• Title/Summary/Keyword: PD (Partial Discharge)

Search Result 501, Processing Time 0.017 seconds

Study on Multi Parameter Measurement and Analysis of Distribution High Voltage Cable Connection Part (배전용 특고압 케이블 접속재의 다변수 측정 분석 연구)

  • Song, Ki-Hong;Bae, Young-Chul;Kim, Yi-Gon
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.16 no.1
    • /
    • pp.53-60
    • /
    • 2021
  • High voltage CV cables have been widely installed underground due to their convenience and urban aesthetics. However, cable accidents have occurred frequently owing to poor construction and natural degradations. This paper proposes the method to measure the multi parameter measurement for optimum diagnostics of high voltage cable connection parts and verifies its technical usefulness. This measurement is intended to diagnose degradations of cable connection parts by using simultaneous vibration and thermography as well as partial discharge(PD). The experiment in a shielded laboratory was carried out to verify the usefulness of the multi parameter measurement. The experiment defined the degradation of the cable connection part as 12 types, and produced each degradation sample. As a result of experiment, it was possible to check the correlation of vibration signals with regard to progress in some defects. In the case of thermography, the coherence with regard to the progress of some defects was found. We figure that the proposed method would be useful also in the noise environment.