• 제목/요약/키워드: Outdoor Air Conditioning Energy

검색결과 146건 처리시간 0.023초

주거용 건물의 난방 방식별 열적성능 및 실내환경 특성 평가를 위한 실험적 연구 (An Experimental Study on Thermal and Environmental Characteristics of Various Heating Systems in the Residential House)

  • 이충국;조성환
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.121-128
    • /
    • 2005
  • This is about experimental comparison study between convective heating and radiation heating system to use the design criteria for residential house. Experiment was done in EC(environment chamber) under simultaneous outdoor condition for 4 kinds of heating system such as CRHP(Ceiling Radiant Heating Panel), BEHC( Bottom Electric Heating Coil Mat), EFCU( Electric Fan Coil Unit) and CEHU( Convective Electric Heating Unit). Result show that CRHP ,which is radiation heating system, can consume more 23% energy than convective heating system when it is operated by dry bulb temperature but can save 1 ${\sim}$ 10% when operated by glove temperature and 27% when operated by MRT.

  • PDF

빙축열 시스템의 제어를 위한 냉방부하 예측 (An Estimation of Cooling Load for Control of Ice Storage System)

  • 유성연;한승호;노관종;이제묘;강태석
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.205-210
    • /
    • 2005
  • Ice storage system stores cold energy using ice, which is used for cooling on next day. Ice storage system is the effective cooling system that uses cheep electric energy during a night, and also suppresses the peak load of electricity. In this study, the normalized temperature, relative humidity and specific humidity are analyzed using the weather data for past five years in order to estimate the cooling load for the control of ice storage system. The calculated cooling loads show fairly good agreement with the measured data of model hospital, especially at the outdoor design temperature of $25^{\circ}C$.

  • PDF

통신기기 냉각용 하이브리드 냉방시스템의 성능특성 (Cooling Performance of a Hybrid Refrigeration System for Telecommunication Equipment)

  • 전종욱;김용찬;최종민
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.489-494
    • /
    • 2006
  • Electronic and telecommunication industries are constantly trying to develop compact components having high power density. Therefore, a proper heat dissipation method is very important to allow reliable operation of the telecommunication equipment. In this study, a hybrid refrigeration system for a telecommunication equipment room was designed to save energy consumption and improve reliability of the compressor In addition, the performance of the hybrid refrigeration system was measured with a variation of outdoor load. The designed hybrid refrigeration system for the telecommunication equipment shelter saved the energy approximately 50%e at the mode switch temperature of $8.3^{\circ}C$.

  • PDF

태양광 에너지를 이용한 계통 독립형 이동식 스마트 쉼터 개발 (Development of a System-Independent Mobile Smart Shelter using Solar Energy)

  • 주종율;이영재;박경욱;오재철
    • 한국전자통신학회논문지
    • /
    • 제15권6호
    • /
    • pp.1061-1068
    • /
    • 2020
  • 본 논문에서는 걷기 여행길이나 계통 전원 사용이 어려운 공원, 시골, 행사장, 공사현장 등 다양한 장소에 자유롭게 설치할 수 있는 태양광 에너지 기술을 이용한 계통 독립형 이동식 스마트 쉼터를 제시한다. 제안된 스마트 쉼터는 태양광 발전과 에너지 저장장치를 갖추고 IoT 기술을 접목하여 실내외 온습도, 미세먼지, 여행객 인지를 실시간으로 수집이 가능하며. 이를 통해 폭염, 한파 상황 및 여행객 유무에 따른 최적의 에너지 운영을 수행함으로써 효율적으로 에너지 관리가 가능하며, 계통 전원 없이 최대한 장시간 대피소의 역할이 가능하다.

쿨루프 적용에 따른 업무용 건물의 내·외부 온도 저감 효과 (Reduction in Indoor and Outdoor Temperature of Office Building with Cool Roof)

  • 송봉근;김경아;박경훈
    • KIEAE Journal
    • /
    • 제16권6호
    • /
    • pp.95-101
    • /
    • 2016
  • Purpose: This study aims to identify the effect of temperature reduction by the application of cool roof coatings to Changwon City Hall in South Gyeongsang Province. The indoor and outdoor temperatures of the cool roofing building were analyzed and compared to that of an existing building with green-colored roof coated with waterproof polyurethane. Method: The surface temperatures and reflectivity of rooftops, surface temperatures of ceilings and the interior, and outdoor temperature and humidity of the two aforementioned buildings were measured from June to September in 2014. The measurements were taken every 10 min. Result: The surface temperature of the building with the cool roof was lower by a maximum of $9^{\circ}C$ with the reflectivity of the rooftop at an average of 0.55, which is higher than that of the building with green polyurethane by approximately 0.3. The temperature of the ceiling inside the building with the cool roof was about $1{\sim}2^{\circ}C$ lower than that of the ordinary building. Also, the indoor temperature of the office with cool roof coatings was about $0.5{\sim}1.0^{\circ}C$ lower than that of the office with green-colored roofing building. The results show that cool roof coatings can lower the temperature of buildings. In the next research, the reduction in consumption of energy for air conditioning will be investigated by utilizing building energy simulation tools.

덕트형 항온챔버에서 히트펌프 실외기의 성능평가 가능성에 대한 CFD (CFD on the possibility of performance evaluation of heat pump outdoor unit in duct-type constant temperature chamber)

  • 김종열
    • 융합신호처리학회논문지
    • /
    • 제22권3호
    • /
    • pp.116-121
    • /
    • 2021
  • 에너지를 절약하기 위해 고효율 히트펌프를 개발하기 위한 많은 연구가 이루어지고 있으며, 실외기 코일에 발생하는 서리가 발생하는 현상을 줄이거나 없애기 위한 연구도 동시에 이루어지고 있다. 계절과 관계없이 히트펌프의 실외기에 서리가 발생하지 않는 연구를 진행할 수 있도록 자연 상태와 동일한 조건에서 실험할 수 있는 곡선형 항온챔버를 구축하였다. 이러한 곡선형 항온챔버가 실험 장치로서 타당성을 갖추고 있는지 검증하기 위해 시뮬레이션을 하였다. CFD 조건은 곡선형 항온챔버 내에 위치한 실외기 앞의 직선형 덕트 길이를 덕트 관경의 1배, 5배, 10배, 15배로 하였다. 그 결과 덕트 관경의 10배 길이로 시뮬레이션했을 때 자연 상태와 가장 유사하다는 것을 알게 되었다.

박스형 이중외피와 커튼월의 냉방기 열적성능에 관한 비교실험 연구 (A Comparative Experimental Study on Thermal Performance of Box-typed Double Skin and Curtain Wall in Cooling Period)

  • 박창영;이건호;윤용상;최창호
    • 한국태양에너지학회 논문집
    • /
    • 제27권2호
    • /
    • pp.111-119
    • /
    • 2007
  • The annual mean temperature of South Korea has risen by $1.3^{\circ}C$ for last 100 years by urbanization and industrialization. Especially, the frequency of unusual hot weather in summer increases for a long time and the frequency of unusual cold weather in winter clearly decreases. In recently, The considerable portion of curtain wall system is appled to building skin in domestic. As related to this, the Korea Institute of Construction Technology devised the box typed double skin facade(It is occasionally called as FDFS : Functional Double Facade System) as an alternative that reflects the distinctive local climate and saves cooling energy. Two mock-ups($49m^*4.9m$) applied to single skin(curtain wall) and double skin each were monitored under the outdoor condition. Therefore, the characteristics of natural ventilation and cooling energy consumption of each window had been analyzed in real time. The results of this study are summarized as follow, Analysis of the experiment on an air conditioner: the indoor temperature of the chamber with FDFS is lower than that of the chamber with single skin facades by $3{\sim}6$ degrees(C). A temperature variation of about $1{\sim}2$ degrees between the 0.2m and 1.7m height of the mock-up occurs in FDFS, while that of about maximum 7 degrees occurs in single skin facade at noon with abundant intensity of solar accident. Also, 67 percent of energy consumption for air conditioning has been saved.

초미세입자 제거를 위한 나노세라믹 필터의 성능 평가 (Performance of Nano Ceramic Filter for the Removal of Ultra Fine Particles)

  • 김종원;안영철;이병권;정현재
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.751-756
    • /
    • 2009
  • In the perspective of saving energy in buildings, the high performance of insulation and air tightness for improving the heating and the cooling efficiency, has brought economically positive effects. However, these building energy saving technologies cause the lack of ventilation, which is the direct cause of increasing the indoor contaminants, and is also very harmful to the residents, because they spend over 90% of their time indoors. Therefore, the ventilation is important to keep the indoor environment clean and it can also save the energy consumption. In this study, a HEPA type nano ceramic filter is designed as a passive ventilation system to collect airborne particles and to supply fresh outdoor air. The double layer filter, which has $30{\mu}m$ in diameter at the conditions of 10wt% of concentration and 3kV/cm of the electric intensity, is produced by electrospinning. The filtration coating technology is confirmed in the solution with $SiO_2$ nano particles using polymer nano fibers. Also double layer filters are coated with $SiO_2$ nano particles and finally the porous construction materials are made by sintering in the electric furnace at $200{\sim}1400^{\circ}C$. The efficiency is measured 96.67% at the particle size of $0.31{\mu}m$, which is slightly lower than HEPA filter. However the efficiency is turned out to be sufficient.

  • PDF

간접식 증발냉각장치의 성능예측과 에너지절약에 관한 연구 (Study on Performance Prediction and Energy Saving of Indirect Evaporative Cooling System)

  • 유성연;김태호;김명호
    • 대한기계학회논문집B
    • /
    • 제39권9호
    • /
    • pp.743-749
    • /
    • 2015
  • 본 연구의 목적은 간접식 증발냉각 장치의 성능을 예측하고, 장치를 공기조화기의 배기열 회수에 적용하였을 경우의 에너지 절약효과를 분석하는 것이다. 플라스틱 열교환기를 사용한 간접식 증발냉각장치의 성능 상관식을 여러가지 조건에서 얻어진 실험 데이터로부터 구하였으며, 이 상관식을 이용하여 환기와 외기의 조건을 변화시켜가면서 장치의 성능변화를 예측하였다. 또한 간접식 증발냉각장치의 배기열 회수에 의한 에너지 절약효과를 우리나라 몇개 도시의 표준기상데이터를 사용하여 분석하였다. 여름철 배기열 회수를 위한 현열냉각장치의 사용율은 평균 44.3%이며 증발냉각장치의 사용율은 96.7% 이다. 증발냉각장치의 배기열 회수에 의한 에너지 절약은 현열냉각장치에 비해서 훨씬 높으며, 서울의 경우 약 3.89 배로 나타났다.

난방도일 기반 대한민국 행정구역별 기후존 구분 기준 정립에 관한 연구 (A Study on the Classification Criteria of Climatic Zones in Korean Building Code Based on Heating Degree-Days)

  • 노병일;최재완;서동현
    • 설비공학논문집
    • /
    • 제27권11호
    • /
    • pp.574-580
    • /
    • 2015
  • Climatic zone in building code is an administrative district classification reflecting regional climatic characteristics. Use of Degree-Days is a fundamental method that can be used in various building design codes, analysis of building energy performance, and establishment of minimum thermal transmittance of building envelopes. Many foreign countries, such as the USA, the EU, Australia, Italy, India, China, etc., have already adapted climatic zone classification with degree-days, precipitation or amount of water vapor based on the characteristics of their own country's climate. In Korea, however, the minimum requirements for regional thermal transmittance are classified separately for the Jungbu area, Nambu area and Jeju Island with no definite criterion. In this study, degree-days of 255 Korean cities were used for climatic zone classification. Outdoor dry-bulb temperature data from the Korea Meteorological Administration for 1981~2010 was used to calculate degree-days. ArcGIS and the calculated degree-days were utilized to analyze and visualize climatic zone classification. As a result, depending on the distribution and distinctive differences in degree-days, four climatic zones were derived : 1) Central area, 2) Mountain area of Gyeonggi and Gangwon provinces, 3) Southern area, and 4) Jeju Island. The climatic zones were suggested per administrative district for easy public understanding and utilization.