• Title/Summary/Keyword: Panelboard

Search Result 5, Processing Time 0.024 seconds

Development of Electrical Safety Monitoring System for Conventional Markets (재래시장 전기안전 감시시스템 개발)

  • Lee, Sang-Ick;Kim, Gi-Hyun;Bae, Seok-Myung
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.552-556
    • /
    • 2009
  • This paper in order to reduce the electric disaster damage which is caused by with electric equipment of conventional markets is introduced the electric safety monitoring system which is suitable in conventional markets. Investigate the actual conditions about electrical equipment of conventional markets, electrical safety monitoring system was constructed. Electrical safety monitoring system to verify the performance of the experiment was to build a test bed. Research results will be used with the data for the reliability security of the electric safe system operation which follows in the conventional markets actual proof equipment construction which will be advanced.

Survey of Panelboard for Weakness Place of Electrical Disaster (전기재해 취약장소의 분전반 실태조사 연구)

  • Lee, Sang-Ick;Kim, Gi-Hyun;Jeon, Hyun-Jae;Bae, Seg-Myeong
    • Proceedings of the KIEE Conference
    • /
    • 2008.04b
    • /
    • pp.125-127
    • /
    • 2008
  • 전기재해에 취약한 장소에서의 화재는 많은 재산상의 피해와 사망자가 발생할 수 있으므로 전기재해에 취약한 장소에서 전기로 인하여 발생할 수 있는 화재를 사전에 예방하고 감시할 수 있는 시스템 개발의 필요성이 있다. 따라서 전기재해에 취약한 장소에서 전기설비를 감시할 수 있는 시스템을 개발하기 위해서는 전기재해 취약장소의 실태조사가 뒤따라야 하므로 전기재해 취약장소 중 하나인 재래시장 분전반을 중심으로 실태조사를 실시하고 그 내용을 분석하여 향후 전기재해에 취약한 재래시장에 알맞은 감시시스템 개발을 위한 기초자료 로 활용하고자 국내 17개소 재래시장 분전반의 실태조사를 실시하고 그 내용을 분석하였다.

  • PDF

Analysis of Electrical Installation Survey at Conventional Markets (재래시장 전기설비 실태조사 분석)

  • Lee, Sang-Ick;Jeon, Hyun-Jae;Kim, Gi-Hyun;Bae, Seok-Myung
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.186-191
    • /
    • 2008
  • The conventional markets is badly damaged by a big fire because of no proper fire fighting management system. The cause of electricity fire is the aging and contact badness of electric equipment. The supervisory detecting system is needed to develop because the electric equipment is located to non visible and non exposing place. In this paper, we investigated the receiving and distributing board, the panel board and the fire prevention system of 17 domestic conventional markets. As a result of survey, capacity of distributing boards is mainly 600A and materials of distributing boards are synthetic resins 49%, metal 44%. ELB is mainly used as branch circuit breaker.

Analysis of Grounding Resistance for Zero Energy Town Floating PV System Using Underground Wiring (매설지선 방식을 적용한 에너지 자립마을용 수상 태양광 발전 시스템의 접지저항 분석)

  • Ko, Jae-Woo;Lim, Jong-Log;Kim, David K.;Cha, Hae-Lim;Kim, Si-Han;Lee, Chang-Koo;Ahn, Hyung-Keun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.5
    • /
    • pp.303-306
    • /
    • 2016
  • Floating PV system is installed on the water such as artificial lake, reservoir, river for the purposes of zero energy town and/or large scale of PV station. There are electrical gains from cooling effect by water and reflection of water surface. Particularly, floating PV power station with high efficiency solar cell modules receives a lot of attention recently. Floating PV system is installed on the water, which means grounding method to the frame of solar cell and electrical box such as connector band and distribution panelboard should be applied in different way from grounding method of PV system on land. The grounding resistance should be 10[${\Omega}$] in case the voltage is over 400[V] in accordance with Korean Standard. The applicable parameters are the resistivity of water in various circumstances, depth of water, and length of electrode in order to meet 10[${\Omega}$] of grounding resistance. We calculated appropriate length of the electrode on the basis of theoretical equation of grounding resistance and analyzed the relation between each parameters through MATLAB simulation. This paper explains grounding system of floating PV power station and presents considerations on grounding design according to the resistivity of water.

Risk Factors of Electrical Fire at the Panelboard and Investigation of Field Conditions (분전반에서의 전기화재 위험요소 및 현장실태조사 분석)

  • Kim, Hyang-Kon;Kim, Dong-Woo;Lee, Ki-Yeon;Choi, Yong-Sung;Choi, Chung-Seog;Choi, Hyo-Sang
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2206-2207
    • /
    • 2008
  • 본 논문에서는 분전반에서의 화재 위험 요소와 화재위험 요소에 대한 현장 실태조사 결과를 분석하였다. 분전반에서의 화재 위험 요소는 크게 전기적 요인, 환경적 요인, 물리적 요인으로 나눌 수 있으며 전기적 요인으로는 단락, 과부하(과전류), 접촉불량, 전류 불평형 등이 있으며 환경적 요인으로는 수분(염분 등), 먼지(분진, 목분, 철분 등), 온도(고온) 등에 의한 절연파괴, 기기 손상, 오동작 등이 있다. 물리적 요인으로는 기계적인 진동이나 충격 등에 의한 전기적 접속부의 이완에 의한 발열 등을 들 수 있다. 이러한 화재 위험 요인에 대하여 현장실태조사를 실시한 결과, 일부 분전반에서 내부에 먼지 등 이물질이 차단기, 전선, 단자대 등의 표면에 부착되어 있음을 확인할 수 있었으며 수분이나 염분 등의 영향으로 전극간 절연물 표면의 열화로 화재가 발생할 가능성이 있다. 또한, 적외선 열화상 분석결과, 일부 차단기 단자에서 국부 발열이 관측되었으며, 부하 분담의 불평형에 의한 발열도 확인되었다. 이러한 위험요인에 의한 화재 예방을 위하여 규정된 전선 굵기의 사용과 적정 체결압력의 확보, 상간 전류 불평형을 줄이기 위한 부하 분담의 조정이 필요하다. 향후, 분전반에서의 전기화재, 감전사고 등 전기재해의 예방을 위하여 지속적이고 체계적인 유지관리는 물론 사고 발생 전에 이상 징후를 사전에 감지하여 조치를 취할 수 있도록 하는 기술의 개발과 현장 적용이 요구된다.

  • PDF