• 제목/요약/키워드: Partial discharge detection

검색결과 197건 처리시간 0.026초

부분방전 신호의 PRPDA누적 검출과 퍼지 알고리즘을 이용한 컴퓨터 진단에 관한 연구 (A study about computer diagnosis that apply fuzzy algorithm and PRPDA accumulation detection of PD signal)

  • 김진수;박건준;오성권;김용갑
    • 대한전자공학회:학술대회논문집
    • /
    • 대한전자공학회 2005년도 추계종합학술대회
    • /
    • pp.1015-1018
    • /
    • 2005
  • In this paper, we introduce about a new class to analysis of partial discharge signal based on Fuzzy model. We can early diagnose life of power cable through detection of partial discharge signal. However, partial discharge signal detector is difficult because of partial discharge signal is very non-linear. Also, it is very difficult work that separate partial discharge signal from noise. We constructed partial discharge accumulation detection system that use Labview for detection of non-linear partial discharge signal. And analyzed partial discharge signal that is detected by Labview system utilizing Fuzzy model.

  • PDF

퍼지 알고리즘을 이용한 부분방전 신호의 진단에 관한 연구 (A study about diagnosis of PD signal using by Fuzzy algorithm)

  • 김진수;박재완;박건준;오성권;김용갑
    • 한국지능시스템학회:학술대회논문집
    • /
    • 한국퍼지및지능시스템학회 2005년도 추계학술대회 학술발표 논문집 제15권 제2호
    • /
    • pp.440-443
    • /
    • 2005
  • In this paper, we introduce about a new class to analysis of partial discharge signal based on Fuzzy model. We can early diagnose life of power cable through detection of partial discharge signal. However, partial discharge signal detector is difficult because of partial discharge signal is very non-linear. Also, it is very difficult work that separate partial discharge signal from noise. We constructed partial discharge accumulation detection system that use Labview for detection of non-linear partial discharge signal. And analyzed partial discharge signal that is detected by Labview system utilizing Fuzzy model.

  • PDF

HFCT를 활용한 고전압직류송전 케이블 부분방전 위치추정 (Detection and localization of partial discharge in high-voltage direct current cables using a high-frequency current transformer)

  • 홍선민;손우영;천혜원;강대경;박종후
    • 센서학회지
    • /
    • 제30권2호
    • /
    • pp.105-108
    • /
    • 2021
  • Detection and localization of partial discharge are considered critical techniques for estimating the lifetimes of power cables. High-frequency current transformers (HFCTs) are commonly used for the detection of partial discharge in high-voltage alternating current (HVAC) power cables; however, their applicability is compromised by the limitations of the installation locations. HFCTs are typically installed in cable terminals or insulation joint boxes because HVACs induce strong time-varying magnetic fields around the cables, saturating the ferromagnetic materials in the HFCTs. Therefore, partial discharges near the installation locations can be detected. In this study, the feasibility of partial discharge detection using a HFCT was investigated for high-voltage direct current (HVDC) cables. We demonstrated that the HFCT could be installed at any location in the HVDC power cable to monitor partial discharge along the entire cable length. Furthermore, we showed that the HFCT could detect the location of partial discharge with high accuracy.

인공지능 알고리즘을 이용한 부분방전 진단에 관한 연구 (A Study on Partial Discharge Diagnosis Using AI Algorism)

  • 김진수;김일권;박건우;김광순;김영일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.1382-1383
    • /
    • 2008
  • In this paper, we have studied for analysis of the partial discharge(PD) signal based on fuzzy algorism. Partial discharge signal detector is difficult because of partial discharge signal is very non-linear. Also, it is very difficult work that separate partial discharge signal from noise. We constructed partial discharge accumulation detection system that use Labview for detection of non-linear partial discharge signal. And analyzed Partial discharge signal that is detected by Labview system utilizing Fuzzy model.

  • PDF

Detection of the Ultrasonic Signals due to Partial Discharges in a 154kV Transformer

  • Kweon, Dong-Jin;Chin, Sang-Bum;Kwak, Hee-Ro
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제2C권6호
    • /
    • pp.297-303
    • /
    • 2002
  • We have developed an on-line ultrasonic detector to monitor partial discharge in an operating transformer. The ultrasonic sensor has 150[KHz] resonance frequency and contains a pre-amplifier with 60[㏈] gain. The on-line ultrasonic detector has 50~300[KHz] frequency band-pass filter to remove electrical and mechanical noises from the transformer. This detector has an ultrasonic signal discrimination algorithm which discriminates ultrasonic signals due to partial discharge in a transformer. A moving average method of ultrasonic signal number was employed to effectively monitor the increasing trend of the partial discharge. This paper describes an experience of partial discharge detection in a 154[㎸] operating transformer using an ultrasonic detector. With regards to gas analysis in oil, C2H2 gas was produced with a warning level in this transformer We detected ultrasonic signals on the transformer steel wall, and estimated the position of partial discharge. With further inspection, we found carbonized marks due to partial discharge on the supporting bolt which fastens the windings.

전력용 변압기 초음파 측정시스템 적용 (Application of the Ultrasonic Detection System for the Power Transformer)

  • 권동진;구교선;김재철
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권12호
    • /
    • pp.553-557
    • /
    • 2005
  • This paper describes the application results of an ultrasonic detection system for the power transformer. The ultrasonic detection system with 6 sensors was applied to detect partial discharge in a 154kV transformer with a dangerous levels of $C_{2}H_{2},\;C_{2}H_4$ and $CH_{4}$ gases. The ultrasonic detection tests were carried out 2 times, respectively, to confirm the existence and location of the partial discharge in the transformer. As a result of internal inspection, the arc trace between the pressure ring and core due to the partial discharge was found at the estimated position based on the amplitude and arriving time of the ultrasonic signals. Therefore, it was verified that the ultrasonic detection system is effective as a preventive diagnosis method for the power transformer. Also, the reliability of the ultrasonic detection system in detecting partial discharges in the transformer was also confirmed. It is expected, therefore, that the ultrasonic detection system will have beneficial effects on applications and verifications in detecting partial discharges for the power transformer.

GIS내부의 부분방전신호 감도개선 및 주파수변환기법에 의한 GIS UHF Sensor 모듈의 외부노이즈차폐기법에 관한 연구 (A Study of the Method for External Noise Shielding using the GIS UHF Sensor Module Applied to the Partial Discharge Signal Sensitivity and Method of Frequency Transforming in the Internal GIS)

  • 이승민
    • 전기학회논문지
    • /
    • 제59권4호
    • /
    • pp.728-732
    • /
    • 2010
  • GIS(Gas insulated switching gear) is power equipment with excellent dielectric strength and is economy merit in high confidence and stability. Recently, because equipment of GIS was occurring problem of confidence used for a long time, partial discharge on-line diagnosis systems have been importantly recognized. Partial discharge (PD) detection is an effective means for monitoring and evaluation of dielectric condition of gas insulated system (GIS). The ultra-high-frequency (UHF) PD detection technique can detect and locate the PD sources inside GIS by detecting electromagnetic wave emitted from PD source. Therefore, real-time diagnostic system using UHF detection method has been developed for this application is being expanded gradually. However, the signal of partial discharge occurring in SF6 gas is very weak and susceptible to external noises which mainly consist of PD in air. Thus, it is important to distinguish the PD in SF6 gas more sensitively from the external noises. Unfortunately, these external noise signals and the partial discharge signals have very similar characteristics. Therefore, to solve this problem, we need the signal processing method for distinguish partial discharge signals with external noise signals for improvement of SNR(signal to noise ratio) and sensitivity. In this paper, we proposed internal signal processing method for removing external noise signals with built-in pre.amplifier and frequency conversion circuit.

운전 중인 전력기기의 부분방전 측정장치 개발에 관하여 (Development of On-Line Patial Discharge Detector for Power)

  • 김광화;선종호;김우성;이종구;이준모;강창원
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2000년도 추계학술대회 논문집
    • /
    • pp.733-739
    • /
    • 2000
  • This paper is described the development of on-line partial discharge detector for high voltage apparatus. This detector consists of acoustic and high frequency current sensors, amplifier part, A/D converter part, data communication part and computer. The contents of paper are characteristics of units and digital signal processing for reducing noise in partial discharge detection. We seek methods to do good digital signal processing for detection of partial discharge. We apply digital filtering methods to the elect Tic signal and a cross con-elation to the acoustic signal. This paper shows the characteristics of these filtering method and cross con-elation in partial discharge detection.

  • PDF

DC 정류기 부분방전 신호검출을 위한 SHF 센서의 성능평가 (Performance Evaluation of SHF Sensor for Partial Discharge Signal Detection on DC Rectifier)

  • 정호성;박영;나희승;장순호
    • 전기학회논문지
    • /
    • 제61권7호
    • /
    • pp.1056-1060
    • /
    • 2012
  • Online monitoring system is becoming an essential element of railway traction system for utilized to condition based malignance management and various techniques currently employed in railway traction system. Among the various techniques, it is efficient to detect partial discharge signals by electromagnetic wave detection in order to detect insulation fault of rectifier. Although VHF (Very High Frequency), UHF (Ultra High Frequency) sensors were adopted to detect partial discharge of power facilities, due to characteristics of urban railway, excessive noise occurs from 500 MHz to 1.5 GHz on UHF bandwidth. In this paper a new measurement system able to monitoring the conditions of power facilities on DC substation in metro was studied and set up. The system uses UHF sensors to measure the partial discharge of the rectifier due to electric faulting and dielectric breakdown. Comparison and estimation for performance of SHF sensor which had devised to detect partial discharge signal of urban railway rectifier has conducted. In order to estimate performance of SHF sensor, we have compared the sensor with existing UHF sensor on sensitivity upon frequency bandwidth generated by pulse generator, and also we have verified performance of the SHF sensor by detection results of partial discharge signal from urban railway rectifier.

배전급 CNC케이블의 결함 종류에 따른 부분방전 분포특성 (Partial Discharge Distribution Characteristics along Defect of CNC Cable)

  • 윤재훈;강성화;최한식;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.102-102
    • /
    • 2010
  • A purpose of this paper is to recognize partial discharge pattern for cable insulation. The classification of PD sources was widely studied for two decades. this research sought to use the partial discharge detection method, and to diagnose the interface of cable, which is deemed vulnerable of cable systems. A research abalyzed faults that can occur in the interface of cable joint as well as accident mechanisms, manufactured test 22.9kV CNC cable, invented artificial faults and carried out partial discharge detection experiments. As a result, various PD pattern along defect measured and distinguished.

  • PDF