• Title/Summary/Keyword: Partial insulation

Search Result 462, Processing Time 0.022 seconds

A Study on Insulation Diagnosis by Partial Discharge Spectroscopy of Generator Stator Winding (발전기 고정자 권선의 부분방전 특성을 이용한 절연진단 연구)

  • Kang, D.S.;Kim, Y.J.;Kim, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1993.07b
    • /
    • pp.584-587
    • /
    • 1993
  • Mica, which have a good thermal and electrical characteristics, while will cleave easily at these layers. In order to bond mica materials soldily, mica/epoxy composite insulation materials were developed for generator stator winding. There are lots of problems such as delamination and partial discharge of these insulation materials caused by mechanical, electrical and thermal aging. Several experiments have been conducted in order to find the useful diagnostic parameters from the partial discharge phenomena by applying a new measurement techniques. this paper deals with the partial discharge pulse characteristics, which may be a useful diagnostic concept in predicting insulation condition of generator stator insulation materials. Long term insulation aging test shows that partial discharge phase angle an magnitude are identified as one of the main key techniques for insulation diagnosis on generator stator winding.

  • PDF

Pattern Analysis of the Defects within the Cable Insulation for UHV Underground Transmission Using Partial Discharge (부분방전을 이용한 초고압 지중 송전 절연 케이블 내부 결함의 패턴분석)

  • Park, Jae-Hwa;Lee, Gwang-Yeol;Chae, Seok;Oh, Young-Seok;Kim, Hak-Sung
    • Proceedings of the KIPE Conference
    • /
    • 1998.07a
    • /
    • pp.175-179
    • /
    • 1998
  • The insulation of cable which used for Ultra-High Voltage(UHV) underground power transmission requires excellent insulation capability for high voltage. The typical insulation materials are used XLPE, EPR, etc, but insulation efficiency of these is affected by void or alien substances, existed at the inside of insulators. In this paper, the partial discharge patterns of the defects within insulation cable are observed and analyzed. In this test, void, fiber and metal inclusions which possibly exist in cables, are simulated and investigated the patterns of partial discharges for each models Also the relations between calculated field strength and the insulation breakdown voltage. The experiment shows distinct partial discharge patterns in accordance with the kinds of defects within Insulation cable.

  • PDF

Partial Discharge Phenomenon with $SF_6$ Gas Pressures in Insulation consisting of Insulation Paper and $SF_6$ Gas (SF_6 가스와 절연지의 절연계에서 가스압력에 따른 부분방전현상)

  • 선종호;김광화;박정후;조정수
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.2
    • /
    • pp.65-71
    • /
    • 2001
  • This paper describes partial discharge phenomenon with SF6gas pressures in insulation consisting of insulation paper and SF6 gas. We made the specimens with SF6 gas gaps which exist between aramid papers and electrodes and calculated the electric field intensity in the these gaps. We measured the partial discharge inception voltages and the AC breakdown voltages with the test method of IEC 60060-2 and did the partial discharge degradation experiments with a constant voltage. According to gas pressures, the breakdown voltages in SF6gas gaps were calculated by Paschen's law. And these results showed the ability applying partial discharge inception voltages evaluation to Paschen's law and the relationship between the PD quantities occurring insulation breakdown and PD occurring area.

  • PDF

Reliability Improvement of Insulation Diagnosis Using the Hydro-Generator On-Line Partial Discharge Monitoring System (수력발전기 On-line 부분방전 측정 시스템을 이용한 절연상태 진단의 신뢰성 향상)

  • Ok, Yeon-Ho;Lee, Eun-Woong;Lim, Jae-Il;Park, Ji-Kun;Kwak, Won-Ku;Lee, Jae-Heung;Shin, Jae-Pil;Shin, Byoung-Chol
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.469-475
    • /
    • 2009
  • Accident dangerousness of domestic hydro power generators which are operated in Korea is on the increase because of use at the long term. On this, the Off-line diagnosis techniques developed to the On-line by continued domestic technical development since 2000. Especially, On-line insulation diagnosis of domestic hydro power generator is possible by localization of partial electric discharge sensor and On-line insulation diagnosis system. This paper shows the diagnosis result that is applied localized Ceramic Coupler and PDMS-HG(Partial Discharge Monitoring System for Hydro Generator) at four Chung-ju hydro Generator used for 25 years. Particularly, the confidence of insulation diagnosis is improved by using high frequency filter and sampling the partial discharge signals which occur in site. For reviewing the confidence of On-Line insulation diagnosis system, we measured the outside noises and partial discharge signals during practical operation by using the partial discharge diagnosis system of the Full A/D process. And we reviewed the confidence of the On-Line insulation diagnosis system by comparing and analyzing these data.

On-line partial discharge measurement techniques of hydro-generator windings (수력 발전기 권선에서의 운전중 부분방전 측정기법)

  • 황동하;김진봉;김용주;박명수;김택수
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.45 no.2
    • /
    • pp.294-300
    • /
    • 1996
  • In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the endwinding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current and .DELTA.tan.delta. tests has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot dischages may not be found with off-line diagnoses. This paper introduces the on-line partial discharge measurement techniques using frequency spectrum analyzer(FSA) for the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.

  • PDF

Insulation Characteristics and Partial Discharge for the SF6 Gas Insulated Transformer (SF6 가스 절연변압기의 절연특성과 부분방전)

  • 선종호;김우성;김광화;오원근;하영식
    • Proceedings of the KSR Conference
    • /
    • 2000.11a
    • /
    • pp.740-747
    • /
    • 2000
  • This paper describes insulation characteristics and partial discharge for the SF6 gas insulated transformer. The characteristic of gas insulated transformer and the degradation sequence of solid insulation under SF6 gas atmosphere were explained. The model electrode system of the types that the aramid papers were inserted between two sphere electrodes was prepared. The partial discharge tests were carried out to that system and the insulation characteristics were considered.

  • PDF

Insulation Performance Estimation of Main Relays by Partial Discharges (부분방전에 의한 주계전기의 절연성능 평가)

  • Kil, Gyung-Suk;Kim, Il-Kwon;Park, Dae-Won;Song, Jae-Yong;Lee, Gang-Won;Cho, Eun-Je
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.4
    • /
    • pp.388-392
    • /
    • 2007
  • A new dielectric test on main relays of electric traction vehicles, the partial discharge(PD) test, is proposed. The PD test will not affect the insulation performance of specimen during the test and provide much more detailed information on insulation, the types of defects, and so on. Insulation performance of relays is estimated by discharge inception voltage(DIV), discharge extinction voltage (DEV), and apparent charge as a function of test voltage and time. Three main relays of different manufacturing date were estimated by applying AC voltage with three patterns in ranges of $0{\sim}1,200[V]$. From the results, we could estimate insulation state and which types of defects exist in them.

Partial Discharge Phenomena with $SF_{6}$ Gas Pressures in Insulation Consisted of Insulation Paper and $SF_{6}$ Gas(II) ($SF_{6}$가스와 절연지의 절연계에서 가스압력에 따른 부분방전 현상(II))

  • Seon, Jong-Ho;Kim, Gwang-Hwa;Park, Jeong-Hu;Jo, Jeong-Su
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.9
    • /
    • pp.430-435
    • /
    • 2002
  • The $SF_{6}$ gas insulated power equipments have the insulation systems which are composed of $SF_{6}$ gas and insulation paper. It is repored that their insulation abilities are influenced by the $SF_{6}$ gas gaps in those insulation systems and gas pressures. This paper describes partial discharge phenomena with $SF_{6}$ gas pressures in insulation system of $SF_{6}$ gas-insulation paper Specimens of $SF_{6}$ gas-insulation paper were prepared and aramid paper was used as insulation paper. Partial discharge inception voltages(PDIV) and breakdown voltages for the existence of $SF_{6}$ gas gaps were measured by short term tests with gas pressures. Also, average PD quantities and pulse counts, life times of each specimens were calculated from the results of long term aging tests with gas pressures. It was found that the $SF_{6}$ gas gaps decrease increasing rates of PDIV and brealdown voltages according to gas pressure increase and the insulation breakdown caused by the smaller PD quantities than 1[pC] at the high gas pressure of 300kPa is due to the increase of energy density with increase of gas pressure.

The Assessment on the Insulation Condition of Generator Stator Windings by a Novel Parameter PDI(Partial Discharge Index) (새로운 파라메타인 부분방전 변화지수에 의한 발전기 고정자 권선의 절연상태 평가)

  • Hwang, Don-Ha;Park, Do-Yeong;Kim, Yong-Ju;Kim, Jin-Bong;Ju, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.11
    • /
    • pp.735-741
    • /
    • 1999
  • The monitoring and assessment on the insulation condition of generator stator windings have been an important task of utility companies. The interest for the assessment of insulation condition has been increasing due to the need to keep old generating equipment reliable in order to extend the equipment life and to increase the generating capacity. Even though many developments and research activities for the condition assessment of generator insulation have been performed for decades, the assessment criterion in order to consistently predict the actual insulation condition is still in question. In this paper, the correlation between the parameters and the insulation condition is analyzed through the various non-destructive diagnostic tests in order to establish the assessment criterion on insulation deterioration of generator stator windings. By analyzing the correlation, PDI(Partial Discharge Index) as a novel parameter for the assessment criterion on insulation diagnosis of stator winding is proposed and verified.

  • PDF

A Study on the Condition Diagnosis for A Gas-insulated Transformer using Decomposition Gas Analysis (가스분해 분석기법을 활용한 가스 전열 변압기의 상태 진단 연구)

  • Ah-Reum, Kim;Byeong Sub, Kwak;Tae-Hyun, Jun;Hyun-joo, Park
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.8 no.2
    • /
    • pp.119-126
    • /
    • 2022
  • A growing number of gas-insulated transformers in underground power substations in urban areas are approaching 20 years of operation, the time when failures begin to occur. It is thus essential to prevent failure through accurate condition diagnosis of the given facility. Various solid insulation materials exist inside of the transformers, and the generated decomposition gas may differ for each gas-insulated equipment. In this study, a simulation system was designed to analyze the deterioration characteristics of SF6 decomposition gas and insulation materials under the conditions of partial discharge and thermal fault for diagnosis of gas-insulated transformers. Degradation characteristics of the insulation materials was determined using an automatic viscometer and FT-IR. The analysis results showed that the pattern of decomposition gas generation under partial discharge and thermal fault was different. In particular, acetaldehyde was detected under a thermal fault in all types of insulation, but not under partial discharge or an arc condition. In addition, in the case of insulation materials, deterioration of the insulation itself rapidly progressed as the experimental temperature increased. It was confirmed that it was possible to diagnose the internal discharge or thermal fault occurrence of the transformer through the ratio and type of decomposition gas generated in the gas-insulated transformer.