• Title/Summary/Keyword: On-air

Search Result 29,041, Processing Time 0.062 seconds

A Study on the Indoor Air Pollution Levels in the Classrooms at Public Schools in Suwon (수원지역 초.중.고등학교 교실의 실내 공기오염도에 관한 연구)

  • 신은상;김진우
    • Journal of environmental and Sanitary engineering
    • /
    • v.17 no.1
    • /
    • pp.20-27
    • /
    • 2002
  • This study has researched the indoor air Pollution in the school classrooms. It focused on the school classrooms in which the students take part in many loaming activities for a long time, not focused on the offices or underground facilities that have occupied the interest so far. First, I investigated the origination sources of indoor air pollution which influences on our health, and researched the data on the consequences of it on the human body. Second, I measured the indoor air Pollution level of the classrooms in which the students take part in activities. I selected CO, $CO_2,{\;}SO_2,{\;}NO_2$and $PM_{10}$ as the research items. Each two schools were chosen in the elementary schools, middle schools and high schools as the ones for measurement. And I distinguished the boys' schools from the girls' schools in the middle and high schools. CO, $SO_2{\;}and{\;}NO_2$were comparatively low comparing with the recommendation of the Ministry of Environment. But, $CO_2{\;}and{\;}PM_{10}$ exceeded the standard concentration in most schools and there was a difference between boys'classrooms and girls'classrooms about them. Also, it was different by the number of members a classrooms. Third, I made a questionnaire on the on the indoor air pollution. The questionnaire showed that many students feel the indoor air pollution directly and they are under the influence of it.

A Study on the Calculation of Ventilation Rate for the Improvement of Indoor Air Quality on the Barracks (군 내무실의 실내공기질 개선을 위한 환기량 산정에 관한 연구)

  • Choi Jeong-Min;Yu Jin-Sang;Jeong Young-Il
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.11
    • /
    • pp.1043-1049
    • /
    • 2005
  • The purpose of this study is to improve indoor air quality of the barracks which have been changed from floor-type living barracks to bed-type living barracks since 2003. Therefore, the ventilation rates of newly constructed two type barracks were simulated with the various building materials including VOCs and HCHO components. And indoor air quality of two type living barracks was measured by the field experiments. With these steps, the measures for upgrading indoor air quality depending on building material types and ventilation rate are suggested.

A Theoretical Evaluation of the Effect of Refrigerant Charge on the Performance of Vapor-Compression Air-Conditioning System (증기압축식 에어컨의 냉매 충전량에 따른 성능 예측)

  • 이경중;방광현
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.5
    • /
    • pp.486-493
    • /
    • 2000
  • A theoretical model for the transient performance of vapor-compression air-conditioning system has been developed to evaluate the influence of the refrigerant charge on the system performance. A set of mass and energy equations for the simulation of the heat exchangers and the capillary tube and a polytropic compression model for the compressor are used. The present model successfully predicts the transient behavior of the vapor-compression air-conditioner from the startup. As the refrigerant charge is increased, both the evaporating and condensing pressures increase gradually, and the cooling rate and the COP show a maximum in the range of 0.75-0.8 kg of refrigerant charge. This amount of refrigerant mass is determined to be the optimum charge of the model system. Also, the effect of outdoor air temperature on the optimum refrigerant charge is discussed.

  • PDF

An Experimental Study on Sealing Improvements of Non-Contact Type Seal for Oil Mist Lubrication

  • Na, Byung-Chul;Chun, Keyoung-Jin;Han, Dong-Chul
    • KSTLE International Journal
    • /
    • v.3 no.2
    • /
    • pp.79-83
    • /
    • 2002
  • Sealing an oil-air mixture plays important roles to have an enhanced lubrication for high speed spindle. High speed spindle requires non-contact type of sealing mechanism. Current work emphases on the investigation of the air jet effect on the protective collar type labyrinth seal. To improve the sealing capability of conventional labyrinth seal, air jet was injected against through the leakage flow, It has a combined geometry of a protective collar type and an air jet type. Both of a numerical analysis by CFD (Computational Fluid Dynamics) and experimental measurements are carried out to verify sealing improvement The sealing effects of the leakage clearance and the air jet magnitude are studied in various parameters. The results of pressure drop in the experiment match reasonably to those of the simulation by introducing a flow coefficient Effect of sealing improvement is explained as decreasing of leakage clearance by air jetting. Thus, sealing effect is improved by amount of air jetting even though clearance becomes larger.

The Air Jet Effect of Sealing Performance Improvement on Labyrinth Seal (공기분사가 라비린스 시일의 성능개선에 미치는 영향)

  • 나병철;전경진;한동철
    • Tribology and Lubricants
    • /
    • v.12 no.4
    • /
    • pp.35-42
    • /
    • 1996
  • The labyrinth seal is one of the widely used non-contact type mechanical seal. Current work was emphasized on the investigation of the air jet effect on the labyrinth seal. To improve the sealing capability of conventional labyrinth seal, air jet was injected against through the leakage flow. In this study, both of the numerical analysis by CFD (Computational Fluid Dynamics) and the experimental measurement were carried out. Both of the turbulence aad the compressible flow model were introduced in CFD analysis. The sealing effect of the leakage clearance and the air jet magnitude were studied in the experiment. The reason of the enhanced sealing was explained as a reduction of effective clearance by jetting air. As a result, the air jet could reduce the effective clearance with a wide range of leakage clearance.

The Effects of the Refrigerant Charge on the Performance of an Air Conditioner with Capillary Tube Expansions (냉매충전량이 모세관 팽창장치를 가진 공기조화기의 성능에 미치는 영향)

  • 최은수;김종배
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.5
    • /
    • pp.359-364
    • /
    • 2002
  • A popular type of residential air conditioner is the split system which has two separate units: indoor and outdoor units During field installation of the split system, the potential exists for not setting the charge exactly to the manufacturer´s specifications. The objective of this study is to investigate the effects of the refrigerant charge on the performance of the air conditioner. An air conditioner with capillary tube expansions was tested for various refrigerant charges. The results indicated that the more charge resulted in the more flowrate of the refrigerant. The flowrate of the refrigerant was one of the most important factors to understand the e(sects of the charge on the performance of the air conditioner with capillary tube expansions. Under-charge results in wide region of superheated vapor of the refrigerant in the evaporator, while over-charge results in high temperature of the liquid refrigerant in the evaporator.

Effect of Louvered Positions on Air-Side Heat Transfer in Louvered Fin Heat Exchangers (루우버 위치(位置)가 루우버핀 열교환기(熱交換器)의 공기측열전달(空氣側熱傳達)에 미치는 영향(影響))

  • Kim, S.J.;Chung, T.H.;Kwon, S.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.2 no.2
    • /
    • pp.99-104
    • /
    • 1990
  • A Study has been conducted experimentally on heat transfer characteristics of louvered fin heat exchangers with various louvered positions in air. The experimental results are as follows; 1. Mean heat transfer coefficient is increased with increasing air velocity and decreasing temperature difference. The maximum value of heat transfer coefficient shows at 10㎜ backward louvered fins. 2. Pressure drop is increased with increasing air velocity and apparently depended on the louvered positions at V>10m/sec. 3. $\bar{h}/{\Delta}P$ is decreased with increasing air velocity and its maximum value shows at 10mm forward louvered fins and its minimum value shows at plate fins.

  • PDF

Probabilistic Model for Air Traffic Controller Sequencing Strategy (항공교통관제사의 항공기 합류순서결정에 대한 확률적 예측모형 개발)

  • Kim, Minji;Hong, Sungkwon;Lee, Keumjin
    • Journal of the Korean Society for Aviation and Aeronautics
    • /
    • v.22 no.3
    • /
    • pp.8-14
    • /
    • 2014
  • Arrival management is a tool which provides efficient flow of traffic and reduces ATC workload by determining aircraft's sequence and schedules while they are in cruise phase. As a decision support tool, arrival management should advise on air traffic control service based on the understanding of human factor of its user, air traffic controller. This paper proposed a prediction model for air traffic controller sequencing strategy by analyzing the historical trajectory data. Statistical analysis is used to find how air traffic controller decides the sequence of aircraft based on the speed difference and the airspace entering time difference of aircraft. Logistic regression was applied for the proposed model and its performance was demonstrated through the comparison of the real operational data.

Cooling Simulation for Fixed-Bed of Rough Rice (벼 퇴적층 냉각 시뮬레이션)

  • 김동철;김의웅;금동혁
    • Journal of Biosystems Engineering
    • /
    • v.24 no.1
    • /
    • pp.31-40
    • /
    • 1999
  • The objective of this study were to develop a cooling simulation model for fixed-bed of rough rice and to analyze the factors affecting cooling time of rough rice. A computer simulation model based on equilibrium conditions between grain and air was developed to predict temperature and moisture content changes during cooling of rough rice. the result of t-test showed that there were no significant differences between predicted and measured temperature changes on significance model agreed well with measured values. This cooling simulation model was applied to analyze the effect of some factors, such as air flow rate, cooling air temperature and humidity, initial grain temperature and moisture content, and bed depth, on cooling time of rough rice. Cooling rate increased with increase of air flow rate and bed depth whereas it decreased with increase of cooling air temperature and humidity and initial grain temperature. Among these factors, the most important factor was air flow rate. Specific air flow rate of 0.35㎥/min㎥ was required for cooling rough rice in 24 hours.

  • PDF

The Effect of Non-condensable Gas on Direct Contact Condensation of Steam/Air Mixture

  • Lee, Hanchoon;Kim, Moohwan;Park, Suki
    • Nuclear Engineering and Technology
    • /
    • v.33 no.6
    • /
    • pp.585-595
    • /
    • 2001
  • A series of experiments have been carried out to investigate the effects of non-condensable gas on the direct contact film condensation of vapor mixture under an adiabatic wall condition. The average heat transfer coefficient of the direct contact condensation was obtained at the atmospheric pressure with four main parameters ; air-mass fraction, mixture velocity, film Reynolds number, and the degree of water film subcooling having an influence on the condensation heat transfer coefficient. With the analysis of 88 experiments, a correlation of the average Nusselt number for direct contact film condensation of steam/air mixture at an adiabatic vertical wall was proposed as functions of film Reynolds number, mixture Reynolds number, air mass fraction, and Jacob number. The average heat transfer coefficient for steam/air mixture condensation decreased significantly while air mass fraction increased. The average heat transfer coefficients also decreased as the Jacob number increased, and were scarcely affected by the film Reynolds number below a mixture Reynolds number of about 245,000.

  • PDF