• Title/Summary/Keyword: Perimeter Sprinkler

Search Result 2, Processing Time 0.016 seconds

A Experiment of Sprinkler System to Protect Ceiling Joints of Sandwich Panel Warehouses (샌드위치패널 창고의 벽 천장 접합부 방호용 스프링클러설비 실험)

  • An, Byung-Kug;Kim, Woon-Hyung;Seo, Dong-Hun;Ham, Eun-Gu
    • Journal of the Society of Disaster Information
    • /
    • v.15 no.1
    • /
    • pp.98-108
    • /
    • 2019
  • Purpose: The purpose of this study is to test the sprinkler performance to protect the wall and ceiling joints of the sandwich panel warehouse in case of fire. Method: Based on the field surveys, test was setup and combustibles were prepared. The sprinkler discharge tests were performed at the corner of the wall and right under the sprinkler head. Results: It has been found that operation of the K-80 closed sprinkler head prevents the ignition of the sandwich panel and therefore no damage to the joints of sandwich panels. To prevent skipping phenomenon, it is necessary to install the sprinkler head from the corner of the wall and to keep a minimum distance of 2.4m and a maximum distance of 3m. Conclution: A Standard Operation Procedure should be prepared to suppress and rescue of fire brigade for a sandwich panel warehouse protected by perimeter sprinklers preventing a ignition of core materials and control fire.

An Experimental Study of Sprinkler system for Sandwich Panel Wall Protection (샌드위치패널 벽면보호용 스프링클러설비 적용 실험)

  • Seo, Dong-Hun;Kim, Won-Hyung;Kim, Jong-Hoon;Lee, Young-Jae
    • Fire Science and Engineering
    • /
    • v.31 no.5
    • /
    • pp.37-43
    • /
    • 2017
  • Domestic sandwich panel buildings are widely used on walls and roofs of factories and warehouse facilities. Factory and warehouse facilities have high fire load and rapid spread of fire due to their use characteristics, leading to large fires. Due to the characteristics of materials, walls and roofs are collapsed, resulting in life damage and property damage. In this regard, this study examined domestic and international standards of sprinkler facilities to prevent ignition of sandwich panel walls. Also, in order to check whether the fire was prevented by installing the head on the wall of the sandwich panel, the fire test was carried out with 10 cm, 60 cm, and 120 cm from the wall along the sprinkler head installation standard of domestic fire safety standards. As a result of the fire test, it was confirmed that the sandwich panel was prevented from igniting when the head of water pressure 0.1 MPa and water quantity K-80 was installed. According to the separation distance, it was impossible to measure the temperature at 10 cm, but at 60 cm, At the maximum temperature of $525^{\circ}C$ and 120 cm, the maximum temperature of the wall of the sandwich panel was measured as $276^{\circ}C$. As a result of the fire test, considering the fire point of 450 degrees Celsius in the fire test of the sandwich panel, the distance from the sandwich panel wall to the combustible is more than 120 cm.