A Study on the Protective Coordination of Generator Overexcitation and Overvoltage Relay (발전기 과여자 및 과전압 계전기 보호협조에 관한 연구)

  • Park, Ji-Kyung;Kim, Kwnag-Hyun;Kim, Chul-Hwan;Lyu, Young-Sik;Yang, Jeong-Jae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.8
    • /
    • pp.1187-1194
    • /
    • 2017
  • After North American wide area black out on August 14, 2003, various studies have been conducted to find out the reason of the disaster. One of main reasons was misoperation of generator protection system. Since then, protective coordination between generator protection system and excitation system controls has been hot issue among electrical engineers. Among various generator protection relays, in this paper, we focused on generator overvoltage and overexcitation relay, which protect the over-flux condition of the generator. Thus, at first, we modeled the generator overvoltage, overexcitation relay and detailed power system including excitation system, governor and etc., based on actual field data. And then, we reviewed the protective coordination of generator overvoltage and overexcitation relay using electromagnetic transient program. In addition, we discussed the protective coordination method for redundant protection relays in both automatic voltage regulator and generator side.

A Transformer Protection Relay Based on Induced Voltages

  • Kang, Yong-Cheol;Lee, Byung-Eun
    • KIEE International Transactions on Power Engineering
    • /
    • v.3A no.2
    • /
    • pp.70-78
    • /
    • 2003
  • This paper describes a transformer protection relay based on induced voltages. The ratio of the induced voltages of the primary and secondary windings is equal to the turns ratio during normal operating conditions such as magnetic inrush, overexcitation, and steady state, but it differs from the turns ratio in the case of internal faults. For a single-phase and a three-phase Y-Y transformer, the induced voltages are estimated and the ratios are compared with the turns ratio. For three-phase Y-Δ transformers, the differences between the induced voltages are estimated to use the line currents because delta-winding currents are practically unavailable. The proposed relay is tested under various conditions such as magnetic inrush, internal winding faults, overexcitation, and different core characteristics. The results evidently indicate that the relay successfully discriminates internal faults from magnetic inrush and overexcitation. This paper concludes by implementing the relay into a TMS320C6701 digital signal processor and reports satisfactory results. The relay requires no hysteresis data and can reduce the operating time of a relay.

Protective Relaying Algorithm for Transformer Using Wavelet Transform (웨이블렛 변환을 이용한 변압기 보호계전 알고리즘)

  • 홍동석;이종범
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.2
    • /
    • pp.134-141
    • /
    • 2003
  • The power transformer is one of the very important electric facilities in power systems. Recently, current differential relay is widely used to protect such power transformer But if inrush occurs in transformer, relay can be tripped by judging like internal fault. Therefore the correct discrimination between internal winding fault, inrush and overexcitation should be performed. This paper presents a new protective relaying algorithm which discriminates inrush, internal faults and overexcitation of transformer modelled using BCTRAN and HYSDAT of EMTP. Discrimination between internal winding fault and inrush is revealed in simulation within 1/2 cycle after fault. Accordingly, it is evaluated that the proposed algorithm has better discrimination characteristics in various cases thin the current relaying for protection of transformer.

A Modified Current Differential Relay for Transformer Protection (변압기 보호용 수정 전류차동 계전방식)

  • 강용철;김은수;원성호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.2
    • /
    • pp.80-86
    • /
    • 2004
  • During magnetic inrush or over-excitation, saturation of the core in a transformer draws a large exciting current, which can cause mal-operation of a differential relay. This paper proposes a modified current differential relay for transformer protection. The relay calculates core-loss current from the induced voltage and the core-loss resistance; the relay calculates the magnetizing current from the core flux and the magnetization curve. Finally, the relay obtains the modified differential current by subtracting the core-loss and the magnetizing currents from the conventional differential current. Comparison study with the conventional differential relay with harmonic blocking is also shown. The proposed technique not only discriminates magnetic inrush and over-excitation from an internal fault, but also improves the speed of the conventional relay.

Protective Relaying Algorithm for Transformer Using Neuro-Fuzzy (뉴로-퍼지를 이용한 변압기 보호계전 알고리즘)

  • 이명윤;이종범;서재호
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.12
    • /
    • pp.722-730
    • /
    • 2003
  • Current differential relay is commonly used to protect power transformer. However, current differential relay will be tripod by judging like internal fault during inrush occurring in transformer. To resolve such problem, this paper proposes a new protective relaying algorithm using Neuro-Fuzzy Inference. A variety of transformer transition states are simulated by BCTRAN and HYSDT of EMTP. Primary phase voltage and differential current are obtained from simulation. The target data which are used in Neuro-Fuzzy algorithm are obtained from transformed primary voltage and current. Then, these are trained by Neuro-Fuzzy algorithm. The trained Neuro-Fuzzy algorithm correctly distinguishes whether internal fault occurs or not, within 1/2 cycle after fault. Accordingly, it is evaluated that the proposed algorithm has good relaying characteristics.

A New Protective Relaying Algorithm for Power Transformer Based on Three Phase Voltage and Current (전압, 전류 변화 추이를 이용한 전력용 변압기 보호계전 알고리즘)

  • Kim, Sang-Tae;Lee, Seung-Jae;Kang, Sang-Hee;Jin, Bo-Gun;Yoon, Sang-Hyun;Lee, Tae-Sung
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.4
    • /
    • pp.157-165
    • /
    • 2001
  • The two criteria to identify the disturbances of the power transformer has been reported in this paper. They have been derived through EMTP simulations of internal faults, inrush and overexcitation for the model of 154/22.9[kV], 40[MVA], Y-Y three-phase power transformer. We propose the crisp algorithm which uses two criteria. A series of test results clearly indicate that the method can identify not only an internal fault but also the other transients. The average of relay operation times is about 7.2[ms]. The proposed algorithm immunes to the transient state.

  • PDF

A Current Differential Relaying Algorithm for Power Transformers Using the Difference of a Differential Current (차전류의 차분을 이용한 변압기 보호용 전류차동 계전방식)

  • Kang, Y.C.;Kim, D.S.;Lee, B.E.;Kim, E.S.;Won, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.274-276
    • /
    • 2002
  • This paper proposes a current differential relaying algorithm for power transformers using the third difference function of a differential current. The algorithm observes the instants when the wave-shape of the differential current is changed due to the change of the magnetization inductance. If the value of the third difference is bigger than the threshold, the output of a current differential relay is blocked for a cycle. In the cases of magnetic inrush and overexcitation, the blocking signal is maintained: however, for internal faults, reset in a cycle. The test results clearly show that the algorithm successfully distinguishes internal faults from magnetizing inrush.

  • PDF

Protective Relaying Algorithm for Transformer Using Neuro-Fuzzy based on Wavelet Transform (웨이브렛 변환 기반 뉴로-펴지를 이용한 변압기 보호계전 알고리즘)

  • Lee Jong-Beom;Lee Myoung-Rhun
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.5
    • /
    • pp.242-250
    • /
    • 2005
  • This paper proposes a new protective relaying algorithm using Neuro-Fuzzy and wavelet transform. To organize advanced nuero-fuzzy algorithm, it is important to select target data reflecting various transformer transient states. These data are made of changing-rates of Dl coefficient and RSM value within half cycle after fault occurrence. Subsequently, advanced neuro-fuzzy algorithm is obtained by converging the target data. As a result of applying the advanced neuro-fuzzy algorithm, discrimination between internal fault and inrush is correctly distinguished within 1/2 after fault occurrence. Accordingly, it is evaluated that the proposed algorithm can effectively protect a transformer by correcting discrimination between winding fault and inrushing state.

A Transformer protective Relaying Algorithm Based on Increment of Flux Linkages (쇄교자속비를 이용한 변압기 보호 알고리즘)

  • Kang, Y.C.;Lee, B.E.;Jin, E.S.;Won, S.H.;Lim, U.J.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.53-55
    • /
    • 2003
  • This paper propose a transformer protective relaying algorithm based on the increment of flux linkages (RIFL) of the Primary and secondary windings. The RIFL is equal to the turn ratio for all operating conditions except an internal faults. For a single-phase transformer and three-phase Y-Y transformer, the increments of flux linkages are calculated and their ratios are compared with the turn ratio. For a three-phase Y-$\triangle$ transformer, the difference of the increments of flux linkages are calculated to use the line currents instead of the delta winding currents, which are practically unavailable. Their ratios are compared with the turn ratio. The results of various tests show that the algorithm successfully discriminates internal faults from normal operation conditions such as magnetic inrush and overexcitation. The algorithm can not only detect internal winding faults, but reduce the relay's operating time.

  • PDF

A Three-Winding Transformer Protective Relaying Algorithm Based on Flux Linkages Ratio (쇄교자속비를 이용한 3권선 변압기 보호 알고리즘)

  • Kang, Y.C.;Lee, B.E.;Jin, E.S.;Won, S.H.;Lim, U.J.
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.341-344
    • /
    • 2003
  • This paper proposes a tree-winding transformer protective relaying algorithm based on the ratio of increment of flux linkages (RIFL). The RIFL of the two windings is equal to the turns ratio for all operating conditions except an internal faults. For a single-phase transformer and three-phase transformer containing the wye-connected windings, the increments of flux linkages are calculated. for a three-phase transformer containing the delta-connected windings, the difference of the increments of flux linkages between the two phases are calculated using the line currents, because the winding currents are practically unavailable. Their ratios are compared with the turns ratio. The results of various tests show that the algorithm successfully discriminates internal faults from normal operation conditions such as magnetic inrush, overexcitation and external faults. The algorithm can not only detect internal winding faults, but reduce the operating time of a relay.

  • PDF