• 제목/요약/키워드: Outdoor/mixed plenum pressure

검색결과 1건 처리시간 0.016초

변풍량 공조시스템의 요구외기량 확보를 위한 제어방식 (Control Methods of the VAV Air Handling Unit for the Required Outdoor Air Demand)

  • 한도영;주영덕;김진;이준호
    • 설비공학논문집
    • /
    • 제15권3호
    • /
    • pp.203-209
    • /
    • 2003
  • Control algorithms of an air handling unit by using the mixing box plenum pressures were developed and verified by experiments. Control algorithms developed for this study were the setpoint algorithms for the outdoor damper position, the outdoor/fixed plenum pressure, and the return/exhaust plenum pressure. The outdoor/fixed plenum pressure setpoint was used to control the bypass damper position, and the return/exhaust plenum pressure setpoint was used to control the return fan speed. Experimental results showed the good control of the required outdoor air demand. Therefore, setpoint algorithms developed for this study may effectively be applied for the control of the VAV air handling unit.