capability of radiator. The thermal analysis is carried out for the hot case, Winter Solsitce EOL (End Of Life), in order to validate thermal design of the panel utilized 6 surface heat pipes and 8 embedded heat pipes. The sensitivity studies for the heat pipe failure case and no heat pipe case are performed and compared to its normal state. The heat transport capability of heat pipe is also obtained from these calculations.

A Study on Grooving Corrosion at the Weld of a Low Carbon Steel Pipe Made by Electrical Resistance Welding (탄소강관의 ERW 용접부 홈부식 손상에 관한 연구)

  • Kim Yong;Lee Bo-Young
    • Journal of Welding and Joining
    • /
    • v.22 no.5
    • /
    • pp.58-64
    • /
    • 2004
  • Although leakage at a low carbon steel pipe made by electrical resistance welding (ERW) was reported due to grooving corrosion, the cause for the corrosion has not yet been cleared. In order to clarify the main cause, failure analysis on the leaked pipe was carried out, followed by metallographic investigation and corrosion test for the various ERW pipe made with different welding heat input. The microstructure, particularly inclusion content, of the weldment is dependant on the welding heat input applied. For an improper low heat input, the amount of inclusion at the weld was high. High inclusion content accelerated grooving corrosion at the weld. It is therefore that welding heat input should be controlled based on the carbon content of the pipe in order to improve the corrosion resistance of the ERW pipe.

Geometric Characteristic of Wall-thinning Defect Causing Circumferential Crack in Pipe Elbows (원주방향 균열이 발생되는 곡관 감육부의 형상적 특성)

  • Kim, Jin Weon;Lee, Sung Ho
    • Transactions of the Korean Society of Pressure Vessels and Piping
    • /
    • v.7 no.1
    • /
    • pp.27-34
    • /
    • 2011
  • The objective of this study is to classify the geometry of wall-thinning defect that causes a circumferential crack in the pipe elbows subjected to internal pressure. For this objective, first of all a criterion to determine the occurrence of circumferential cracking at wall-thinned area was developed based on finite element simulation for burst tests of pipe elbow specimens that showed axial and circumferential cracking at wall-thinned area. In addition, parametric finite element analysis including various wall-thinning geometries, locations, and pipe geometries was conducted and the wall-thinning geometries that initiate circumferential crack were determined by applying the criterion to the results of parametric analysis. It showed that the circumferential crack occurs at wall-thinning defect, which has a deep, wide, and short geometry. Also, it is indicated that the pipe elbows with larger radius to thickness ratio are more susceptible to circumferential cracking at wall-thinned area.

Failure Criterion of Straight Pipe with Outer Local Wall Thinning under Internal Pressure (내압을 받는 외부 국부 감육 직관의 파손 기준)

  • Kim, Soo-Young;Nam, Ki-Woo
    • Journal of Power System Engineering
    • /
    • v.18 no.1
    • /
    • pp.76-83
    • /
    • 2014
  • This study was carried out an experimental and finite element analysis on the fracture behavior of straight pipes with local wall thinning under internal pressure. Local wall thinning was machined on the pipes in order to simulate erosion/corrosion metal loss. The configurations of the eroded area has an eroded ratio of d/t=0.80~0.92 and an eroded length of l=25, 50 and 102 mm. Three-dimensional elastic-plastic analyses were also carried out using the finite element method, which is able to accurately simulate failure behaviors. In regards to the relation ship between pressure and eroded ratio, the criterion that can be used safely under operating pressure and design pressure were obtained from this calculation. The results of this calculation were in relatively good agreement with that of the experiment.

Limit States and Corresponding Seismic Fragility of a Pipe Rack for Maintaining Operation (운전성 유지를 위한 파이프랙의 한계상태와 지진취약도)

  • Kim, Juram; Hong, Kee-Jeung;Hwang, Jin-Ha
    • Journal of the Earthquake Engineering Society of Korea
    • /
    • v.27 no.6
    • /
    • pp.283-291
    • /
    • 2023
  • Unlike other facilities, maintaining processes is essential in industrial facilities. Pipe racks, which support pipes of various diameters, are important structures used in industrial facilities. Since the transport process of pipes directly affects the operation of industrial facilities, a fragility curve should be derived based on considering not only the pipe racks' structural safety but also the pipes' transport process. There are several studies where the fragility curves have been determined based on the structural behavior of pipe racks. However, few studies consider the damage criteria of pipes to ensure the transportation process, such as local buckling and tensile failure with surface defects. In this study, an analysis model of a typical straight pipe rack used in domestic industrial facilities is constructed, and incremental dynamic analysis using nonlinear response history analysis is performed to estimate the parameters of the fragility curve by the maximum likelihood estimation. In addition, the pipe rack's structural behavior and the pipe's damage criteria are considered the limit state for the fragility curve. The limit states considered in this paper to evaluate fragility curves are more reasonable to ensure the transportation process of the pipe systems.

Statistical Approach for Corrosion Prediction Under Fuzzy Soil Environment

  • Kim, Mincheol;Inakazu, Toyono;Koizumi, Akira;Koo, Jayong
    • Environmental Engineering Research
    • /
    • v.18 no.1
    • /
    • pp.37-43
    • /
    • 2013
  • Water distribution pipes installed underground have potential risks of pipe failure and burst. After years of use, pipe walls tend to be corroded due to aggressive soil environments where they are located. The present study aims to assess the degree of external corrosion of a distribution pipe network. In situ data obtained through test pit excavation and direct sampling are carefully collated and assessed. A statistical approach is useful to predict severity of pipe corrosion at present and in future. First, criteria functions defined by discriminant function analysis are formulated to judge whether the pipes are seriously corroded. Data utilized in the analyses are those related to soil property, i.e., soil resistivity, pH, water content, and chloride ion. Secondly, corrosion factors that significantly affect pipe wall pitting (vertical) and spread (horizontal) on the pipe surface are identified with a view to quantifying a degree of the pipe corrosion. Finally, a most reliable model represented in the form of a multiple regression equation is developed for this purpose. From these analyses, it can be concluded that our proposed model is effective to predict the severity and rate of pipe corrosion utilizing selected factors that reflect the fuzzy soil environment.