멀티존 시뮬레이션에 의한 공동주택의 미생물 오염원 확산과 제거에 관한 연구 (A Study on the Diffusion and Removal of Airborne Microorganism Pollution in Multistoried Apartment by the Multi-Zone Simulation)

  • 홍진관;최상곤
    • 설비공학논문집
    • /
    • 제19권4호
    • /
    • pp.291-298
    • /
    • 2007
  • The purpose of this study is to evaluate the efficacy of multizone simulation that enables to grasp of details about microbial contaminant problem in an multistoried apartment. We used actual indoor test data to figure up microbial contaminant level as initial value for the multizone simulation and estimated the various effects of indoor occupant infected with germs such as bacteria and fungus and the performance of air sterilization by using multizone simulation in substitute for infeasible experimental approach. The results show that natural ventilation make ourselves generally useful for removing indoor microbial contaminants. The results also show that the performance of air sterilization reach the maximum in the case of using mechanical ventilation and UVGI air sterilizer. The conclusion is that this multizone simulation is useful tool for actual design method for immune building systems.

생물안전밀폐시설에서 Multizone과 CFD 연동해석에 의한 실내기류 및 Influenza A 오염농도해석 (Applications of a Coupled Multizone and CFD Simulation to Validate Airflow and Influenza A Contaminant Dispersion in Biosafety Laboratory)

  • 황지현;홍진관
    • 설비공학논문집
    • /
    • 제26권12호
    • /
    • pp.588-593
    • /
    • 2014
  • To maintain a negative pressure, the supply, exhaust airvolume are adjusted by setting volume damper and the infiltration through leakage area of the door between rooms in biosafety laboratory. Multizone simulation is useful way to predict room pressure, supply and exhaust air volume. But in a particular room, local change such as airflow and contaminants concentration distribution can not be evaluated unfortunately. Through this study, a coupled multizone and CFD simulation was performed, indoor air flow and local contaminants concentration distribution in a particular room of BSL lab are predicted. The results show that all zones of BSL lab are well ventilated by unidirectional flow without local stagnation. In addition, in case that unexpected biohazard is occured in BSL lab, multizone simulation results about the spread of pollutants along movement of the occupant also show that contaminants concentration is removing totally without the spread of the outside. In conclusion, a coupled multizone and CFD simulation can be applied to interpret differential pressure in room and local change of physical quantity in a particular room such as airflow and Influenza A contaminants concentration distribution. This simulation method is useful to enhance the reliability and accuracy of biosafety laboratory design.

멀티죤 시뮬레이션에 의한 공동주택의 미생물 오염원제거 성능평가에 관한 연구 (The study on the Performance of air sterilization of multistoried apartment by the multizone modeling)

  • 최상곤;박경수;윤영수;홍진관
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.319-324
    • /
    • 2006
  • The purpose of this study Is to evaluate the efficacy of multizone simulation that enables to grasp of details about microbial contaminant problem in an multistoried apartment. We used actual indoor test data to figure up microbial contaminant level as initial value for the multizone simulation and estimated the various effects of indoor occupant infected with germs and the performance of air sterilization by using multizone simulation in substitute for infeasible experimental approach. The results show that natural ventilation make ourselves generally useful for removing indoor microbial contaminants. The results also show that the performance of air sterilization reach the maximum in the case of using mechanical ventilation and UVGI air sterilizer. The conclusion is that this multizone simulation is useful tool for actual design method for Immune building systems.

  • PDF

생물안전 3등급시설의 공기환경 예측 및 공조부하 절감에 대한 해석 (An Analytical Study on the Prediction of Indoor Air Quality and the Reduction of Air Conditioning Load in Bio Safety Level 3 Laboratory)

  • 홍진관;박현진
    • 설비공학논문집
    • /
    • 제24권11호
    • /
    • pp.813-822
    • /
    • 2012
  • In this study, the multizone simulation for biosafety of BSL3 lab. and energy simulation are carried out simultaneously by using linked model of CONTAM and TRNSYS. In BSL3 lab., annual energy consumption is approximately five to ten times more than the magnitude of the office building. This is because required air change rate is extremely large and it is difficult to maintain room pressure difference efficiently. To maintain pressure difference between laboratory rooms through sealing condition of doors and proper airflow control is significant. In this study, to predict indoor environment of the BSL3 lab.(Influenza A research lab.), the multizone simulation for four kinds of biohazard scenario is also performed as part of risk assessment. Multizone and energy simulation results by using linked model show that these approaches are used as a tool for the energy efficient design and operation method for the safer BSL3 lab. facilities.

멀티죤 시뮬레이션을 이용한 생물안전 3등급(BSL3)시설의 설계 검증에 관한 연구 (A Study on Verification for the Design of Bio Safety Level 3 Laboratory by using Multi-zone Simulation)

  • 이현우;최상곤;홍진관
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.745-750
    • /
    • 2009
  • In Korea, since the implementation of the GMO Law, the intrest of biosafety level 3(BL3) lab. is increasing. In this study, using CONTAM which is applying multizone modelling, the multizone simulation for design verification of BL3 lab. was performed. In BL3 lab., because required air change rate is greater than general estimated air-conditioning load and it is difficult to maintain room pressure difference efficiently, to maintain pressure difference between laboratory rooms is important through sealing condition of doors and proper airflow control of laboratory rooms. In this study, about BL3 lab.(M. tuberculosis research lab.), the multizone simulation for four kind of biohazard scenarios was performed in the case of unexpected spread of contaminants in the laboratory room, anteroom, corridor and inside of BSC. Multizone simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.

  • PDF

멀티죤 시뮬레이션을 이용한 생물안전 3등급(BSL3)시설의 설계 검증에 관한 연구 (A Study on Verification for the Design of Bio Safety Level 3 Laboratory by using Multi-zone Simulation)

  • 이현우;최상곤;홍진관
    • 설비공학논문집
    • /
    • 제21권12호
    • /
    • pp.671-677
    • /
    • 2009
  • In Korea, since the implementation of the LMO Law, the interest of biosafety level 3(BL3) lab. is increasing. In this study, using CONTAM which is applying multizone modelling, the multizone simulation for design verification of BL3 lab. is performed. In BL3 lab., because required air change rate is greater than general estimated air-conditioning load and it is difficult to maintain room pressure difference efficiently, to maintain pressure difference between laboratory rooms is important through sealing condition of doors and proper airflow control of laboratory rooms. In this study, about BL3 lab,(M. tuberculosis research lab.), the multizone simulation for four kind of biohazard scenarios is carried out in the case of unexpected spread of contaminants in the laboratory room, anteroom, corridor and inside of BSC. Multizone simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.

급배기 방식 개선에 따른 생물안전 밀폐시설의 Risk Assessment와 초기 건설비 저감에 대한 연구 (A Study on the Risk Assessment and Reduction of Initial Construction Cost in a Biosafety Laboratory According to Improvement of Supply and Exhaust Method)

  • 황지현;홍진관;주영덕
    • 설비공학논문집
    • /
    • 제25권10호
    • /
    • pp.534-539
    • /
    • 2013
  • In general, entire supply air of the BSL3 laboratory should be vented to the outside for its biosafety and the air conditioning system should always be operating to maintain a room pressure difference. In this regard, annual energy consumption is approximately five or ten times greater than the magnitude of the office building. In addition, to adjust room pressure difference to the set value efficiently, the supply and exhaust duct system are installed in each room of the BSL3 lab. Thus, initial construction cost is extremely high. In this study, multizone simulation is performed to estimate maintaining the appropriate room pressure difference in the case of changing model A (each room supply and exhaust system) to model B (each zone supply and exhaust system) for verification of the BSL3 lab biosafety. Also, in the case of these two models, the multizone simulation for three kinds of biohazard scenario is performed as part of risk assessment. The analysis of initial construction cost of two models is conducted for comparison. According to the studies, initial construction cost of model B is less than about 22% of existing model A. Moreover, biosafety of the BSL3 lab is still maintaining in the case of the two models.

생물안전 3등급(BSL3)시설의 생물재해 시나리오에 따른 실내 공기환경예측에 관한 연구 (A Study on the Prediction of Indoor Environment in Bio Safety Level 3 Laboratory According to Biohazard Scenario)

  • 박현진;홍진관
    • 설비공학논문집
    • /
    • 제22권11호
    • /
    • pp.745-750
    • /
    • 2010
  • Since the implementation of the LMO Law in Korea, the importance of the design qualification of BSL3 lab. is emphasizing. In this study, multizone simulation for three kind of biohazard scenarios using CONTAM is performed for design qualification of BSL3 lab. Also, in the case of unexpected spread of contaminants such as Influenza A virus(H1N1) in BL3 zone, the design qualification is carried out for diffusion and decontamination of contaminants according to differential pressure of BSL3 anteroom and door area of BSL3 lab. Also, in this study, appropriateness of laboratory room differential pressure and air flow rate to maintain pressure difference between laboratory rooms, and energy consumption due to air change rate variation according to door area in BL3 lab. Simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.

실내 미생물오염 전파방지를 위한 멀티죤 모델링에 관한 연구 (The study on the multizone modeling for preventing transmission of air borne contagion)

  • 최상곤;이현우;홍진관
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.429-435
    • /
    • 2006
  • In this study multi-zone modeling program CONTAM 2.4 which is developed by NIST is used for modeling the air disinfection system which is consist of dilution, filtration, ultra violet germicidal irradiation (UVGI) for removing the indoor microorganism such as bacteria and fungus. Developed models those protect occupants against indoor microorganism generated in our daily life are enable to use for immune building simulation tool. Also, results indicate that those models are enable to compute the real situation that is almost impossible of carrying out experiment and identify the disinfection rate with highly reliance. Results also suggest that engineers will use these models as a design tool for the immune building system.

  • PDF

Bioviolence Agents에 따른 건물내 미생물오염원의 효율적인 제거방안에 관한 연구 (A Study on the Effective Removal Method of Microbial Contaminants in Building According to Bioviolence Agents)

  • 이현우;홍진관
    • 설비공학논문집
    • /
    • 제22권12호
    • /
    • pp.881-890
    • /
    • 2010
  • As Influenza A virus(H1N1) has been spreading more rapidly around globe, the study on the airborne disease which is transimitted through the respiratory system is on the rise. In this study, the multizone simulation of the public building against bioviolence is performed in the case of unexpected spread of microbial contaminants, such as bioviolence agent, Influenza A, Smallpox, B. anthrax and transport and control characteristics of above three kinds of bioviolence agents are evaluted. Results suggest that Influenza A and Smallpox which has small mean diameter can be more removable than B. anthrax by using high UVGI grade condition and B. anthrax which has large mean diameter can be more removable than Influenza A and Smallpox by using high filter grade condition. Results also suggest that installing a combined air treatment system is more effective to reduce the damage and engineers will use immune building technology for removing the bioviolence agents effectively.