• 제목/요약/키워드: Multi evaporator

검색결과 82건 처리시간 0.027초

다중 유로에서 과열도의 불균형에 따른 증발기의 성능 특성에 관한 연구 (The Effect of Non-uniform Superheat on the Performance of a Multi-path Evaporator)

  • 최종민;김용찬
    • 설비공학논문집
    • /
    • 제15권12호
    • /
    • pp.1043-1048
    • /
    • 2003
  • An experimental investigation was executed to determine the capacity degradation due to non-uniform refrigerant distribution in a multi-path evaporator. In addition, the possibility of recovering the capacity reduction by controlling the refrigerant distribution among refrigerant paths was assessed. The finned-tube evaporator, which had a three-path and three-depth-row, was tested by controlling inlet quality, exit pressure, and exit superheat for each refrigerant path. The capacity reduction due to superheat unbalance between each path was as much as 30%, even when the overall evaporator superheat was kept at a target value of 5.6$^{\circ}C$. It may indicate that the internal heat transfer within the evaporator assembly caused the partial capacity drop. For the evaporator having air mal-distributions, the maximum capacity reduction was found to be 8.7%. A 4.5% capacity recovery was obtained by controlling refrigerant distribution to obtain the target superheat at the outlet of each path.

멀티형 공조/냉동시스템의 증발기 과열도 제어 (Evaporator Superheat Control of a Multi-type Air-conditioning/Refrigeration System)

  • 김태섭;홍금식;손현철
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집B
    • /
    • pp.712-717
    • /
    • 2001
  • This paper investigates the control problem of evaporator superheat, i.e., the difference between the temperature of the refrigerant at the entrance region of an evaporator and that at the exit region, for multi-type air-conditioning/refrigeration systems. Mathematical equations describing the characteristics of compressor, condenser, evaporator, and electronic expansion valve are first derived. Then, the transfer functions from the current input of the electronic expansion valve to wall temperatures of evaporator tube at two-phase region and superheated region, respectively, are derived. The stability and performance of the closed loop system with a PI controller are analyzed by Nyquist stability criterion. Simulation results are provided.

  • PDF

핀의 전도 열전달 및 과열도 변화에 따른 증발기 성능 특성에 관한 연구 (Effects of Fin Conduction and Superheat Unbalance on the Performance of an Evaporator)

  • 최종민;김용찬
    • 설비공학논문집
    • /
    • 제17권3호
    • /
    • pp.216-222
    • /
    • 2005
  • An experimental investigation was executed to determine the capacity degradation due to fin conduction and non-uniform refrigerant distribution in a multi-path evaporator with cross-counter flow. The finned-tube evaporator, which had a three-path and three-depth-row, was tested by controlling inlet quality, exit pressure, and exit superheat for each refrigerant path. The capacity reduction due to superheat unbalance between each path was as much as $25\%$ for non-cutting evaporator, even when the overall evaporator superheat was kept at a target value of $5.6^{\circ}C$. It indicates that the internal heat transfer within the evaporator assembly causes the partial capacity drop. The capacity of cutting-evaporator with respect to non-cutting evaporator was enhanced according to the increment of air flow rate when superheat or superheat unbalance increased.

Fuzzy Clustering 기법을 이용한 Multi-Evaporator Vapor Compression Cycle의 적정 냉매량 판정에 관한 연구 (Studies on Correct Refrigerant Amount Detection for Multi-Evaporative Vapor Compression Cycle using Fuzzy Clustering)

  • 김성환;최창민;권기백;정백영
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.459-464
    • /
    • 2009
  • This study has been conducted on how to determine the multi-evaporator vapor compression cycle system is charged correctly by using sensor readings which are used to control system. In this paper, the characteristics of the multi-evaporator were presented and sensor values were classified using fuzzy clustering. finally classification logic and it's performance were discussed by applying commercial VRF system.

  • PDF

멀티형 공조시스템의 증발기 과열도에 관한 실험적 연구 및 냉매유량 제어 (Experimental Study of the Superheat and Control of the Refrigerant Flow-Rate in the Evaporator of a Multi-type Air-Conditioning System)

  • 김태섭;홍금식;손현철
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2000년도 제15차 학술회의논문집
    • /
    • pp.221-221
    • /
    • 2000
  • The heat exchange part in a modern multi-type air-conditioning system employs multiple-pass heat exchangers. The heat-transfer performance of an each pass in such an exchanger depends strongly on the length of the two-phase region and the mass flow of the refrigerant. The total length and diameters of the pipes, the exit conditions, and the arrangement of each pass as well as the geometrical shape of the distributor at the branching sections are considered to be major factors affecting the heat-transfer performance. The refrigerant commonly used in these systems is HCFC-22. The two objectives of this paper are to investigate the characteristics of the refrigerant flow rate and the superheat in the evaporator of a multi-type air-conditioning system for a single or simultaneous operating conditions and to control the superheat and the refrigerant flow rate of the evaporator.

  • PDF

평판핀이 부착된 증발기의 시뮬레이션 (Numerical Simulation of Plate Finned-Tubes Evaporator)

  • 손병진;민묘식;최상경
    • 설비공학논문집
    • /
    • 제1권4호
    • /
    • pp.297-304
    • /
    • 1989
  • Development of a more satisfactory program of computing the performance on a multi-tube evaporator with continuous plate fins is attempted in this study. The fluid flow involving a change of phase make the flow properties and fluid friction factor of refrigerants, the heat transfer coefficients of refrigerant and air sides vary significantly. Taking such variations into account, a useful program is developed to predict the steady state performance of a multi-tube evaporator. The program was applied to an evaporator which has outside diameter of 10.05mm, inside diameter of 9.35mm, length of 5.4m and two rows arraied staggered. Then the variations of refrigerant quality, temperature, pressure, velocity, enthalpy, specific volume and air temperature, tube temperature were discussed. Satisfactory results were presented that the degree of superheat at the outlet side was $4.4^{\circ}C$ and the air temperature drop between the inlet and outlet of the air conditioner was $10^{\circ}C$.

  • PDF

멸티형 공조/냉동시스템의 증발기 과열도 제어 (Evaporator Superheat Control of a Multi-type Air-Conditioning/Refrigeration System)

  • 김태섭;홍금식;손현철
    • 에너지공학
    • /
    • 제10권3호
    • /
    • pp.253-265
    • /
    • 2001
  • 본 논문은 멀티형 공조/냉동시스템의 증발기의 과열도(증발기 2상영역과 출구영역의 냉매기 온도차)제어를 위한 모델링과 PI제어에 관한 연구이다. 먼저, 제어기 설계를 목적으로 하여 압축기, 응축기, 증발기 그리고 전자식 팽창밸브의 동특성이 수학적으로 모델링된다. 증발기에서의 일정한 크기의 과열도 발생을 제어목적으로 한정한 후 전자식 팽창밸브의 전류입력으로부터 증발기의 2상영역과 과열영역에서의 관벽의 온도로의 전달함수들이 유도된다. 비례적분 제어기의 폐루프시스템의 안정성과 제어성능은 Nyquist 안정성 판별법에 의해 분석된다. 시뮬레이션 결과가 제시된다.

  • PDF

MED 담수기내 수평관 강하막식 증발기의 3D 수치해석적 연구 (3D Numerical Study of Horizontal Falling Film Evaporator in Multi Effect Distillation (MED) Plant)

  • 김수재;제준호;김무환
    • 대한기계학회논문집B
    • /
    • 제37권5호
    • /
    • pp.513-522
    • /
    • 2013
  • 본 연구에서는 다중효용 증발식 담수기에 쓰이는 강하막식 증발기의 수치해석을 수행하였다. 증발기에 사용되는 다관군을 다공성 매질로 묘사하고 공간평균 개념을 적용하였다. 증발기 내부의 유동계산 및 열 전달로 인한 상변화를 계산하기 위해서 FLUENT 와 UDF 가 사용되었다. 작동조건에 대한 증발기의 성능변화를 살펴보기 위해 수평관 내 증기 질량 유속을 $0.5{\sim}2.5kg/m^2s$, 관내입구 측 비 응축성 기체의 질량분율을 0~1%, 그리고 수평관 외 뿌려지는 강하막의 액막 레이놀즈 수를 100~1000 으로 바꾸어가며 해석을 수행하였다. 관내 증기유속 및 관외 강하막 레이놀즈 수가 증가할수록 증발량은 증가하였으며, 관내 비 응축성 기체의 질량분율이 1%증가함에 따라 증발량이 0.87%줄어들었다.

MF증발기 기초 형상 설계에 관한 연구 (A Study on the Basic Shape of an MF Evaporator)

  • 박용석;성홍석;서정세
    • 한국기계가공학회지
    • /
    • 제18권6호
    • /
    • pp.39-44
    • /
    • 2019
  • The evaporator is a key driver of an air conditioning system's efficiency. In this study, we study methods of maximizing the efficiency of a Massey Ferguson (MF) evaporator by measuring how the cooling performance of different shapes vary with temperature. We varied the tube insertion depth as well as the shape of the evaporator's header and tube. When we compare header shapes of "D", "Ellipse", and "Quadrangle" types, we find that the elliptical header creates the smallest pressure loss and the highest temperature difference. Between tube shapes of "Rectangular", "Projection", and "Circular" types, the "Projection" type tube creates the most temperature difference. We also investigated the depth of tube insertion in the header and find that tube insertion of 5 - 10 mm is feasible; we selected the depths of 5, 7, and 10 mm since they corresponded to approximately 30%, 50%, and 70% of the total width of the header. The tube insertion test demonstrated that a tube insertion depth of 7 mm creates the least pressure loss and the highest temperature difference. In conclusion, the optimal evaporator design uses an "Ellipse" type header, "Projection" type tube, and a tube insertion depth between 30 and 50% of the header width.

태양에너지 해수담수화를 위한 3중 효용 증발식 담수기 개발 (Development of 3th Effects Evaporative desalination system for Solar Desalination System)

  • 황인선;주홍진;윤응상;곽희열
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.201-201
    • /
    • 2010
  • The evaporative desalination system with solar energy would be the efficient and attractive method to get fresh water. This study was described the development of Multi Effect Distillation(MED) with solar energy desalination system. The system was designed and manufactured Multi effect distillation on the capacity of $3m^3$/day. The experimental apparatus consists mainly of ejector pump, Hot water pump, flow meter, demister, cooler, evaporator and condenser. Evaporator and condenser were made Shell&Tube Heat Exchanger type with corrugated tube. The experimental variables were chosen $75^{\circ}C$ for hot water inlet temperature, 40, 60 and $80{\ell}$/min for hot water inlet volume flow rate, 6.0 and $8.0{\ell}$/min for evaporator feed seawater flow rate, $18^{\circ}C$ for sea water inlet temperature to cover the average sea water temperature and the salinity of sea water is measured about 33,000 PPM (parts per million). for a year in Korea. This study was analyzed the results of thermal performance of Multi Effect Distillation. The results are as follows, The experimental Multi effect distillation is required about 40 kW heat source for production of $3m^3$/day fresh water. Various operating flow rate was confirm in the experiments to get the optimum design data and the results showed that the optimum total flow was $8.0{\ell}$/min. Comparison of Single Effect Distillation with Multi Effect Distillation showed MED is at least more than double of SED.

  • PDF