Partial Discharge Measurements of High Voltage Rotating Machine Stator Windings (고압회전기 고정자 권선의 부분방전 측정)

  • Kim, Hee-Dong;Lee, Young-Jun;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1828-1830
    • /
    • 2003
  • Partial discharge(PD) tests are used to evaluate the insulation condition of stator windings in two 4.16kV and three 6.6kV motors. These tests were conducted using a conventional partial discharge detector(PDD) and turbine generator analyzer(TGA). Off-line PD measurements were performed on five high voltage motors. PD magnitudes ranged from 1000 pC to 5400 pC at the normal line-to-ground voltage. Five high voltage motors have been equipped with 80pF epoxy-mica coupler on the motor terminal box. The PD pulse from sensors were measured with the TGA instrument. TGA summarizes each plot with two Quantities such as the peak PD magnitude(Qm) and the total PD activity(NQN). The defect mechanisms of high voltage motor can be associated with PD patterns such as internal, slot and conductor surface discharges. The PDD and TGA test results of No. 4 motor showed that internal discharge was detected in voids of the groundwall insulation.

  • PDF

PD Diagnosis on 22.9kV XLPE Underground Cable using Ultra-wideband Sensor

  • Lwin, Kyaw-Soe;Lim, Kwang-Jin;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.3 no.3
    • /
    • pp.422-429
    • /
    • 2008
  • This paper presents compact low frequency ultra-wide band (UWB) sensor design and study of the partial discharge diagnosis by sensing electromagnetic pulse emitted from the partial discharge source with the newly designed UWB sensor. In this study, we designed a new type of compact low frequency UWB sensor based on microstrip antenna technology to detect both the low frequency and high frequency band of the partial discharge signal. Experiments of offline PD testing on medium voltage (22.9kV) underground cable mention the comparative results with the traditional HFCT as a reference sensor in the laboratory. In the series of comparative tests, the calibration signal injection test provided with the conventional IEC 60270 method and high voltage injection testing are included.

Partial Discharge Property of Hydrogenerator Stator Windings (수력발전기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.