• Title/Summary/Keyword: Partial discharge tests

Search Result 100, Processing Time 0.029 seconds

The Effect of Pressurized Hydrogen on the Aging and Partial Discharge Activity in Generator Winding Insulations (가압 수소가 발전기 고정자 권선 절연 열화와 부분 방전 특성에 미치는 영향)

  • 김진봉
    • Journal of the Korean Society of Safety
    • /
    • v.14 no.4
    • /
    • pp.100-107
    • /
    • 1999
  • The purpose of the study is to investigate the effect of H$_2$ pressure on partial discharge (PD) activity and aging rate in turbine generator winding insulations. A series of field tests and laboratory tests were peformed to investigate the effect of $H_2$ pressure on PD activity. Field tests were conducted at two unit turbine generators in two conditions, in $H_2$ pressure and in air atmosphere. Obtained results are as follows ; 1) ${\Delta}tan{\delta}$ and maximum partial discharge are reduced with increase of $H_2$ pressure and partial discharge inception voltage. 2) The reduction ratio of ${\Delta}tan{\delta}$ due to $H_2$ pressure is higher than one of PD magnitude. 3) Partial discharge pulses suffer from attenuation and distortion when transmitted along windings, because of the complex L-C network between windings. From the result, partial discharge pulses are subjected to resonance phenomena in a generator winding.

  • PDF

On-Line and Off-Line Partial Discharge Properties in the Pumped Storage Generator Stator Windings (양수발전기 고정자 권선에서 운전중 및 정지중 부분방전 특성)

  • Kim, Hee-Dong;Ju, Young-Ho;Yoon, Dea-Hen
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2089-2092
    • /
    • 1999
  • Partial discharge(PD) tests were performed both when the pumped storage generator(rated 13.8kV and 220MVA) was on-line and off-line. This generator has been equipped with 12 bus coupler sensors in directional mode. PD tests were conducted using partial discharge analyzer(PDA), partial discharge meter(PDM) and digital partial discharge detector. PDA showed that the patterns of the normalized quantity number(NQN) and the partial discharge magnitude are in accord with on-line and off-line. The insulation condition was estimated by diagnostic tests(off-line) such as PD magnitude and dissipation factor.

  • PDF

Partial Discharge Property of Hydrogenerator Stator Windings (수력발전기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.

  • PDF

On-line partial discharge measurement techniques of hydro-generator windings (수력 발전기 권선에서의 운전중 부분방전 측정기법)

  • 황동하;김진봉;김용주;박명수;김택수
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.45 no.2
    • /
    • pp.294-300
    • /
    • 1996
  • In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the endwinding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current and .DELTA.tan.delta. tests has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot dischages may not be found with off-line diagnoses. This paper introduces the on-line partial discharge measurement techniques using frequency spectrum analyzer(FSA) for the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.

  • PDF

Off-Line and On-Line Partial Discharge Properties of Large Turbine Generator (대용량 터빈발전기 고정자 권선의 정지중 및 운전중 부분방전 특성)

  • Kim, Hee-Dong;Lee, Young-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1846-1849
    • /
    • 2000
  • Off-line and on-line partial discharges were measured on a 828MVA, 22kV and direct hydrogen-cooled large turbine generator. Partial discharge tests were conducted using digital partial discharge detector(PDD) and turbine generator analyzer(TGA). PDD and TGA showed that off-line partial discharge pattern seems to be very, similar to that found with on-line. Most of the partial discharge is originating with the stator slot in the three phases. As the partial discharge activity is very low, the stator insulation condition of this generator is very good.

  • PDF

Characteristics of Insulation Aging in Large Generator Stator Windings (대용량 발전기 고정자 권선의 절연열화 특성)

  • Kim, Hee-Dong;Lee, Young-Jun;Ju, Young-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.7
    • /
    • pp.1375-1379
    • /
    • 2009
  • Insulation tests have been performed on two generator stator bars under accelerated aging under a laboratory environment. Electrical stress was applied to stator bar No.1, and electrical and thermal stresses were applied to stator bar No.2. Nondestructive stator insulation tests including the ac current, dissipation factor($tan{\delta}$), and partial discharge tests have been performed on both bars as the bars were aged for 11460 hours. Experimental test results show that ${\Delta}I$, ${\Delta}tan{\delta}$, and partial discharge of No. 1 and No.2 stator bars increased with increased in aging time. It has been concluded from the test that the stator insulation of the two generators are in good condition.

A study on the heat cycle aging of insulation materials in large generator stator windings (대형발전기 고정자권선 절연재료의 열 사이클에 의한 열화에 관한 연구)

  • 김희곤;박영관
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.45 no.4
    • /
    • pp.553-557
    • /
    • 1996
  • Heat cycle aging of insulating materials in large generator stator winding has been investigated using both on-line and off-line test methods. On this study, principally, off-line test against actual generator in service was carried out to acquire information about polarization index(PI) and dissipation factor, dissipation factor tip-up, maximum partial discharge for the purpose of remnant breakdown voltage and life assessment. It was found from the tests that both dissipation factor and maximum partial discharge decreased with the increase of operating hours and starting numbers. It was found from off-line tests that the remnant breakdown voltage had a strong relationship with both dissipation factor and maximum partial discharge the remnant breakdown voltage as a results of both operating hours and starting number and the nondestructive tests were proposed as parameters which can predict the remnant lifetime of insulating materials in large generator stator windings. (author). 8 refs., 8 figs., 2 tabs.

  • PDF

Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings (수력발전기 고정자 권선의 운전중 부분방전 특성)

  • Kim, Byong-Han;Kim, Hee-Dong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.172-177
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude$(Q_m)$ were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, Band C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, Band C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrogenerators were in good condition.

Partial Discharge Properties of High Voltage Motor Stator Insulation using Partial Discharge Analyzer (PDA를 이용한 고압전동기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong;Lee, Sang-Kil
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05c
    • /
    • pp.225-228
    • /
    • 2001
  • Partial discharge(PD) testing for different capacitive couplers was performed on a 6.6kV, 448kW pulverizer motor. The motor has been in service for twenty years. PD tests were measured using digital partial discharge detector(DPDD) and partial discharge analyzer(PDA), respectively. PDA is used to in the motor stator insulation, which three 80pF or three 500pF epoxy-mica couplers were installed, one per phase. The 500pF couplers did detect more normalized quantity number(NQN) than the 80pF couplers. DPDD and PDA showed that PD and NQN magnitudes increased with increase of ac voltage. Internal discharge was discovered in the motor stator insulation. DPDD and PDA test results are in accordance with the pattern and magnitude of PD.

  • PDF

A Study on the Effect of Pressure upon A.C Partial Discharge in Insulating Oil (제어유의 문류품분효전에 미치는 형력의 영향)

  • Sang-Hoon Kook
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.32 no.7
    • /
    • pp.227-233
    • /
    • 1983
  • Noticing that action of gaseous phase in insulating oil concerns to the discharging characteristics, I investigated the smalness pressure effects on quantity of the partial discharge and discharging pulse frequency. Tests are carried out between the niddle points in insulating oil at pressure being changed by gradual charge of inert gas Ar. At pressure as low as of 0.1-0.5 torr pulse frequency and maximum partial discharge reach peak while at pressure haigher than 20 torr no pulse is observed. The fact that pulse frequency has peak value at certain presure, which is changed either by charging Ar or by adding oil, implies that the action of gaseous phase depends on pressure. Test results are that partial discharge pulse are governed by pressure of Ar-charged oil, and less partial discharge pulses correspond to smaller bubbles whereas more partial descharge pulses correspond to larger bubbles.

  • PDF