• 제목/요약/키워드: Open Loop Geothermal Heat Pump

검색결과 11건 처리시간 0.026초

지하수 수위가 개방형 지열시스템 성능에 미치는 영향에 관한 연구 (A Study of the Influence of Groundwater Level on the System Performance of Open Loop Geothermal System)

  • 김진상;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제9권3호
    • /
    • pp.1-10
    • /
    • 2013
  • Open loop geothermal heat pumps have great potential where the groundwater resources are sufficient. Performance of open loop geothermal heat pump systems is considered higher than that of ground source heat pumps. Head and power calculation of submersible pumps, heat pump units, and piping are numerically based on regression data. Results shows that the system performance drops as the water level drops, and the lowest flow rates generally achieve the highest system COPs. The highest achievable cooling system COPs become 6.34, 6.12, and 5.95 as the groundwater levels are 5m, 15m, and 25m. The highest heating system COPs also become 4.59, 4.37, and 4.20. Groundwater level and submersible pump selection greatly influence the system performance of open loop geothermal heat pumps. It needs to be analysed during the design process of open loop geothermal heat pump system, possibly with analysis tools that include wide range of pump product data.

복수정을 이용한 개방형 지열 시스템의 초기투자비 회수기간 분석 (Analysis of the Initial Cost Payback Period on the Open-loop Geothermal System Using Two Wells)

  • 조정흠;남유진
    • 설비공학논문집
    • /
    • 제29권3호
    • /
    • pp.119-126
    • /
    • 2017
  • Recently, ground source heat pump systems are being used in buildings for cooling and heating to reduce greenhouse gas and save energy. However, ground source heat pump systems mainly use the vertical closed-loop geothermal system design rather than the open-loop geothermal system design. This is due to a lack of knowledge and few research feasibility studies. In this research, a dynamic thermal analysis numerical simulation based on a standard house model was conducted for an open-loop geothermal system. Based on heating load analysis results, the life cycle costs of a standard house using an open two-well geothermal system were analyzed and compared with a vertical closed-loop geothermal system, and a diesel boiler. As a result, it was found that using an open two-well geothermal system shows economic return on investment after three years.

밀폐형과 개방형이 결합된 복합지열시스템의 지중열교환기 성능 분석 (Performance Analysis of Ground Heat Exchanger in Combined Well and Open-Closed Loops Geothermal (CWG) System)

  • 박영윤;송재용;이근춘;김기준;목종구;박유철
    • 한국지하수토양환경학회지:지하수토양환경
    • /
    • 제22권5호
    • /
    • pp.23-29
    • /
    • 2017
  • This study was conducted to evaluate performance of geothermal heat exchanger (GHE) in the combined well and open-closed loops geothermal (CWG) systems. The CWG systems were designed to combine open loop geothermal heat pumps and closed loop geothermal heat pumps for high energy efficiency. GHE of the CWG systems could be installed at pumping wells for agricultural usage. To get optimal heat exchange capacity of GHE of the CWG systems, 4 GHEs with various materials and apertures were tested at laboratory scale. Polyethylene (PE) and stainless steel (STS) were selected as GHE materials. The maximum heat exchange capacity of GHEs were estimated to be in the range of 33.0~104 kcal/min. The heat exchange capacity of STS GHEs was 2.4~3.2 times higher than that of PE GHE. The optimal cross section area of GHE and flow rate of circulating water of GHE were estimated to be $2,500mm^2$ and 113 L/min, respectively. For more complicated GHE of the CWG systems, it is necessary to evaluate GHEs at various scales.

토조 및 수치모형을 이용한 개방형 지중 열교환 시스템 모의 (Simulation of Open-Loop Borehole Heat Exchanger System using Sand Tank Experiment and Numerical Model)

  • 이성순;배광옥;이강근
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2007년도 추계학술대회 논문집
    • /
    • pp.489-492
    • /
    • 2007
  • Understanding the thermohydraulic processes in the aquifer is necessary for a proper design of the aquifer thermal energy utilization system under given conditions. Experimental and numerical test were accomplished to evaluate the relationship between the geothermal heat exchanger operation and hydrogeological conditions in the open-loop geothermal system. Sand tank experiments were designed to investigate the open-loop geothermal system. Water injection and extract ion system as open-loop borehole heat exchanger was applied to observe the temperature changes in time at injection well, extraction well and ambient groundwater. The thermohydraulic transfer for heat storage was simulated using FEFLOW for two cases of extraction and injection phase operation in sand tank model. As one case, the movement of the thermal plume was simulated with variable locations of injection and extraction well. As another case, the simulation was performed with fixed location of injection and extraction well. The simulation and experimental results showed that the temperature distribution depends highly on the injected water temperature and the length of injection time and the groundwater flow and pumping rate sensitively affect the heat transfer.

  • PDF

지반 투수계수와 양수량 조건이 복수정 지열 히트펌프 시스템의 성능에 미치는 영향 (The Effect of Soil Permeability and Pumping Rate on Performance of Two-well Geothermal Heat Pump System)

  • 조정흠;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제11권4호
    • /
    • pp.28-34
    • /
    • 2015
  • The groundwater heat pump (GWHP) systems have great potential for heating-cooling system which use annual constant groundwater temperature for heat source. Generally, the performance of GWHP system significantly depends on the geological and hydraulic properties such as hydraulic conductivity, thermal conductivity, soil condition so on. Therefore, in order to use GWHP systems efficiently, it is necessary to analyze the effect of design factors on the system performance. However, there are a few researches on the optimum design method for the open-loop geothermal system. In this research, the design factor in the open-loop geothermal system was analyzed quantitatively for the optimal design method by using numerical simulation. As a result, it was found that the temperature change of heat source depends on the design factor.

수치 시뮬레이션을 이용한 복수정(Two-Well) 개방형 지열 시스템의 열원수 온도 변화 검토 (A Study on the Characteristics of Heat Source Temperature for Two-Well Geothermal System Using Numerical Simulation)

  • 조정흠;남유진
    • 설비공학논문집
    • /
    • 제27권4호
    • /
    • pp.207-212
    • /
    • 2015
  • The use of groundwater and ground_heat is one of the ways to use natural and renewable energy, and it has been considered as a technology to reduce greenhouse gas emissions and increase energy-saving. There are a few researches on the optimum design for the open-loop geothermal system. In this study, to develop the optimal design method numerical simulation of the open-loop geothermal system with two-wells was performed by a groundwater and heat transfer model. In this paper, a study was performed to analyze the system performance according to well distance and pumping flow rate. In the result, average heat exchange rate and heat source temperature were calculated and it was found that they were dependent on the pumping rate.

관정간 도수통로를 설치한 개방형 지열 시스템의 냉방성능 실험 (Performance Analysis for Open-loop Geothermal System with Spill-way technology by Real-scale Experiment)

  • 김홍교;배상무;남유진;전운;오종현;이병호
    • 설비공학논문집
    • /
    • 제30권4호
    • /
    • pp.186-194
    • /
    • 2018
  • A ground-source heat pump system (GSHP) is more energy efficient than other heat-source systems because it uses annual constant underground and water temperatures. Especially, two-well geothermal systems using groundwater as the heat source can achieve higher performance than closed-loop geothermal systems. However, performance of two-well geothermal systems is decreased by occurring overflow according to scale during long-term operations. Therefore, this study presents a two-well pairing geothermal system that controls the groundwater level of a diffusion well. In addition, a two-well pairing geothermal system and an SCW geothermal system were installed, and a comparative analysis of cooling performance depending on system operation under the same load conditions was conducted. The result was that the average heat pump coefficient of performance (COP) of the two-well pairing system was 6.5, and the entire system COP was 4.3.

개방형 지열 히트펌프 시스템의 운전 특성 (Operation Characteristics of Open Type Geothermal Heat Pump)

  • 임효재;공형진;송윤석;박성구
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.701-706
    • /
    • 2006
  • Groundwater heat pump systems are the oldest of the ground-souce systems and it has various type. Standing column well type are must be located in hard rock geology site and produce sufficient water for the conventional open loop system. These system are indirect type(the building circulating loop and ground water are intercept). Existence of the exchanger the foundation protect water quality to use of open loop. The design of open loop system are concern on the power requirements. An experimental study was analysis the extremely heating operation COP of ground water heat pump system. Operation efficiency of the 50RT systems shows that, COP $2.9{\sim}5.0$ in heating operation. And generally it shows 3.4.

  • PDF

개방형 지열 시스템 설계법 개발을 위한 관정 주위 지중 온도 환경 검토 (Study on the Underground Thermal Environment around Wells for a Design Method of Open-Loop Geothermal System)

  • 배상무;김홍교;김현우;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제13권1호
    • /
    • pp.14-20
    • /
    • 2017
  • Groundwater heat pump (GWHP) system can achieve higher performance of the system by utilizing heat source of the annual constant groundwater temperature. The performance of GWHP system depends on the ground thermal environment such as groundwater temperature, groundwater flow rate and hydraulic conductivity. In this study, the geothermal environment was analyzed by using numerical simulation for develop the two-well geothermal system. As the result, this paper shows the change of the groundwater level and underground temperature around wells according to the conditions of flow rate and hydraulic conductivity.

모니터링 및 시뮬레이션을 통한 SCW형 지열 시스템의 성능인자 분석에 관한 연구 (Study on the performance analysis of SCW geothermal system by simulation and monitoring)

  • 이상준;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제9권2호
    • /
    • pp.8-15
    • /
    • 2013
  • Recently, an interest in the use of renewable energy has been growing up due to the rise of raw material price, international oil price and depletion of fossil energy. Ground source heat pump system has a high efficiency by using the constant temperature of underground and various types of the systems have been installed and utilized in the building. there are few studies on the system performance factors in the SCW system. Furthermore, even though the performance of the system depends on the temperature of heat source, the research on their relationship is rare. In this research, in order to analyze the performance factor for the open-loop system the monitoring of the real building with the standing column well systems and the simulation with building model were conducted.