• Title/Summary/Keyword: Optimal Relay Setting

Search Result 13, Processing Time 0.031 seconds

Optimal Setting of Overcurrent Relay in Distribution Systems Using Adaptive Evolutionary Algorithm (적응진화연산을 이용한 배전계통의 과전류계전기 최적 정정치 결정)

  • Jeong, Hee-Myung;Lee, Hwa-Seok;Park, June-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.9
    • /
    • pp.1521-1526
    • /
    • 2007
  • This paper presents the application of Adaptive Evolutionary Algorithm (AEA) to search an optimal setting of overcurrent relay coordination to protect ring distribution systems. The AEA takes the merits of both a genetic algorithm (GA) and an evolution strategy (ES) in an adaptive manner to use the global search capability of GA and the local search capability of ES. The overcurrent relay settings and coordination requirements are formulated into a set of constraint equations and an objective function is developed to manage the overcurrent relay settings by the Time Coordination Method. The domain of overcurrent relays coordination for the ring-fed distribution systems is a non-linear system with a lot of local optimum points and a highly constrained optimization problem. Thus conventional methods fail in searching for the global optimum. AEA is employed to search for the optimum relay settings with maximum satisfaction of coordination constraints. The simulation results show that the proposed method can optimize the overcurrent relay settings, reduce relay mis-coordinated operations, and find better optimal overcurrent relay settings than the present available methods.

A Study on the Optimal Setting Method of Directional Overcurrent Relay Considering Fault Ride Through of Distributed Generation (분산전원의 Fault Ride Through를 고려한 방향성 과전류 계전기 최적 정정법에 관한 연구)

  • Song, Jin-Sol;Cho, Gyu-Jung;Kim, Ji-Soo;Shin, Jea-Yun;Kim, Dong-Hyun;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.8
    • /
    • pp.1002-1008
    • /
    • 2018
  • Fault Ride Through(FRT) requirement prevents disconnections of distributed generations during the specific time on disturbance condition for system stability. However, since there is a limitation to the FRT capability of distributed generation, and the protection system needs to clear the fault quickly before the distributed generation is disconnected. Therefore, this paper proposes a novel optimal setting method of directional overcurrent relay considering FRT of distributed generation. The proposed method reduces the probability of disconnections of the distributed generation in disturbance without additional equipment considering the FRT capability of the distributed generation by calculating the optimal relay setting through the Genetic Algorithm(GA).

Digital Adaptive Distance Relay for Transmission Line Protection (송전선로 보호용 디지털 지능형 거리계전기)

  • Jeong, Chang-Ho;Kim, Jin-O
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.9
    • /
    • pp.411-416
    • /
    • 2001
  • Distance relay is the most widely used in transmission line protection because it is applicable not only as main protection but also as back-up protection. However, the protection range of the distance relay is always fixed in the unchangeable operating range while the power system varies, and therefore the distance relay is the device that is the highly influenced by the power system changes. In this regard, this paper describes an approach to minimize the mal-operation of the distance relay due to the power system changes through changing protection range of the distance relay into optimal condition in response to the load variation and power system condition. Also mal-function of the distance repay in case of high resistance ground faults could be minimized through modeling the protection range into quadratic function.

  • PDF

An Experimental Study on Operation Setting Optimization of Circuit Breaker for Improving Safety on DC Railroad Feeder System (직류철도 급전계통의 안전성 향상을 위한 차단기 동작 최적 설정의 실험적 고찰)

  • Lee, Jae-Bong;Jung, No-Geon;Kim, Jae-Moon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.3
    • /
    • pp.526-531
    • /
    • 2016
  • This paper presents an experimental study on the optimal settings for the selected DC fault relay (50F) to improve the operating performance for the high-speed circuit breaker on DC feeding system which ensure safety within rolling stock maintenance depot. In this study, current supplied to overhead contact wire was calculated on 1 ms interval to analyze the correction values of DC fault selective relay for the operation of current supply cutout. Particularly, standards for the accurate detection of accidents between an electric railway vehicle and the electric power facilities are shown by investigating the optimal correction values for detection of fault current, and the results indicated that it takes about 213 ms for the DC fault selective relay(50F) to fully open. In the future, the correction values of DC fault selective relay suggested in this paper will be used as the reference values of protective relay for the safe operation of DC electric railroad system such as urban railway.

Optimal Coordination of Overcurrent Relays in the Presence of Distributed Generation Using an Adaptive Method

  • Mohammadi, Reza;Farrokhifar, Meysam;Abyaneh, Hossein Askarian;Khoob, Ehsan
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.6
    • /
    • pp.1590-1599
    • /
    • 2016
  • The installation of distributed generation (DG) in the electrical networks has numerous advantages. However, connecting and disconnecting of DGs (CADD) leads to some problems in coordination of protection devices due to the changes in the short circuit levels in the different points of network. In this paper, an adaptive method is proposed based on available setting groups (SG) of relays. Since the number of available SG is less than possible CADD states, a classifying index (CI) is defined to categorize the several states in restricted setting groups. Genetic algorithm (GA) with a suitable objective function (OF) is used as an optimization method for the classification. After grouping, a modified coordination method is applied to achieve optimal coordination for each group. The efficiency of the proposed technique is demonstrated by simulation results.

Gray Wolf Optimizer for the Optimal Coordination of Directional Overcurrent Relay

  • Kim, Chang-Hwan;Khurshaid, Tahir;Wadood, Abdul;Farkoush, Saeid Gholami;Rhee, Sang-Bong
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.3
    • /
    • pp.1043-1051
    • /
    • 2018
  • The coordination of directional overcurrent relay (DOCR) is employed in this work, considering gray wolf optimizer (GWO), a recently designed optimizer that employs the hunting and leadership attitude of gray wolves for searching a global optimum. In power system protection coordination problem, the objective function to be optimized is the sum of operating time of all the main relays. The coordination of directional overcurrent relays is formulated as a linear programming problem. The proposed optimization technique aims to minimize the time dial settings (TDS) of the relays. The calculation of the Time Dial Setting (TDS) setting of the relays is the core of the coordination study. In this article two case studies of IEEE 6-bus system and IEEE 30-bus system are utilized to see the efficiency of this algorithm and the results had been compared with the other algorithms available in the reference and it was observed that the proposed scheme is quite competent for dealing with such problems. From analyzing the obtained results, it has been found that the GWO approach provides the most globally optimum solution at a faster convergence speed. GWO has achieved a lot of relaxation due to its easy implementation, modesty and robustness. MATLAB computer programming has been applied to see the effectiveness of this algorithm.

Resource Allocation Algorithm Based on Simultaneous Wireless Information and Power Transfer for OFDM Relay Networks

  • Xie, Zhenwei;Zhu, Qi;Zhao, Su
    • KSII Transactions on Internet and Information Systems (TIIS)
    • /
    • v.11 no.12
    • /
    • pp.5943-5962
    • /
    • 2017
  • A resource allocation algorithm based on simultaneous wireless information and power transfer (SWIPT) to maximize the system throughput is proposed in orthogonal frequency division multiplexing (OFDM) relay networks. The algorithm formulates the problem under the peak power constraints of the source and each subcarrier (SC), and the energy causality constraint of the relay. With the given SC allocation of the source, we give and prove the optimal propositions of the formulated problem. Then, the formulated problem could be decomposed into two separate throughput maximization sub-problems by setting the total power to transfer energy. Finally, several SC allocation schemes are proposed, which are energy priority scheme, information priority scheme, balanced allocation scheme and exhaustive scheme. The simulation results reveal that the energy priority scheme can significantly reduce computational complexity and achieve approximate performance with the exhaustive scheme.

A Study on Adaptive Distance Protection of Double-circuit Line with Mutual Impedance and Fault Resistance (2회선 송전선로에서 상호임피던스와 고장저항을 고려한 거리계전기의 동작 특성 연구)

  • 이원석;정창호;김진오
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.4
    • /
    • pp.221-226
    • /
    • 2004
  • Power system has recently used Double-circuit Line and Multi-circuit Line in the industrial development. This has an advantage of system stability and reliability, but the complexity of the system has a disadvantage that makes it difficult to protect the power line. Double-circuit Line has two operation conditions in the Single-circuit operation and Double-circuit operation, so it has mutual impedance. To make it possible for the remaining single-line to operate independently while there is a fault with first line or when maintenance is needed, a trip region for the single-circuit operation should be set in order to set the relay trip region. An optimal trip region for each operation, a different operational conditions for the relay setting should be calculated. In this paper, trip regions of each operation condition have been compared by considering mutual impedance and fault resistance that led to the calculation of fault impedance. Also, as we know that one of the advantages in the distance relay is the back-up protection, we calculated the trip region(Zone-2) in consideration of the mutual impedance.

A Study on Adaptive Distance Protection of Double-circuit Line with Mutual Impedance and Fault Resistance (2회선 송전선로에서 상호임피던스와 고장저항을 고려한 거리계전기의 동작 특성 연구)

  • 이원석;정창호;김진오
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.4
    • /
    • pp.221-221
    • /
    • 2004
  • Power system has recently used Double-circuit Line and Multi-circuit Line in the industrial development. This has an advantage of system stability and reliability, but the complexity of the system has a disadvantage that makes it difficult to protect the power line. Double-circuit Line has two operation conditions in the Single-circuit operation and Double-circuit operation, so it has mutual impedance. To make it possible for the remaining single-line to operate independently while there is a fault with first line or when maintenance is needed, a trip region for the single-circuit operation should be set in order to set the relay trip region. An optimal trip region for each operation, a different operational conditions for the relay setting should be calculated. In this paper, trip regions of each operation condition have been compared by considering mutual impedance and fault resistance that led to the calculation of fault impedance. Also, as we know that one of the advantages in the distance relay is the back-up protection, we calculated the trip region(Zone-2) in consideration of the mutual impedance.

Protectability Evaluation of Distance Relay based on a Probabilistic Method for Transmission Network (오차확률 기반 송전계통 보호계전기 보호도 평가방법 연구)

  • Zhang, Wen-Hao;Choi, Myeon-Song;Lee, Seung-Jae
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.286_287
    • /
    • 2009
  • In this paper, the protectability of distance relay is furtherly researched. Based on the probabilistic modeling of the measurement errors, the protectability of three zones is presented in detail by considering their different protection aims denoted by sensitivity and selectivity. The optimal setting for the each zone can be obtained to provide a reference for the practical application.

  • PDF