• 제목/요약/키워드: Oil flow electrification

검색결과 18건 처리시간 0.019초

열화된 광유와 식물성절연유에서 온도, 벤조트리아졸의 유동대전 영향 (Influence of Temperature and Benzotriazole on the Flow Electrification by aging Mineral, Vegetable Oil)

  • 최순호;정중일;허창수
    • 전기학회논문지
    • /
    • 제60권2호
    • /
    • pp.338-343
    • /
    • 2011
  • In this paper, the FT-IR, conductivity and flow electrification phenomena of Vegetable oils were discussed. Vegetable oil has high flash point and eco-friendly properties compared to conventional mineral oil. Accelerated aging transformer oil samples produced in the oven at 140[$^{\circ}C$] for 500 hours, 1000 hours, 1500 hours, 2000 hours. Serial device to measure the flow electrification phenomena was designed and fabricated. Pico ammeter and the Labview data measurements were utilized. The effects of Temperature and antistatic agent on fluid flow electrification were investigated. Both Mineral and vegetable oil showed similar trends for temperature change. The polarity reversal occurred in mineral oil with antistatic agent above 10 ~ 30[ppm] and in vegetable oil with antistatic agent above 5[ppm].

Research on the Relation between Transformer Oil Flow Electrification and Electrostatic Current

  • Fu, Qiang;Wang, Rui;Zou, Pinguo;Li, Zhao;Yang, Yang;Xie, Xuejun
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권2호
    • /
    • pp.610-615
    • /
    • 2015
  • In order to study and obtain the mathematical relation between the electrification degree of transformer oil flow and the electrostatic current, a small amount of data about the electrification degree of oil flow and the corresponding electrostatic current is studied by linear regression method and grey model method. The results show that the linear correlation between the electrification degree and the electrostatic current was not good, and the relation between the electrification degree of oil flow and electrostatic current (i) could be expressed as ${\rho}(0)=0.2049\;i^{(0)}+169.4419$ according to grey model GM (0, 2) when the electrification degree of oil flow is represented by the charge number generated from transformer oil per unit volume, namely the charge density (${\rho}$).

친환경 식물성절연유의 유동대전현상 연구 (Research of Flow Electrification Phenomena of the used Environment-Friendly Vegetable Insulating Oils)

  • 최순호;허창수
    • 전기학회논문지
    • /
    • 제61권4호
    • /
    • pp.580-584
    • /
    • 2012
  • The insulating oils perform a cooling and insulation action in electric power transformer. The mineral oil has immanent fire dangerousness and environmental contamination problem. Vegetable insulating oil has higher ignition point, flash point and more excellent biodegradability than conventional mineral oil. In a real oil-filled transformers, some of the power is dissipated in the form of heat. And transformer require the heat to be removed from the winding and insulator by forced convection of the insulating oil. The flow electrification occurs when insulating oil was forced to be circulated. In this paper, influence of temperature, velocity of flow, and insulating pipe and diameter on streaming electrification of vegetable insulating oil was investigated using forced circulation apparatus. Temperature effects were most significant, and it showed a peak in the temperature $30^{\circ}C$ to $35^{\circ}C$ at insulating and copper pipe. The change of flow electrification according to area variety could be checked by change of diameter.

식물성 절연유의 유속과 BTA에 따른 유동대전 현상 연구 (Research of Flow Velocity and BTA According to the Streaming Electrification of Vegetable Insulating Oils)

  • 최순호;방정주;허창수
    • 한국전기전자재료학회논문지
    • /
    • 제25권10호
    • /
    • pp.791-797
    • /
    • 2012
  • Mineral insulating oils are an important insulating materials in oil-filled transformer. However, the mineral oil is the cause of the environmental problem. The vegetable oils are substitutes for mineral oil because of its biodegradability characteristic. As large size and high rating of the transformer increases, the losses increase at a faster rate. So insulating oil is forced circulation in the oil-filled transformer by using oil pumps. The flow electrification occurs when insulating oil was forced to be circulated. To check the flow electrification, had conducted experiments varying factors. As a result, the streaming electrification could see the changes according to flow velocity, oil temperature and insulation materials.

UHV변압기에서 유동대전에 의한 사고 방지에 관한 연구 (A Study on the Preventive Method of Accident by Streaming Electrification in UHV Transformer)

  • 박재윤;고희석
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제6권5호
    • /
    • pp.38-44
    • /
    • 1992
  • In this paper, electrification pipe modeled on the oil path that insulating oil flow in the high power transformer is manufactured in order to prevent the accident cause from streaming electrification generated when insulating off flow at a solid-liquid interface, and the streaming current is measured and analyzed according to the shape of oil path in electrification pipe. From the result of this study, the streaming current increases linearly with increasing of a oil velocity and it increases at lower temperature and decreases at higher temperature than [$46^{\circ}C$]. The smoother the flow of insulating oil is the more the streaming current decreases.

  • PDF

유로형상에 의한 절연지의 유동대전 특성 (Streaming Electrification of Pressbord by Oil Path Form)

  • 이동훈;최창락;박재윤;이충식;고희석;이덕출
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1995년도 추계학술대회 논문집
    • /
    • pp.332-335
    • /
    • 1995
  • Electrification pipe modeled on the oil path of the high power transformer is designed and manufactured. Distributions of oil flow velocity are simulated as spacer form in the electrification pipe. Streaming currents are investigated as each electrification pipe. The surface oil velocity of spacer is small the streaming current.

  • PDF

변압기유의 유동대전 현상에 관한 연구 (A Study on the Streaming Electrification Phenomena of the Transformer Oil)

  • 강성화;임기조;주상범;김명녕;강도열;김봉협
    • 대한전기학회논문지
    • /
    • 제39권6호
    • /
    • pp.568-576
    • /
    • 1990
  • Recently, streaming electrification in forced oil cooled power transformer has been taken up as a serious problem. In this paper, the charging tendency of various insulation oils, such as mineral oil, polybutene and silicone oil has been measured by means of an injection type charging tendency measuring apparatus under various condition. The experimental data of the dependence of the leakage current on flow velocity and temperature of oil can be explained by considering the flow state such as laminar and turbulent flow. The effect of additives on the charging tendency of mineral oil has been investigated. BTA is regarded as the most effective retardant to electrification of oil among the additives chose for this investigation.

  • PDF

유동대전된 절연유의 제전방식중 필터에 의한 영향 (The Effect of Filter in the Static Charge Elimination Methodes for Streaming-Electrification Insulating Oil.)

  • 정광현;김용운;신재화;김보열;이덕출
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1995년도 추계학술대회 논문집
    • /
    • pp.361-364
    • /
    • 1995
  • The static charges are generated by streaming electrification phenomena when insulating oil flowing by force for the purpose of cooling at the internal of Ultra-high power transformer. In this thesis, their elimination method was studied. The falter represents a greet much electrification characteristics because falter has large interfaces with liquid. In this paper, the streaming-electrification phenomena of insulating oil by metal filter were measured by mesh number, oil flow rate, oil temperature and a kind of mesh and The effect of charge elimination by metal filter generated minus ion was measured.

  • PDF

변압기 절연유의 순환 계통에서의 흐름 조건의 개선에 의한 유동대전현사의 완화 방법에 관한 연구 (A Study on the Method for Mitigation of Streaming Electrifiction by the Improvement of Flow Condition in the Oil Folw System of Transformer)

  • 권석두;남상천
    • 대한전기학회논문지
    • /
    • 제43권4호
    • /
    • pp.594-600
    • /
    • 1994
  • The maximum charge accumulation in transformers caused by streaming electrification is commonly observed on the bottom area of transformer winding(i.e.the oil inlet of transformer winding). It is because turbulent flows occur in this portion of transformers. Consequently, if we are to reduce the maximum charge accumulation of transformers, it is important that we should have a good understanding of the conditions of the occurence of partial turbulent flows in the oil inlet of transformer winding. With this point in mind, a simple flow model was designed in this study in order to simulate oil flow in the insulation ducts of power transformers. As a method for mitigating charge accummulation, attention was given to (a) a flow path design for the improvement of flow conditions, and (b) the charge tendency of the material used this design. The results of this study show that the above method is useful for mitigating charge accumulation.

  • PDF

파이프 재질에 따른 절연유의 대전및재전에 관한 연구 (A Study on the Streaming Electrification and Static Charge Elimination of Insulating Oil on Pipe Materials.)

  • 김용운;조영규;신용덕;정해덕;이덕출
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1993년도 춘계학술대회 논문집
    • /
    • pp.72-75
    • /
    • 1993
  • The characteristic of streaming electrification and static charge diminution in Cu, Fe and Sus pipes were investigated. The Cu and Fe pipes are charged positively, whereas the Sus pipes are charged negatively. Electrification rate in Cu and Fe pipes increases with increasing a pipe length for no-charged insulating oil. The electrification rate in Cu and Fe pipes abruptly increase with increasing the temperature and flow rate of insulating oil but decrease in Sus pipes. The current flows as a direction of insulating oil in all pipes.

  • PDF