• 제목/요약/키워드: Part-Load

검색결과 2,117건 처리시간 0.029초

Part-load Performance of a Screw Chiller with Economizer using R22 and R407C

  • Chang, Young-Soo;Kim, Young-Il;Lee, Yong-Chul
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제13권1호
    • /
    • pp.1-10
    • /
    • 2005
  • Screw compressor chillers are widely used in refrigeration for capacity over 30 RT. In general, chillers operate under part-load conditions during most of the time. Therefore, information on the characteristics of part-load is very important for better chiller performance and energy economy. In this study, performance tests of screw chiller with economizer using R22 and R407C under part-load conditions have been performed for various secondary fluid temperatures. Adoption of an economizer system increased the cooling capacity and improved COP except for lower part-load condition when economizer volume ratio is 1.01. For the same cooling capacity condition at part-load, COP's of both non-economizer and economizer system showed similar values.

이코노마이저를 채용한 스크류 냉동기에서 R22와 R407C의 부분부하 성능실험 (Part-Load Performance Test of a Screw Chiller with Economizer using R22 and R407C)

  • 장영수;이용철;김영일
    • 설비공학논문집
    • /
    • 제15권11호
    • /
    • pp.902-909
    • /
    • 2003
  • Screw compressor type chillers are widely used in refrigeration for capacity over 30 RT. In general, chillers operate under part-load conditions. Therefore, information on characteristics at part-load is very important in view of chiller performance and energy economy. In this study, performance tests of part-load and economizer system using R22 and R407C have been performed for various secondary fluid temperatures. Adoption of an economizer system increased the cooling capacity and improved COP except for lower part-load condition when injection volume ratio is 1.01. For the same cooling capacity condition at part-load, COP of both non-economizer and economizer system showed similar values.

하천수 열원 2단 압축 열펌프시스템의 부분부하 운전특성에 관한 실험적 연구 (An Experimental Study on the Part-Load Performance of a River Water Source 2-Stage Heat Pump)

  • 김지영;백영진;이영수;나호상
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.1964-1968
    • /
    • 2007
  • The river water heat source heat pump has the advantage in the performance compared to air source heat pump. Although its better performance, the large temperature difference between load and source makes system performance worse by nature. In this study, 2-stage compression is considered as the solution of this problem. Generally, heat pump is designed for maximum capacity rate, but it actually operates at part load condition in many cases. Therefore, an information on the part-load character is very important in view of the system overall performance. In this study, part-load performance tests of a R134a 2-stage compression heat pump were carried out over the river water and supply heating water temperature changes. The experimental results show that the system performance is influenced by the part load rates, river water temperature, load temperature, etc.

  • PDF

2MWe 순환유동상 보일러의 부분 부하 운전 성능 모사 (Performance Simulation of Part Load Operation for 2MWe Circulating Fluidized Bed Boiler)

  • 김태현;최상민;현주수
    • 한국연소학회:학술대회논문집
    • /
    • 한국연소학회 2012년도 제44회 KOSCO SYMPOSIUM 초록집
    • /
    • pp.35-36
    • /
    • 2012
  • Part load operation usually covers large periods of the total operation time on the economic ground and electricity demand in small-scale boilers. Performance analysis of part load behavior is very important for the purpose of boiler operation optimization. A simple thermal calculation approach is applied to predict performance of a pilot-scale circulating fluidized bed (CFB) boiler at part load operation. Verification has been carried out by comparing between calculation results an operation data of the boiler.

  • PDF

자동차 쇽업소버의 피로해석에 관한 연구 (A Study on Fatigue Analysis of Automotive Shock Absorber)

  • 조재웅;한문식
    • 한국공작기계학회논문집
    • /
    • 제17권1호
    • /
    • pp.92-97
    • /
    • 2008
  • The safety and the durability of the shock absorber as an automotive chassis part under the fatigue load can be predicted in this study. The fatigue life becomes constant from 0.5 to 0.75 at the change of load which is the amplitude load divided by average load. But its life is sharply decreased at the change of load from 0.75 to 1.5. The influence of fatigue life according to the change of load can be predicted by these results. As the value of maximum damage is 9.61 at the middle part of upper side on shock absorber under the concentrated load, there is the greatest possibility of destruction at this part. The spring of shock absorber becomes nearly the state of pure shear and the uniaxial or biaxial stress exists at the rest part of it under the fatigue load.

사무소 건물에서 냉동기의 부분부하율 및 냉방 에너지 성능 특성 분석 (A Detailed Analysis of the Part Load Ratio and Cooling Energy Characteristics of Chiller Operation in an Office Building)

  • 서병모;유병호;이광호
    • 설비공학논문집
    • /
    • 제27권11호
    • /
    • pp.567-573
    • /
    • 2015
  • Commercial buildings account for significant portions of the total building energy in Korea, and thus, a variety of research on chiller operation has been carried out. However, most of the studies were carried out on the chiller itself, i.e., the part load ratio characteristics and the corresponding electricity energy consumption patterns were not analyzed in existing studies. In this study, the part load ratio and the operating characteristics of the vapor compression chiller were analyzed within an office building equipped with the conventional variable air volume system. As a result, significant portions of total operating hours, cooling load, and energy consumption turned out to be in the part load ratio range of 0 through 50%. Thus, energy consumption was significantly affected by the chiller COP at low part load conditions, indicating that chiller operation at the part load is an important factor in commercial buildings.

배열 이용도를 고려한 가스터빈 발전시스템의 부분부하 성능 비교분석 (Comparative Part Load Performance Analysis of Gas Turbine Power Generation Systems Considering Exhaust Heat Utilization)

  • 김동섭
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2002년도 유체기계 연구개발 발표회 논문집
    • /
    • pp.290-297
    • /
    • 2002
  • This paper presents analysis results for the effect of power control strategies on the part load performance of gas turbine based power generation systems utilizing exhaust heat of the gas turbine such as cumbined cycle power plants and regenerative gas turbines. For the combined cycle, part load efficiency variations were compared among different single shaft gas turbines representing various technology levels. Power control strategies considered were fuel only control and IGV control. It has been observed that gas turbines with higher design performances exhibit superior part load performances. Improvement of part load efficiency by adopting air flow modulation was analyzed and it is concluded that since the average combined cycle performance is affected by the range of IGV control as well as its temperature control principle, a control strategy appropriate for the load characteristics of the individual plant should be adopted. For the regenerative gas turbine, it is likewise concluded that maintaining exhaust temperature as high as possible by air flow rate modulation is required to increase part load efficiency.

  • PDF

배열 이용도를 고려한 가스터빈 발전시스템의 부분부하 성능 비교분석 (Comparative Part Load Performance Analysis of Gas Turbine Power Generation Systems Considering Exhaust Heat Utilization)

  • 김동섭
    • 한국유체기계학회 논문집
    • /
    • 제6권3호
    • /
    • pp.28-35
    • /
    • 2003
  • This paper presents analysis results for the effect of power control strategies on the part load performance of gas turbine based power generation systems utilizing exhaust heat of the gas turbine such as combined cycle power plants and regenerative gas turbines. For the combined cycle, part load efficiency variations were compared among different single shaft gas turbines representing various technology levels. Power control strategies considered were fuel only control and IGV control. It has been observed that gas turbines with higher design performances exhibit superior part load performances. Improvement of part load efficiency of the combined cycle by adopting air flow modulation was analyzed and it was concluded that since the average combined cycle performance is affected by the range of IGV control as well as its temperature control principle, a control strategy appropriate for the load characteristics of the individual plant should be adopted. For the regenerative gas turbine, it is likewise concluded that maintaining exhaust temperature as high as possible by air flow rate modulation is required to increase part load efficiency.

수소추출기의 부분부하 운전을 위한 PSA 제어전략에 대한 연구 (A Study on PSA Controll Strategy for Part Load Operation of a Hydrogen Generator)

  • 이상호;김선엽;최영
    • 한국수소및신에너지학회논문집
    • /
    • 제33권6호
    • /
    • pp.819-826
    • /
    • 2022
  • Fuel cell systems are being supplied to households and buildings to reduce greenhouse gases. The fuel cell systems have problems of high cost and slow startup due to fuel processors. Greenhouse gas reduction of the fuel cell systems is also limited by using natural gas. The problems can be solved by using a hydrogen generator consisting of a reformer and pressure swing adsorption (PSA). However, part load operation of the hydrogen generator is required depending on the hydrogen consumption. In this paper, PSA operation strategies are investigated for part load of the hydrogen generator. Adsorption and purge time were changed in the range of part load ratio between from 0.5 to 1.0. As adsorption time increased, hydrogen recovery increased from 29.09% to 48.34% at 0.5 of part load ratio. Hydrogen recovery and hydrogen purity were also improved by increasing adsorption and purge time. However, hydrogen recovery dramatically decreased to 35.01% at 0.5 of part load ratio.

부하추종 운전방법에 따른 고체산화물 연료전지/가스터빈 하이브리드 동력 시스템의 부분부하 성능특성 (Part-load Performance Characteristics of a Solid Oxide Fuel Cell/Gas Turbine Hybrid Power System Operating with Various Load-following Operation Modes)

  • 김재훈;양진식;노승탁;손정락
    • 대한기계학회논문집B
    • /
    • 제30권3호
    • /
    • pp.193-200
    • /
    • 2006
  • The purpose of this study is to compare the part-load performance of a SOFC/GT hybrid power system with three different kinds of load-following operation modes. The primary mode for the part load operation of a hybrid power system is the reduction of supplied fuel (e.g., fuel control mode) to the hybrid system. The other two options, i.e., variable speed and VIGV controls, are related to the reduction of supplied air simultaneously with the reduction of supplied fuel to the system. With the performance analysis of a SOFC/GT hybrid power system, it is concluded that the variable speed con佐ol mode Provides the best performance for the part-load operations. It is also found that the VIGV control mode, with its better performance behavior than the fuel control mode, can be used as an important option for the part-load operation especially in case that the variable speed control mode can not be adopted.