• 제목/요약/키워드: National inpatient isolation units

검색결과 2건 처리시간 0.016초

국가지정 입원치료 격리병상 시설적격성 평가분석에 관한 연구 (A Study on the Facility Eligibility Inspection of National Inpatient Isolation Units)

  • 홍진관
    • 설비공학논문집
    • /
    • 제27권10호
    • /
    • pp.506-514
    • /
    • 2015
  • During the progression of this study, we visited 17 medical institutions. These medical institutions underwent inspection for facility eligibility of national inpatient isolation units to care for patients. Seventeen consultation meetings were held to gather expert opinions, and conferences were held with the medical institutions and local levels of government. Based on these facts, we established a field application model of the criteria of safety-management and conducted a study on this method in order to create more scientific and systematic safety-management criteria including criteria regarding facilities maintenance and methods of equipment inspection. According to an analysis on the 17 medical institutions examined, facility eligibility of 17 national inpatient isolation units was found to be 78.3% on average. Through analysis of the present domestic and foreign conditions of medical institutions, we proposed improvements for when remodeling becomes necessary and established criteria for safety-management in national inpatient isolation units for the care of patients in accordance with the domestic healthcare system.

국가지정 입원치료 격리병상 시설적격성 및 환경개선효과 분석에 관한 연구 (A Study on the Facility Eligibility Inspection & Effect of Environment Improvement for National Inpatient Isolation Units)

  • 이두루나;권순정;성민기;윤형진;홍진관
    • 의료ㆍ복지 건축 : 한국의료복지건축학회 논문집
    • /
    • 제23권4호
    • /
    • pp.67-75
    • /
    • 2017
  • Purpose: This study is for the facility eligibility and improvement evaluation analysis for the patient care environment of 7 facilities which has national inpatient isolation units. Methods: For the evaluation, first of all, the patient care environment of national inpatient isolation units are scrutinized by the checklist which is used on from 2014 with the 4 fields of criteria : architectural planning and layout, general requirement and condition for operating the negative pressured isolated patient room, HVAC system, and waste water discharging system. Finally, the evaluation results are compared with that of 2014. Results: The result shows that the average value of facility eligibility is 89.3 percent and which is 8.9 percent higher than the value before the MERS occurred. Implications: It is clear that facility remodeling of 7 institutions is being performed continuously, and the result of facility eligibility evaluation is reflected on design of a new 21 national inpatient isolation units those are going to be constructed from 2016. Therefore, it is expected that this study is used as a practical reference to establish the criteria of patient care environment management and safety management for both infectious disease outbreak and general service condition.