Characteristics of Insulation Aging in 4.16kV Motor Stator Windings (4.16kV 전동기 고정자 권선의 절연열화 특성)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1381_1382
    • /
    • 2009
  • Nondestructive tests were performed on two 4.16kV motors. Epoxy-mica coupler(80pF) was connected to 4.16 kV motor stator windings. The voltage applied to the stator windings was 2.4 kV, 3.0kV, 3.5kV and 4.16kV, respectively. Digital partial discharge detector(PDD) and turbine generator analyzer(TGA) were used to measure partial discharge(PD) activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of stator windings were indicated the internal discharge. PD patterns are consistent with the result of measurement using PDD and TGA.

  • PDF

Feature Extraction for Fault Signals of High Voltage Motor Stator Windings (고압전동기 결함신호의 특징추출에 관한 연구)

  • Park, Jae-Jun;Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1154-1157
    • /
    • 2004
  • During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in imitation stator winding of high voltage motors. The motor was energized to 4.47kV, 6.67, respectively. Applied voltage to Imitation winding was used two voltage level, 4.47[KV]and 6.67[KV]. Motors having imitation stator winding were installed with 80pF capacitive couplers at the terminal box Case of PD Pattern regarding applied voltage phase angel, the PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). As the result, we could discrimidate using TGA the difference of internal and surface discharge for imitation stator winding. We have used the other technique, in order to feature extraction of faulty signals on stator winding, Daubechies Discrete wavelet transform and Harmonics analysis(FFT) about faulty signals.

  • PDF

Analysis of On-Line Partial Discharge Trend in High Voltage Motors (고압전동기 운전중 부분방전 추이 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik;Kim, Chung-Hyo
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1472-1473
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) measurements were peformed with turbine generator analyzer(TGA) in two high voltage motors(rated 6.6 kV). These high voltage motors were installed with 80 pF capacitive couplers at the terminal box. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude (Qm). The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in stator windings of high voltage motors.

  • PDF

Analysis of Partial Discharge in High Voltage Motor Model Coils (고압전동기 모델 코일의 부분방전 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2091-2093
    • /
    • 2005
  • Five model coils of 6.6kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals, respectively The voltage applied to the coils was 3.81kV, 4.76kV, 6.0kV and 6.6kV. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector (PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns coincide with both PDD and TGA.

  • PDF

Studies on chemical components of fermented maeh in the brewing of Maggerley (Korean wine) (막걸리 제조시 술덧의 성분동태에 관한 연구 1)

  • 이성범;장원길;임병종;김덕치
    • Korean Journal of Microbiology
    • /
    • v.7 no.4
    • /
    • pp.153-158
    • /
    • 1969
  • It is the most important thing to substitute sweet potato for wheat flour as the brewing material of Maggerley(Korean wine) in order to save precious wheat flour which is now consumed as the sole material in it. In this study, the fermenting mash material has been prepared with combination of wheat (KIorean wine) as a first step of sabing wheat flour consuming. The combination ratio of wheat flour and sweet potato starch in mashing, in this experiment, are such as mashing plot of 100% wheat flour (No.3 plot), 50% wheat flour plus 50 % of sweet potato starch (No.2plot), 30% wheat flour plus 70% starch syrup of sweet potato (No. 4 plot), and 60% wheat flour plus sweet potato starch (No. 1 plot). The results of fermentation and chemical components of each mash in experimental plot are as following : 1. Alocholic fermentation was most vigorous in No.4 plost among them, the next are in order to hydrolyze and break down the protein sourece to glucose and amino acid, the new enzymic source were added in experimantal amsh before putting yeasts, those enzymic sources have been developed and prepared in this laboratory No.4 and No.2 plot at same degree. Generally, the activities of alcholic fermentation of all plots are vigorous and fair. The acidity of each fermented mash is in the rangw of 3.7-4.8. 2. Amounts of amino acids in fermented mash are in the range of 145 mg per 100 ml and 158 mg for all experiments, and these amounts are much more than those of present commerical Maggerley. However, the amount of it in the No.4 plots is much less among the m, this is due to the lack of protein source in starch syrup. 3. Amounts of organic acids in fermented mash are in the range of 0.44g per 100ml and 0.62g, these amounts are generally much more than those of the present commercial Maggerley. 4. The result of sensory test for the experimental Maggerley shows good taste and flavour in comparison with those of commercial Maggerely. 5. It is proved that these experimental fermentation of Maggerley is succesful in the partial substitution of sweet potato starch potato starch for wheat flour, and it is also be able to make a good Maggerley in all aspects of quality.

  • PDF

Analysis of Partial Discharge in High Voltage Motor Model Coils (고압전동기 모델 코일에서 부분방전 분석)

  • Kim, Hee-Dong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.178-182
    • /
    • 2006
  • Five model coils of 6.6 kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals. The voltage applied to the coils was 3.81 kV, 4.76 kV, 6.0 kV and 6.6 kV, respectively. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns are consistent with the result of measurement using PDD and TGA instruments. AC breakdown test was performed on five model coils in order to confirm the result of PD measurements. All the failures were located in a line-end coil at the exit from the core slot.

A Complex Noise Suppression Algorithm for On-line Partial Discharge Diagnosis Systems (운전중 부분방전 진단시스템을 위한 복합 잡음제거 기법)

  • Yi, Sang-Hwa;Youn, Young-Woo;Choo, Young-Bae;Kang, Dong-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.2
    • /
    • pp.342-348
    • /
    • 2009
  • This paper introduces a novel denoising algorithm for the partial-discharge(PD) signals from power apparatuses. The developed algorithm includes three kinds of specific denoising sub-algorithms. The first sub-algorithm uses the fuzzy logic which classifies the noise types in the magnitude versus phase PD pattern. This sub-algorithm is especially effective in the rejection of the noise with high and constant magnitude. The second one is the method simply removing the pulses in the phase sections below the threshold count in the count versus phase pattern. This method is effective in removing the occasional high level noise pulses. The last denoising sub-algorithm uses the grouping characteristics of PD pulses in the 3D plot of the magnitude versus phase versus cycle. This special technique can remove the periodical noise pulses with varying magnitudes, which are very difficult to be removed by other denoising methods. Each of the sub-algorithm has different characteristic and shows different quality of the noise rejection. On that account, a parameter which numerically expresses the noise possessing degree of signal, is defined and evaluated. Using the parameter and above three sub-algorithms, an adaptive complex noise rejection algorithm for the on-line PD diagnosis system is developed. Proposed algorithm shows good performances in the various real PD signals measured from the power apparatuses in the Korean plants.

Partial Discharge Measurements of High Voltage Rotating Machine Stator Windings (고압회전기 고정자 권선의 부분방전 측정)

  • Kim, Hee-Dong;Lee, Young-Jun;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1828-1830
    • /
    • 2003
  • Partial discharge(PD) tests are used to evaluate the insulation condition of stator windings in two 4.16kV and three 6.6kV motors. These tests were conducted using a conventional partial discharge detector(PDD) and turbine generator analyzer(TGA). Off-line PD measurements were performed on five high voltage motors. PD magnitudes ranged from 1000 pC to 5400 pC at the normal line-to-ground voltage. Five high voltage motors have been equipped with 80pF epoxy-mica coupler on the motor terminal box. The PD pulse from sensors were measured with the TGA instrument. TGA summarizes each plot with two Quantities such as the peak PD magnitude(Qm) and the total PD activity(NQN). The defect mechanisms of high voltage motor can be associated with PD patterns such as internal, slot and conductor surface discharges. The PDD and TGA test results of No. 4 motor showed that internal discharge was detected in voids of the groundwall insulation.

  • PDF

A new approach on Traffic Flow model using Random Trajectory Theory (확률경로 기반의 교통류 분석 방법론)

  • PARK, Young Wook
    • Journal of Korean Society of Transportation
    • /
    • v.20 no.5
    • /
    • pp.67-79
    • /
    • 2002
  • In this paper, observed trajectories of a vehicle platoon are viewed as one realization of a finite sequence of random trajectories. In this point of view, we develop novel and mathematically rigorous concept of traffic flow variables such as local traffic density, instantaneous traffic flow, and velocity field and investigate their nature on a general probability space of a sequence of random trajectories which represent vehicle trajectories. We present a simple model of random trajectories as an illustrative example and, derive the values of traffic flow variables based on the new definitions in this model. In particular, we construct the model for the sequence of random vehicle trajectories with a system of stochastic differential equations. Each equation of the system nay represent microscopic random maneuvering behavior of each vehicle with properly designed drift coefficient functions and diffusion coefficient functions. The system of stochastic differential equations nay generate a well-defined probability space of a sequence of random vehicle trajectories. We derive the partial differential equation for the expected cumulative plot with appropriate initial conditions. By solving the equation with numerical methods, we obtain the values of expected cumulative plot, local traffic density, and instantaneous traffic flow. In addition, we derive the partial differential equation for the expected travel time to a certain location with appropriate initial and/or boundary conditions, which is solvable numerically. We apply this model to a case of single vehicle trajectory.

Noise Evaluation Algorithm for Applying Complex Denoising Technique in On-line Partial Discharge Diagnosis System for Power Apparatus (전력기기의 운전중 부분방전 진단장치에서 복합잡음제거 적용을 위한 잡음평가 알고리즘)

  • Yi, Sang-Hwa;Youn, Young-Woo;Choo, Young-Bae;Kang, Dong-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.2
    • /
    • pp.70-76
    • /
    • 2009
  • This paper introduces an evaluation code, which can numerically express the noise possessing degree of signals. By using this code, the best kind and setting of noise suppressing techniques can be chosen automatically. This code is applied to three kinds of specific denoising techniques; those are simple noise removing method in the count versus phase distribution, fuzzy logic method based on noise type in magnitude versus phase plot, and lastly, the technique using grouping characteristics of PD pulses in 3D plot of magnitude versus phase versus cycle. The algorithm shows good performance in the various real PD signals measured from various high voltage apparatuses in Korea.