• 제목/요약/키워드: Multi type heat pump system

검색결과 31건 처리시간 0.019초

멀티형 히트펌프 시스템 컴퓨터 시뮬레이션과 실험적 검증 (Multi type heat pump system computer simulation and experimental verification)

  • 한도영;정민영
    • 설비공학논문집
    • /
    • 제12권1호
    • /
    • pp.12-19
    • /
    • 2000
  • The multi type heat pump system may provide more energy savings and better environmental conditions than the single type heat pump system may do. In order to design a multi type heat pump system, it may be recommended to develop the system simulation program, which can predict the characteristics of the system such as unit capacities, power consumptions, and system COP's. In this study, the steady state simulation program of the multi type heat pump system was developed. The results from the simulation program were compared with those from the experimental tests which were performed in the environmental chamber, Cooling tests show 3.11% and 0.94% of error in capacity and COP, and heating tests show 3.30% and 1.90% of error in capacity and COP, respectively. Therefore, the steady state simulation program developed for this study can effectively be used for the design and the performance prediction of the multi type heat pump system.

  • PDF

모세관을 이용한 멀티형 열펌프의 신뢰성에 관한 실험적 연구 (An Experimental Stuff on the Performance of Multi-type Heat Pump using Capillary Tubes)

  • 권영철;장근선;이윤수;김대훈;전용호;이상재
    • 설비공학논문집
    • /
    • 제14권9호
    • /
    • pp.749-755
    • /
    • 2002
  • In order to develop a multi-type heat pump system with two indoor units of non-uniform capacities, the optimum refrigerant circuit was developed using capillary tubes. The refrigerant circuit was composed of four main parts, a heating circuit, a cooling circuit, a by-pass circuit and a balance circuit. The system characteristics of multi-type heat pump was investigated through the rating test and the reliability test, using the multi-type psy-chrometric calorimeter. The results of the rating test showed that the capacity of the multi-type heat pump was about 93% of the design value. In particular, the capacity of cooling single mode was about 13% higher than the design value, and the capacity of heating multi mode was about 5% higher than the design value. The reliability of the multi-type heat pump was verified by various reliability tests (overload, extension tube, freeze up, under/over charging, sweat, flood back). The optimal amount of refrigerant charge and compressor capacity were determined from the present work.

퍼지룰을 이용한 멀티형 히트펌프 시스템의 제상 제어 (Fuzzy Defrost Control of the Multi-Type Heat Pump System)

  • 한도영;김경훈
    • 설비공학논문집
    • /
    • 제12권8호
    • /
    • pp.711-716
    • /
    • 2000
  • A fuzzy defrost control algorithm for the multi-type heat pump system was developed. In the fuzzy defrost control algorithm, the air temperature difference at the outdoor unit and the refrigerant pressure difference at the compressor were used as input variables, and the defrost starting time and the defrost time interval were used as output variables. This fuzzy algorithm was applied to the multi-type heat pump system and tested in the five dynamic environmental chambers. Test results show that the newly developed control algorithm is more effective than the conventional control algorithm in the removal of frost formed at the outdoor unit of the heat pump.

  • PDF

3실형 인버터 열펌프 시스템의 냉방성능 측정 (Cooling Performance Measurement of a 3 Room Type Inverter Heat Pump System)

  • 정광진;최영돈;장효환;송재복;박윤철
    • 설비공학논문집
    • /
    • 제13권6호
    • /
    • pp.431-439
    • /
    • 2001
  • Recently, multi-room type heat pump system has aroused much attention, because it can achieve much reduction of installation cost and space as well as energy saving in companion with the single room type heat pump system. In the present study, performance characteristics of a 3 room type inverter driven heat pump system, which is widely spread in Japanese market, are measured.. In the single room operation, performances of a heat pump system such s the difference of compressor outlet and inlet pressures and the mass flowrate may increase with the increase of cooling capacity so that COP of the system decrease with the increase of cooling capacity. However, in the 2 room operation, mass flowrate and COP of the total system increase markedly as compared with the single room operation.

  • PDF

Simulation Program Verification and Performance Prediction of the Multi-type Heat Pump System

  • Han, Do-Young;Park, Kwan-Jun;Lee, Han-Hong
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제9권4호
    • /
    • pp.47-54
    • /
    • 2001
  • The simulation program which can predict major performances of the multi-type heat pump system was developed. In order to verify the simulation program, several experimental tests were performed under various recommended conditions. The experimental results show in good agreement with simulation results. The verified simulation program was used to analyze the system performance. The capacities and the COP's under the various indoor and outdoor conditions were predicted. Therefore, it may be concluded that the system simulation program developed in this study may be effectively used for the system design and the performance prediction of the multi-type heat pump system.

  • PDF

PID 제어를 이용한 멀티형 열펌프의 용량조절 (Capacity Modulation of a Multi-Type Heat Pump System Using PID Control)

  • 정대성;김민성;김민수;이원용
    • 설비공학논문집
    • /
    • 제12권5호
    • /
    • pp.446-475
    • /
    • 2000
  • Performance of a water-to-water multi-type heat pump system using R22 has been experimentally investigated. Total refrigerant flow rate was adjusted with a variable speed compressor and the refrigerant flow rate for two indoor units were controlled by electronic expansion valves. Evaporator outlet pressure of refrigerant and indoor unit outlet temperatures of secondary fluid were selected as controlled variables. Experiments were carried out for both cooling and heating modes using PID control method. Results show that the multi-type heat pump system can be adequately controlled by keeping control gains at certain levels for various operating conditions.

  • PDF

퍼지 로직 적용 PID 제어를 이용한 멀티형 열펌프의 용량조절 (Capacity Modulation of a Multi-Type Heat Pump System using PID Control with Fuzzy Logic)

  • 김세영;김민수
    • 설비공학논문집
    • /
    • 제13권9호
    • /
    • pp.810-817
    • /
    • 2001
  • Performance of a water-to-water multi-type heat pump system using R22 which has tow indoor units has been investigated experimentally. The refrigerant flow rate of each indoor unit was regulated by an electronic expansion valve and the total refrigerant flow rate of the system was controlled by a variable speed compressor. In the system, evaporator outlet pressure of refrigerant and outlet temperatures of secondary fluid from indoor units were selected as control variables. Experiments were executed for both cooling and heating modes using PID control method with fuzzy logic, and results of the test are compared with a classical PID method. In the case of PID control with fuzzy logic, the fuzzy control rules corrects PID parameters each time. Results show that PID control with fuzzy logic has the merits of quick response and reduced overshoot.

  • PDF

멀티형 인버터 열펌프의 냉방성능해석에 관한 연구 (Performance Analysis of a Multi-type Inverter Heat Pump)

  • 김영철;박근우;윤영;민만기;최영돈
    • 설비공학논문집
    • /
    • 제13권3호
    • /
    • pp.153-159
    • /
    • 2001
  • A system simulation program was developed for a multi-type inverter heat pump. Electronic expansion valve(EEV) was used to extend the capacity modulating range of the heat pump as expansion device. The program was also developed to calculate actual system performance with the building load variation with climate during a year. The performance variation of a multi-type hat pump with two EEV and an inverter compressor was simulated with compressor speed, capacity, and flow area of the EEV. As a result, the optimum operating frequency of the compressor and openings of the expansion device were decided at a given load. As compressor speed increased, he capacity of heat pump increased, the capacity of heat pump increased. Therefore flow area of EEV should be adjusted to have wide openness. Thus the coefficient of performance(COP) of the heat pump decreased due to increasement of compressor power input. The maximum COP point at a given load was decided according to the compressor speed. And under the given specific compressor speed and the load, the optimum openings point of EEV was also decided. Although the total load of indoor units was constant, the operating frequency increased as the fraction of load in a room increased. Finally ad the compressor power input increased, the coefficient of performance decreased.

  • PDF

지열원 물대공기 멀티 히트펌프의 일일 난방 운전 특성에 관한 실증 연구 (Daily Heating Performance of a Ground Source Multi-heat Pump at Heating Mode)

  • 최종민;임효재;강신형;문제명;김록희
    • 설비공학논문집
    • /
    • 제21권9호
    • /
    • pp.527-535
    • /
    • 2009
  • The aim of this study is to investigate the daily heating performance of ground source multi-heat pump system with vertical single U-tube type GLHXs, which were installed in a school building located in Cheonan. Daily average COP of heat pump unit on Jan. 12th, 2009 at heating mode was lower than it on Nov. 10th, 2008 and Dec. 15th, 2008, because of lower EWT of the outdoor heat exchanger and relatively smaller size of condenser and evaporator. But, the system COP on the former was higher than it on the latter because ground loop circulating pump was operated in rated speed. It is suggested that the new algorithms to control the flow rate of secondary fluid for GLHX according to load change have to be developed in order to enhance the performance of the system COP.