• Title/Summary/Keyword: PD pattern

Search Result 239, Processing Time 0.02 seconds

A Study on Partial Discharge Pattern Recognition Using Neuro-Fuzzy Techniques (Neuro-Fuzzy 기법을 이용한 부분방전 패턴인식에 대한 연구)

  • Park, Keon-Jun;Kim, Gil-Sung;Oh, Sung-Kwun;Choi, Won;Kim, Jeong-Tae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.12
    • /
    • pp.2313-2321
    • /
    • 2008
  • In order to develop reliable on-site partial discharge(PD) pattern recognition algorithm, the fuzzy neural network based on fuzzy set(FNN) and the polynomial network pattern classifier based on fuzzy Inference(PNC) were investigated and designed. Using PD data measured from laboratory defect models, these algorithms were learned and tested. Considering on-site situation where it is not easy to obtain voltage phases in PRPDA(Phase Resolved Partial Discharge Analysis), the measured PD data were artificially changed with shifted voltage phases for the test of the proposed algorithms. As input vectors of the algorithms, PRPD data themselves were adopted instead of using statistical parameters such as skewness and kurtotis, to improve uncertainty of statistical parameters, even though the number of input vectors were considerably increased. Also, results of the proposed neuro-fuzzy algorithms were compared with that of conventional BP-NN(Back Propagation Neural Networks) algorithm using the same data. The FNN and PNC algorithms proposed in this study were appeared to have better performance than BP-NN algorithm.

Pattern Recognition of PD by Particles in GIS (GIS내 파티클에 의한 PD의 패턴인식)

  • 곽희로;이동준
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.1
    • /
    • pp.31-36
    • /
    • 2003
  • This paper describes the quantitative analysis and the pattern recognition of partial discharge signals generated by particles in GIS. Four states of particles were simulated in this paper. Partial discharge signals from each state was measured and the Ф-Q-N distribution of partial discharge signals was displayed and then the Ф-Q, the Ф-Qm, the Ф-N and the Q-N distribution were displayed. Each distribution can be quantitatively represented by statistical parameters and the parameters were used for input data of pattern recognition. As the results, it was found that the forms of each distribution were different according to the particle states. Recognition rate using neural network was about 92〔%〕 and the more input data number, the more accurate results.

Fabrication and Characterization of Portable Electronic Nose System using Gas Sensor Array and Artificial Neural Network (가스센서 어레이와 인공 신경망을 이용한 소형 전자코 시스템의 제작 및 특성)

  • 홍형기;권철한;윤동현;김승렬;이규정
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1997.04a
    • /
    • pp.99-102
    • /
    • 1997
  • An electronic nose system is an instrument designed far mimicking human olfactory system. It consists generally of gas (odor) sensor array corresponding to olfactory receptors of human nose and artificial neural network pattern recognition technique based on human biological odor sensing mechanism. Considerable attempts to develop the electronic nose system have been made far applications in the fields of floods, drinks, cosmetics, environment monitoring, etc. A portable electronic nose system has been fabricated by using oxide semiconductor gas sensor array and pattern recognition technique such as principal component analysis (PCA) and back propagation artificial neural network The sensor array consists of six thick film gas sensors whose sensing layers are Pd-doped WO$_3$ Pt-doped SnO$_2$ TiO$_2$-Sb$_2$O$_3$-Pd-doped SnO$_2$ TiO$_2$-Sb$_2$O$_{5}$-Pd-doped SnO$_2$+Pd filter layer, A1$_2$O$_3$-doped ZnO and PdCl$_2$-doped SnO$_2$. As an application the system has been used to identify CO/HC car exhausting gases and the identification has been successfully demonstrated.d.

  • PDF

The Analysis of VHF/UHF PD and 3d-PD Pattern (3d-PD 패턴과 VHF/UHF PD 신호의 고찰)

  • Lim, Jang-Seob;Park, Yong-Sik;Park, Byoung-Ha;Han, Sok-Kyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05b
    • /
    • pp.75-78
    • /
    • 2001
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

A Complex Noise Suppression Algorithm for On-line Partial Discharge Diagnosis Systems (운전중 부분방전 진단시스템을 위한 복합 잡음제거 기법)

  • Yi, Sang-Hwa;Youn, Young-Woo;Choo, Young-Bae;Kang, Dong-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.2
    • /
    • pp.342-348
    • /
    • 2009
  • This paper introduces a novel denoising algorithm for the partial-discharge(PD) signals from power apparatuses. The developed algorithm includes three kinds of specific denoising sub-algorithms. The first sub-algorithm uses the fuzzy logic which classifies the noise types in the magnitude versus phase PD pattern. This sub-algorithm is especially effective in the rejection of the noise with high and constant magnitude. The second one is the method simply removing the pulses in the phase sections below the threshold count in the count versus phase pattern. This method is effective in removing the occasional high level noise pulses. The last denoising sub-algorithm uses the grouping characteristics of PD pulses in the 3D plot of the magnitude versus phase versus cycle. This special technique can remove the periodical noise pulses with varying magnitudes, which are very difficult to be removed by other denoising methods. Each of the sub-algorithm has different characteristic and shows different quality of the noise rejection. On that account, a parameter which numerically expresses the noise possessing degree of signal, is defined and evaluated. Using the parameter and above three sub-algorithms, an adaptive complex noise rejection algorithm for the on-line PD diagnosis system is developed. Proposed algorithm shows good performances in the various real PD signals measured from the power apparatuses in the Korean plants.

GlSPD Analysis Using UHF Dual-Band Method (UHF 이중대역법을 이용한 GIS PD 분석)

  • Yi, Sang-Hwa;Choi, Jae-Gu;Kim, Kwang-Hwa
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.63-66
    • /
    • 2004
  • It is widely known that the ultra high frequency (UHF) method that detects the electromagnetic wave of the PD pulses in the gas insulated space is one of the most competitive methods for its high sensitivity. From the above point of view, this paper describes the characteristics of GIS PD signals measured with ultra wide band (UWB) GIS PD defecting system in which PD signals are defected into the dual UHF band. Thc UWB PD detection system consists of the UWB UHF coupler, the UWB low noise amplifier (LNA) and the oscilloscope. The dual bands for PD signals are 0.5-2GHz(full band) and 1-2GHz(high band). As results, it was found that the partial discharges of each defect have their own characteristic pattern and the ratio of High hand to Full band increases with gas pressure.

  • PDF

Pattern Classification of Partial Discharge Data

  • Kim Sung-Ho;Bae Geum-Dong
    • International Journal of Fuzzy Logic and Intelligent Systems
    • /
    • v.5 no.4
    • /
    • pp.347-352
    • /
    • 2005
  • PD(Partial discharges) are small electrical sparks that occur within the electric insulation of cables, transformers and windings on motors. PD analysis is a proactive diagnostic approach that uses PD measurements to evaluate the integrity of this equipment. Recently, several diagnostic algorithms for classifying the type of PD and locating the defect position have been developed. In this work, a new PD recognition system is proposed, which utilizes approximate coefficients of wavelet transform as a feature vector, furthermore, introduces bank of Elman networks to recognize the various PD phenomena. In order to verify the performance of the proposed scheme, it is applied to the simulated PD data.

Effect of Space Charge on the PD Pattern or Dielectric barrier Discharge at AC Voltage (교류전압에서 PD 패턴(또는 유전체장벽 효과)에 미치는 공간전하의 영향)

  • 황보승;이동영
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 1998.11a
    • /
    • pp.101-107
    • /
    • 1998
  • 본 논문에서는 최근 국내·외적으로 활발하게 연구되고 있는 고분자 절연재료에 있어서 공간 전하가 전기적 특성에 미치는 영향에 대한 연구로서, 기존에는 보고되지 않았던 새로운 측정시스템과 분석 방법을 제시하였다. 그리고, 이러한 측정시스템을 이용하여 교류전압 하에서 PD 발생시에 절연체 표면에 축적되는 공간전하의 직접적인 관측을 통하여 공간전하와 PD와의 연관성에 대한 규명을 실시하였다. 실험결과로부터 PD 패턴은 방전에 의해 절연체 내부보다는 표면에 축적되는 동적 공간전하와 매우 밀접한 관계를 가지고 있는 것을 알 수 있었으며, 또한 PD 발생시 공기층 전압은 이러한 동적 공간전하에 의해 지배됨을 확인할 수 있었다. 그리고, 일정전계 이상에서는 공간전하의 축적에 의한 영향으로 PD 크기와 공기층 전압은 더 이상 증가하지 않았다는 것을 확인할 수 있었다. 이러한 실험결과는 유전체장벽방전을 이용한 NOx, SOx 등의 공해물질의 분해에 있어서, 현재까지는 분해시스템에 전달되는 전력은 인가전압의 주파수와 크기에 비례하는 것으로 생각해 왔으나, 본 실험결과를 통하여 일정전계 이상에서는 전압상승에 의한 분해 효율의 향상을 기대하기 힘들다는 것을 나타낸다.

  • PDF

A New Information Data Hiding Scheme based on Pattern Information of Secret Data (비밀데이터의 패턴정보에 기반한 새로운 정보은닉 기법)

  • Kim, Ki-Jong;Shin, Sang-Ho;Yoo, Kee-Young
    • Journal of Korea Multimedia Society
    • /
    • v.15 no.4
    • /
    • pp.526-539
    • /
    • 2012
  • This paper proposes a high capacity data hiding method using high frequence secret data indexing algorithm. Many novel data hiding methods based on LSB and PVD methods were presented to enlarge hiding capacity and provide an imperceptible quality. In this paper, first, calculating data iteration frequency of the secret message and make up the high frequency data index matrix (HFDT) using high frequence data's location information. Next, HFDT uses to that data hiding process on the cover image and recovering process on the stego image. The experimental results demonstrate the efficiency of the proposed high frequency secret data indexing method. For the data hiding method, experiments are conducted for four cases: 2 pattern secret data (2PD), 4 pattern secret data (4PD), 8 pattern secret data (8PD) and higher pattern secret data (HPD). When comparing the proposed method with other data hiding methods, for the HPD case, the results show that the proposed method has a good PSNR and more capacity, and for the other case, the results show that the proposed method has a higher PSNR and larger capacity.

A Study on the partial Discharge Characteristics according to the Distribution pattern of voids within LDPE (보이드 분포 형태에 따른 LDPE의 부분 방전 특성 연구)

  • Shin, Doo-Seong;Jeon, Seung-Ik;Lee, Jun-Ho;Yun, Do-Hong;Han, Min-Koo
    • Proceedings of the KIEE Conference
    • /
    • 1995.07c
    • /
    • pp.1081-1084
    • /
    • 1995
  • Internal voids located within an insulation will arise partial discharge that causes local breakdown and even the entire insulation breakdown. For HV apparatuses, it is usual case that several voids are formed within non-uniform electric field condition rather than single void within uniform field, which can be solved analitically. The purpose of this work is to study partial discharge and breakdown characteristics of an insulation according to the distribution pattern of two disc-type voids that are located within non-uniform field. The results from numerical field analysis and experiments show that the electric field within the voids decreases as they are arranged more serially, which accordingly results in the increase of partial discharge inception field(PDIF) much higher than that of single void model. With parallel arranged voids, PDIF is almost the same as that of single void model. On the other hand, AC breakdown strength decreases as voids are arranged more serially, which is a natural result considering the reduction of effective insulation thickness. For parallel voids, this effect cannot he noticed where as they show different pattern compared with single void and serial void models in $\Phi$-Q-N analysis. Considering these results may leads us to the conclusion that, in the evaluation of insulating products through PD test, it is not sufficient to determine only PDIV or existence of PD at predetermined voltage level. We could evaluate more accurately by considering all the available data such as PDIV, PD magnitude, PD occurring phase, number of PD pulses, and etc.

  • PDF